INTRODUCTION
SPECIFICATIONS
1 - 6
I-E96-310B
®
IMDSO03
(continued)
Max. on voltage drop
2.1 V at 1.0 A, 25°C (77°F) with 0.3-m (1-ft) long termination device cable
Max. surge current
2 A for 1 second
All IMDSO01/02/03
Isolation
300 VRMS between output and logic circuitry and between outputs. CSA
approved for 300 V isolation.
Mounting
Occupies one slot in standard INFI 90 module mounting unit.
Electromagnetic/radio
frequency interference
Values not available at this time. Keep cabinet doors closed. Do not use com-
munication equipment any closer than 2 meters from the cabinet.
Ambient temperature
0° to 70°C (32° to 158°F)
Relative humidity
5% to 90% up to 55°C (131°F) (noncondensing)
5% to 40% above 55°C (131°F) (noncondensing)
Atmospheric pressure
Sea level to 3 km (1.86 mi.)
Air quality
Noncorrosive
Installation category
Category III
Certification
CSA certified for use as process control equipment in an ordinary (nonhaz-
ardous) environment
Factory Mutual approved for use in Class I, Division 2, hazardous locations.
NOTES:
1. The open fuse detection circuitry may not function for load voltages below 10 VDC.
2. The open fuse detection circuitry may not function for load voltages below 24 VDC.
Table 1-4. Specifications
(continued)
Property
Characteristic/Value