REMOTE LINK (NIRL03) TERMINATION MODULE CONFIGURATION
CABLE TERMINATION
I-E96-317A
B - 3
Table B-4. NIRL03 Terminal Assignments
TB1
Terminal
Assignment
TB2
Terminal
Assignment
TB3
Terminal
Assignment
1
2
3
Ground
Common
+ 24 VDC
4
5
6
7
8
9
10
DCS (+)
DCS (-)
Expander Bus
Disable Out
Expander Bus
Disable In
Out (-)
Out (+)
Shield
25
26
27
In (-)
In (+)
Shield
NOTE: There are three Terminal Blocks (TB) on the NIRL03. TB1, located at the bottom of the board, is numbered 1 through 3. TB2, located
just above TB1, is numbered 4 through 11 (11 not used). TB3, located above TB2, is numbered 25 through 32 (28 through 32 not used).
Figure B-2. Cable Connections for the NIRL03
LOCAL IMRIO02
REMOTE IMRIO02
NCIS02
P3
P3
P3
NKTU02
NIRL03
NICS01
NIDS01
NKTD01
NOTE: COAX CABLE (IN PLACE OF NKPL01):
NIRL03
NIRL03
NKTL01
NKTL01
NKCL01
NKTU02
RIBBON CABLE
6634408
NKTD02
NKCS01
TB1
TB2
J4
J1
J1
ICS
J2
TB3
TB3
NKTD02
IISAC01 WITHOUT BYPASS
IISAC01 WITHOUT BYPASS
IISAC01 WITH BYPASS
NIRL03
NKPL01
IRL
IRL
TB2-9 TO TB3-26 (–)
TB2-8 TO TB3-25 (+)
IRL
ICS
TB2-5 TO TB-22 (–)
TB2-4 TO TB-21 (+)
(SEE NOTE)
NKTU02
P1
P1
P1
P1
OUT
OUT
TWISTED PAIR
IN
IN
P1
P1
26
26
25
25
9
8
22
5
4
21
TP85135A