background image

INTRODUCTION

HOW TO USE THIS MANUAL

I-E96-435A   

1 - 3

HOW TO USE THIS MANUAL

Read this manual before handling the TM. Refer to the sections
in this list as needed for more information.

1. Read 

Section 2

 before connecting the NIAI03.

2. Refer to 

Appendix A

 for the IMASM03/04 slave module.

3. Refer to 

Section 3

 for the maintenance schedule.

4. Refer to 

Section 4

 and 

Section 5

 when needed.

GLOSSARY OF TERMS AND ABBREVIATIONS

Table 

1-1

 contains the glossary of terms for this manual.

REFERENCE DOCUMENTS

Table 

1-2

 contains the reference documents for the NIAI03.

Table 1-1.  Glossary of Terms and Abbreviations

Term

Definition

Analog

Continuously variable as opposed to discretely variable.

RTD

Resistance temperature detector. A sensing device that changes resistance with 
changes in temperature.

Slave Module

One of a series of modules designed to perform high or low level operations as 
directed by a master module.

TM

Termination Module. Provides input/output connection between plant equipment and 
the INFI 90/Network 90

®

 modules.

TMU

Termination Mounting Unit. A card cage that provides housing for INFI 90/Network 
90 termination modules.

Table 1-2.  Reference Documents

Document 

Number

Description

I-E96-205

Analog Master Module and Analog Slave Modules (IMAMM03 and IMASM01/ 02/03/
04)

I-E96-500

Site Planning and Preparation

® Registered trademark of Elsag Bailey Process Automation.

Содержание Infi 90 NIAI03

Страница 1: ... Process Control and Automation Solutions from Elsag Bailey Group E96 435 RTD Analog Input Termination Module NIAI03 ...

Страница 2: ...MENTS ÉLECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FRÉQUENCE RADIO DES PRÉCAUTIONS DEVRONT ÊTRE PRISES LORS DE L UTILISATION DU MATÉ RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PRÉCAUTIONS À PRENDRE DANS CE CAS SOIENT SIGNALÉES AUX ENDROITS VOULUS DANS VOTRE USINE PERTURBATIONS DU PROCÉDÉ L ENTRETIEN DOIT ÊTRE ASSURÉ PAR UNE PERSONNE QUALIFIÉE EN CONSIDÉRANT L ASPECT SÉCURITAIRE...

Страница 3: ...put Termination Module NIAI03 interfaces RTD inputs to the Analog Input Slave Module IMASM03 04 This manual explains how to install and use the NIAI03 on the INFI 90 system It has sections that describe the setup and cabling The appendix contains information about the IMASM03 04 module Registered trademark of Elsag Bailey Process Automation ...

Страница 4: ...1 through 4 2 Original 5 1 Original A 1 Original Index 1 Original When an update is received insert the latest changed pages and dispose of the super seded pages NOTE On an update page the changed text or table is indicated by a vertical bar in the outer mar gin of the page adjacent to the changed area A changed figure is indicated by a vertical bar in the outer margin next to the figure caption T...

Страница 5: ...lling or removing a cable assigned to that slot Failure to do so could result in damage to the module p 2 3 4 1 If input or output circuits are a shock hazard after disconnecting sys tem power at the power entry panel then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist p 2 4 4 1 It is strongly recommended...

Страница 6: ... emplacement Un manquement à cette procédure pourrait endom mager le module p 2 3 4 1 Si des circuits d entree ou de sortie sont alimentes a partir de sources externes ils presentent un risque de choc electrique meme lorsque l alimentation du systeme est debranchee du panneau d entree l alimentation Le cas echeant un avertissement signalant la presence de sources d alimentation multiples doit etre...

Страница 7: ...IAL HANDLING 2 1 UNPACKING AND INSPECTION 2 2 SETUP PHYSICAL INSTALLATION 2 2 Cable Installation 2 2 Termination Module Installation 2 3 Terminal Wiring 2 4 Power Wiring 2 5 SECTION 3 MAINTENANCE 3 1 INTRODUCTION 3 1 MAINTENANCE SCHEDULE 3 1 SECTION 4 REPAIR REPLACEMENT PROCEDURES 4 1 INTRODUCTION 4 1 REPLACEMENT PROCEDURES 4 1 SECTION 5 SUPPORT SERVICES 5 1 INTRODUCTION 5 1 REPLACEMENT PARTS AND ...

Страница 8: ... Nomenclature 1 4 1 4 Specifications 1 4 2 1 NIAI03 Cable Applications 2 2 3 1 Maintenance Schedule 3 1 A 1 Address Switch Settings SW1 A 1 List of Figures No Title Page 1 1 Application Example for NIAI03 1 2 2 1 Cable Connections for NIAI03 2 2 2 2 Terminal Assignments for NIAI03 2 5 A 1 Address Select Switch SW1 A 1 ...

Страница 9: ...PTION The NIAI03 is a single printed circuit board that uses one slot in a Termination Module Mounting Unit NTMU01 02 The termination module TM has one card edge connector that connects to the slave module through a cable The terminal blocks for field wiring are on the TM The NIAI03 handles up to eight three wire RTD inputs for the IMASM03 04 Figure 1 1 shows an application example for the NIAI03 ...

