INSTALLATION
JUMPERS (E1 TO E13)
WBPEEUI240759A0
3 - 5
JUMPERS (E1 TO E13)
Verify the jumpers E1 to E13 are set as shown in Table
for
normal operation. Jumpers E5 to E13 configure the module for
either front panel BNC connection or card edge P3 connection
using an IKED01 cable. Refer to Figure
for switch, jumper,
and connector locations.
Table 3-4. Example I/O Expander Bus
Address Switch Settings (S6)
Address
Switch Position
1,2
(Binary Value)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
08
0
0
1
0
0
0
32
1
0
0
0
0
0
63
1
1
1
1
1
1
NOTES:
1. Switch positions one and two must be ON (closed).
2. 0 = ON or closed; 1 = OFF or open.
Table 3-5. Jumper Settings
(E1 to E13)
Jumper
Setting
Description
E1
Jumper installed
Enable MFT
Jumper removed
Disable MFT
1
E2
Jumper installed
Enable P6/P7 connectors
1
Jumper removed
Disable P6/P7 connectors
E3
Jumper installed
TCK signal low
Jumper removed
TCK signal high (floating)
1
E4
1-2
Enable heartbeat check
2-3
Disable heartbeat check
1
E5 - E10
1-2
Enable Ethernet signals at P3
connector (card edge)
2-3
Enable Ethernet at BNC
connector (front panel)
E11 - E12
Jumper installed
Enable Et12 VDC at
P3 connector
Jumper removed
Disable Et12 VDC at
P3 connector
E13
Jumper installed
Enable BNC connector
Jumper removed
Disable BNC connector
NOTE:
Bold-italic indicates normal operation setting.
1. For testing purposes only.