INSTALLATION
INIIL02 INFI-NET TO INFI-NET LOCAL INTERFACE INSTALLATION
3 - 22
I-E96-607A
®
HW SETUP DIPSHUNT
The HW SETUP dipshunt is factory installed. There should be a
jumper installed in the second dipshunt position (i.e., pin two
is shorted to pin 15). Verify that the jumper is installed in the
correct position. The INIIT03 module will not operate properly
if this dipshunt position is open. All other dipshunt positions
should be open.
INIIL02 Interface Module Mounting Unit Preparation
The INIIL02 INFI-NET to INFI-NET Local Interface requires a
dedicated module mounting unit. If the module mounting unit
is part of an older system, it must be checked for -30 VDC. The
next three subsections explain how to check the module
mounting unit for -30 VDC, INIIT03 installation options avail-
able for systems that use -30 VDC, and how to isolate the MMU
card cage for the INIIL02 interface.
Do not
attempt to install
Table 3-12. INIIT03 Jumper Settings for J1, J2, J4 and J5
Jumper
Setting
Function
User Setting
J1
1
Vertical
Sets the RS-232-C diagnostic port (P4) to operate as
DCE.
Horizontal
Sets the RS-232-C diagnostic port (P4) to operate as
DTE.
J2
4-3
Factory setting.
Shorted
4-2
Not used.
Open
4-1
Not used.
Open
J4
Open
MFT disable jumper. This jumper must remain open for
normal operation.
Open
J5
2
30 V
Disconnects Controlway for operation in module mount-
ing units that have -30 VDC (early Network 90).
MODB
Connects Controlway channel B for operation in module
mounting units that have Controlway (INFI 90).
NOTES:
1.This feature is used by Bailey service personnel. The J1 setting does not affect the module during normal operation.
2.Refer to
for an explanation of the installation options available when installing the INIIL02 interface in
a system that uses -30 VDC.
CAUTION
To avoid potential module damage, evaluate your system for
compatibility prior to module installation. This module uses
connections to the module mounting unit backplane that
served other functions in early Network 90 systems.
ATTENTION
Pour éviter d'endommager des modules, évaluez la compatibil-
ité de votre système avant de les y brancher. L'uage que fait ce
module de certianes connexions au fond de panier du châssis
de montage diffère de l'assignation prévue par le système Net-
work 90 original.