SECTION 4 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
This section explains the replacement procedures for the
NIAC03 Analog Input Calibration Module. No special tools are
required to replace the module.
REPLACEMENT PROCEDURES
If an NIAC03 module is faulty, replace it with a new one.
Do
not
try to repair the module. Replacing components may affect
performance and certification.
To replace an NIAC03 calibration module:
1. Remove (pull straight off) the calibration module front
cover.
2. Slide the calibration module out of the cabinet.
3. Slide the new calibration module into the same slot as the
module that was removed.
4. Verify that cabling to the calibration module is correct.
5. Fully insert the calibration module into the TMU card cage.
6. Replace (snap on) the calibration module front cover.
CAUTION
Remove modules from their module mounting unit slots before
installing or removing a cable assigned to that slot. Failure to
do so could result in damage to the module.
ATTENTION
Retirer le module de son emplacement dans le chassis de
montage des modules avant d'installer ou de retirer un cable
assigne a cet emplacement. Un manquement a cette procedure
pourrait endommager le module.