REMOTE LINK (NIRL03) TERMINATION MODULE CONFIGURATION
CABLE TERMINATION
B - 2
I-E96-317A
®
Table B-1. J3 jumper Settings
Application
Jumper Position
Coax cable
(end nodes only)
Coax or Twinax cable
(middle nodes only)
Twinax cable
(end nodes only)
NOTE: Jumper positions for twisted wire pairs are the same as those for Twinax cable.
Table B-2. Remote I/O Application Guide
Type
Nomenclature
Maximum Length Between
RIOs
Coax
Twinax
Twisted Pair
1
NKCL01/NKTL01
NKPL01
---
10,000 feet (3000 m)
4,500 feet (1371 m)
1500 feet (457 m)
1. The twisted pair is 22 AWG with 36 AWG shield drain wire. Each wire of the twisted pair is 7
strands of 30 AWG wire.
Table B-3. Termination Unit Cable Application Guide
Type
Nomenclature
Maximum Length Between
RIOs and TMs
Flat Cable
Twisted Pairs
Twisted Pair
NKTM01
NKTU02
NKLM01
20 feet
20 feet
45 feet