Service Data List / Table TS and M-Bus-Address
For setting the meter data list use menu
Lists
Reading lists
Service Table TS
:
Note: The M-Bus module XC uses for
ID-Addresses
the OBIS Register 0.0.0 (secondary address)
and 0.0.1 (primary address) in the service data list TS.
In this example we use the identification number 1 (OBIS 0.0.1) for M-Bus primary address:
menu
Meter
Meter ID
OBIS Register 0.0.1
, e.g. value 123 (:= 00000123):
Standards for M-Bus addresses:
Primary address: OBIS Register 0.0.1 (Identification 1), range 0 to 250, default := 1
Secondary address: OBIS Register 0.0.0 (device number / fabrication number), range 0 to
99999999, default := 0
For determining the address it is possible to use the wildcard searching procedure (answer E5
Hex
).