INTRODUCTION
I-E96-322A
6 - 1
SECTION 6 - TROUBLESHOOTING
INTRODUCTION
This section provides troubleshooting information for the
hydraulic servo (HSS) module. This information includes diag-
nostic testing, alarm and exception reporting, problem reports
and troubleshooting flowcharts. Additional reference docu-
ments that are helpful for troubleshooting are product instruc-
tions for the processor module, the operator interface (i.e.,
OIS, EWS, etc.) and the
Function Code Application Manual
IMHSS03 FACEPLATE LEDS
There are nine LEDs visible through the IMHSS03 faceplate.
The top LED (red/green) indicates communication status
between the HSS module and multi-function processor mod-
ule, and overall status (see Figure
). The next eight LEDs
(labeled one through eight) are used for diagnostic purposes.
LEDs one, four and eight are used during normal operation to
indicate automatic tuning of parameters/calibration, outputs
disabled and hard manual mode. Table
lists the LED
states for various operating conditions. In diagnostics mode,
the eight red LEDs indicate either pass/fail count or test num-
ber and status (pass/fail). Figure
shows the diagnostic
LED display.
Figure 6-1. Diagnostic LED Display
TEST NUMBER
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
FAILURE COUNT
PASS COUNT
LSB
LSB
MSB
MSB
NOT USED
TEST NUMBER
MODE FAIL
TP50335B