INSTALLATION
SETUP AND PHYSICAL INSTALLATION
3 - 4
I-E96-310B
®
Physical Installation
The DSO module inserts into a standard INFI 90 module
mounting unit and occupies one slot.
Before installing the DSO module, verify the following:
1. Dipswitch S1 is properly configured.
2. All required fuses are functional and properly installed.
3. The appropriate termination device is properly installed.
To install the DSO module:
1. Verify the DSO slot assignment in the module mounting
unit.
2. Verify that a 24-pin dipshunt is installed in the I/O
expander bus sockets between the module mounting unit slot
to be used by the DSO module and the slot to be used by the
appropriate control module.
3. Remove any 24-pin dipshunts from the I/O expander bus
sockets that would connect the DSO module to any control
module other than the appropriate control module.
4. Attach the hooded end of the NKTU01, NKTU02, NKTU11
or NKTU12 cable to the module mounting unit backplane cable
connector opening for the DSO module.
5. Guide the top and bottom edges of the module along the
top and bottom rails of their assigned slots in the module
mounting unit.
6. Push on the faceplate until the rear edge of the module is
firmly seated in the module mounting unit backplane connec-
tor.
7. Turn the 2 latching screws
1
/
2
-turn to lock the module in
place. The module is locked in place when the open end of the
slots on the latching screws faces the center of the faceplate.
WARNING
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
AVERTISSEMENT
Interrompez l'alimentation avant d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'électrocu-
tion sérieuse ou fatale.