Страница 10: ...before applying power Maintenance Provides a maintenance schedule Repair Replacement Procedures Details how to replace a TM Support Services Describes the support services repair parts training docu mentation etc available from Bailey Controls Company Appendix A Shows the board layout and cabling for the Analog Slave Mod ule IMASM03 04 Figure 1 1 Application Example for NIAI03 COMMUNICATION HIGHWA...

Страница 11: ...d Abbreviations Term Definition Analog Continuously variable as opposed to discretely variable RTD Resistance temperature detector A sensing device that changes resistance with changes in temperature Slave Module One of a series of modules designed to perform high or low level operations as directed by a master module TM Termination Module Provides input output connection between plant equipment a...

Страница 12: ...unting Slides into a single slot in NTMU01 02 Environmental Electromagnetic Radio Frequency Interference Ambient Temperature Relative Humidity Atmospheric Pressure Air Quality No values available at this time Keep cabinet doors closed Do not use communication equipment closer than 2 meters from the cabinet 0o to 70o C 32o to 158o F 5 to 90 5 up to 55o C 131o F noncondensing 5 to 40 5 up to 70o C 1...

Страница 13: ...dules Static discharge may damage MOS devices on modules in the cabinet Use grounded equipment and static safe practices when working with modules 1 Use Antistatic Bag Keep the modules in the antistatic bag until you are ready to install them in the system Save the bag for future use 2 Ground Bags Before Opening Before opening a bag containing an assembly with CMOS devices touch it to the equipmen...

Страница 14: ...lains how to configure and install the NIAI03 The required procedures are installing the termination module into the TMU and connecting the field wiring and communica tion cables Cable Installation The NKTU02 12 and NKTM01 cable connects the NIAI03 to the IMASM03 04 slave module Figure 2 1 shows the cabling for the NIAI03 to the IMASM03 04 Table 2 1 lists the NIAI03 cable applications Figure 2 1 C...

Страница 15: ...to the NIAI03 module The cable should latch securely in place Card edge connector P1 of the NIAI03 module connects to this end of the cable 6 Replace or add the cable retaining bracket if round type cables NKTU02 12 are installed in the TMU Termination Module Installation The NIAI03 inserts into a standard INFI 90 termination mount ing unit TMU and occupies one slot To install 1 Verify slot assign...

Страница 16: ...wer entry panel then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist ATTENTION Si des circuits d entree ou de sortie sont alimentes a partir de sources externes ils presentent un risque de choc electrique meme lorsque l alimentation du systeme est debranchee du panneau d entree l alimentation Le cas echean...

Страница 17: ...rom the I O common bus bar on the TMU power bus bar to the TB1 terminal on the TM marked COM 5 Insert the module until it locks securely into place 6 Replace the front cover The NIAI03 is ready for operation if 1 The circuit board is mounted in the termination mounting unit 2 All required cables are connected to the termination module 3 All required field wires are connected to the termination mod...

Страница 18: ...maintenance schedule MAINTENANCE SCHEDULE Execute the tasks in Table 3 1 at the specified intervals Table 3 1 Maintenance Schedule Task Interval Clean and tighten all power and grounding connections Every 6 months or during plant shutdown whichever occurs first Use a static safe vacuum cleaner to remove dust from Termination Mounting Unit Termination Modules ...

Страница 19: ... Le cas echeant un avertisse ment signalant la presence de sources d alimentation multiples doit etre appose sur la porte de l armoire CAUTION It is strongly recommended that all power cabinet I O etc be turned off before doing any termination module wiring Failure to do so could result in equipment damage Do not apply power until all connections are verified ATTENTION Ll est fortement recommande ...

Страница 20: ...ring from the termi nal blocks 4 Slide the TM out of the cabinet 5 Slide the new TM into the same slot as the module that was removed 6 Connect all field and power wiring removed in Step 3 7 Verify that wiring and cabling to the TM is correct 8 Fully insert the termination module into the TMU 9 Replace the termination module front cover 10 Turn on the cabinet power supply that provides power to th...

Страница 21: ...on part number and quantity 2 Model and serial numbers if applicable 3 Bailey instruction manual number page number and refer ence figure that identifies the part Order parts without commercial descriptions from the nearest Bailey Controls Company sales office TRAINING Bailey Controls has a modern training facility available for training your personnel On site training is also available Con tact a...

Страница 22: ...n on the IMASM03 04 and its settings This information is provided as a quick reference guide for person nel installing the NIAI03 Figure A 1 shows the address select switch SW1 Table A 1 lists the binary addresses for setting SW1 Refer to the IMAMM03 instruction for more detailed information to install and configure the slave Figure A 1 Address Select Switch SW1 Table A 1 Address Switch Settings S...

Страница 23: ...schedule 3 1 N NIAI03 cable applications 2 2 Nomenclature 1 4 R Reference documents 1 3 Replacement parts 5 1 Replacement procedures 4 1 S Setup physical installation 2 2 Setup physical installlation Cable installation 2 2 Power wiring 2 5 Terminal module installation 2 3 Terminal wiring 2 4 Special handling 2 1 Specifications 1 4 T Technical documentation 5 1 Terminal assignments for NIAI03 2 5 T...

Страница 24: ... 8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefax 39 10 6582 941 GERMANY Graefstrasse 97 D 60487 Frankfurt Main Germany Telephone 49 69 799 0 Telefax 49 69 799 2406 Form I E96 435A Litho in U S A 692 Copyright 1992 by Elsag Bailey Process Automati...

Отзывы: