INSTALLATION
SWITCHES
WBPEEUI240759A0
3 - 3
IP Address (S1, S2, S3, S4)
The EDI module acts as a generic node on the Ethernet LAN.
Set switches S1 through S4 to the IP address assigned to the
module. The address must be converted to binary format to set
the switches. Table
provides examples of IP address
settings.
NOTES:
1.
Switch position one is the most significant bit.
2.
Maximum for switch S4 is 191 for a class B network and 223 for
a class C network.
Hardware Options (S5)
Refer to Tables
and
for hardware options (S5) switch
settings.
Figure 3-1. Module Layout
S TAT U S
LE D s
M O D U L E S TAT E
LE D s
IP A D D R E S S
D R A M
S O C K E T
H A R DW A R E
O P T IO N S
I/O E X PA N D E R
B U S A D D R E S S
R S -23 2 -C
P O R T
(P 5)
E T H E R N E T
B N C
(P 8)
S TO P /
R E S E T
P 1
P 3
P 2
S 6
E 3
E 2
E 13
E 1
S 4
S 3
S 2
S 1
S 5
E 5 --- E 1 0
E 11
E 12
T 01 2 64 A
E 4
Table 3-1. Example IP Address Switch Settings
Address
S4
S3
S2
S1
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
177.12.1.28 1 0 1 1 0 0 0 1 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 1 0 0 0 1 1 1 0 0
10.41.4.17
0 0 0 0 1 0 1 0 0 0 1 0 1 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 1
NOTE: 0 = ON or closed; 1 = OFF or open.