Motorized Linear Actuator   

 

 

    baelz 373-E45

4.4  Electrical connection

  

Risk of electric shock!

 Danger

Use an appropriate power supply to ensure that no hazardous voltage can enter the 

device during normal operation or in the event of a system failure or defective system 

components.

Failure to heed this warning may result in death, serious injury or substantial material 

damage.

For short-circuit protection and disconnection of the actuator from the power supply, fuses and 

switch disconnectors must be provided on site. The current values for the rating depend on the 

operating current of the motor (refer to the nameplate). 

The electrical connection should only be carried out by trained, qualified personnel.

 

● Prior to connection, observe the instructions in this chapter.

 

● After connection, but before applying voltage, observe the instructions in the chapter 

"Commissioning" (page 12).

 

● When making the electrical connection, be sure that the power supply is turned OFF! 

Ensure protection against unintentional reconnection to the power supply!

 

● For wiring and connection, observe the regulations for the construction of electric power 

installations and the regulations of the local energy supplier!

 

● Check compliance of the supply voltage and frequency with the specifications on the 

nameplate of the actuator and on the nameplate of the actuator motor. 

 

● Always select the cable cross section so as to match the actuator's power consumption 

and the required cable length. Minimum cross section of the cable for this linear 

actuator: 1 mm²

In case of malfunction

Dangerous voltage if protective earth conductor is NOT connected! Risk of electric shock!

→ Do not operate the device if the protective earth conductor is not connected!

Trapped wires can lead to short circuiting! Risk of electric shock and malfunction.

4.5  Carrying out the electrical connection

  

Risk of electric shock!

 Danger

→ Disconnect the device from the power supply before removing cover.

Always use the wiring diagram on the inside of the cover or supplied with the actuator. 

Replace the dummy plugs with cable glands.

1.  Strip the cable as necessary.

2.  Strip the ends of the individual wires.

3.  For flexible wires: Use wire end ferrules as specified in DIN 46228.

4.  Connect the wires as shown in the job-specific wiring diagram.

The IP-rating shown on the nameplate is only valid if suitable cable glands are used.

Содержание BA 373-E45

Страница 1: ...5 74076 Heilbronn Germany www baelz de Seite Page BA_373 E45_05_DEF_MJ_2119 Operating Instructions BA 373 E45 Motorized Linear Actuator baelz 373 E45 Technical specifications subject to change without...

Страница 2: ...otorized linear actuator 6 2 2 Technical Specifications 6 2 4 Accessories and options 7 2 3 Type name 7 2 5 Operating conditions 7 3 TRANSPORT AND STORAGE 7 4 ASSEMBLY 8 4 1 Fitting position 8 4 2 Ass...

Страница 3: ...2 5 3 point control with a continuous output signal 20 8 3 Wiring diagrams and allocation of connection terminals 20 8 3 1 Wiring diagram 20 8 3 2 Allocation of connection terminals 21 8 4 Configurati...

Страница 4: ...dentification complies with the nameplate of the linear actuators before starting any activities The actual technical specifications of the linear actuators and the power supply requirements are the s...

Страница 5: ...ny way 1 4 Before starting work Before carrying out any work check whether the types specified here correspond to the information on the name plate of the actuator baelz 373 E45 1 5 During operation S...

Страница 6: ...ower consumption 230 V VA 11 Nominal current 230 V A 0 045 Type of motor synchronous motor syn Motor protection stall proof motor B Maximum stroke mm 44 Supply voltage 2 24 V 115 V 230 V 50 60 Hz 10 O...

Страница 7: ...case of extreme variations in ambient temperature and high humidity levels installation of a heating resistor is recommended to minimise condensation in the actuator Actuator covers with suppression o...

Страница 8: ...mage if no valve is fitted to actuator Caution Caution If the linear actuator is operated without a valve the missing stop may cause damage to the actuator The actuator must therefore never be operate...

Страница 9: ...e and actuator match The linear actuator is supplied with the spindle retracted A slight adjustment for fitting of the coupling can be carried out by turning the spindle The following dimensions must...

Страница 10: ...le spindle nut is driven by an electric motor via a gearbox This converts the rotary movement into a linear movement Load dependent limit switches dictate the end positions 4 3 1 Manual adjustment Man...

Страница 11: ...ower supply For wiring and connection observe the regulations for the construction of electric power installations and the regulations of the local energy supplier Check compliance of the supply volta...

Страница 12: ...rection of rotation is wrong switch off immediately Check wiring jumpers Repeat the test run If the direction of travel is set incorrectly damage to actuator and valve is imminent as the limit switche...

Страница 13: ...he distance sleeve 4 onto the threaded end of the connecting rod and tighten Place the laminate washer 2 over the threaded end onto the self locking nut Insert the position detector for the potentiome...

Страница 14: ...oke 44 mm note that for reverse mode the potentiometer must be turned to the new zero point mechanical stop opposite For this adjustment the actuator spindle must be in the correct end position Normal...

Страница 15: ...020A DIGITAL POSITIONER Disconnect actuator from power supply before starting work Danger These instructions apply given that the potentiometer assembly has been correctly fitted as described in secti...

Страница 16: ...373 E45 Before fitting the adaptor panel the nameplate must be stuck to the underside If the digital positioner board ist replaced this nameplate must also be changed Place the 4 click fit spacer con...

Страница 17: ...anel on the bracket so that the countersunk hole and the hole in the bracket are aligned Insert the plastic screws and fit and tighten the nuts on the underside of the bracket Fit the spacer sleeve on...

Страница 18: ...ar Actuator baelz 373 E45 Wire up the digital positioner board with the motor and the potentiometer according to the wiring diagram 7020A Fig 9 page 21 Stick the wiring diagram to the inside of the ac...

Страница 19: ...onal modes and operating options For further information and additional functions see baelz 7020 operating instructions 8 2 1 Standard operation using DIP switches The DIP switches can be used to carr...

Страница 20: ...o account See wiring diagrams in the baelz 7020 operating instructions 8 2 5 3 point control with a continuous output signal 1 Set the positioner up and wire to power supply as described previously an...

Страница 21: ...control the N S switch must be set to S safety mode 20 22 Digital input for a switch used to select between two conditions e g open closed or summer winter 23 24 25 26 Analogue output position indica...

Страница 22: ...spindle extended valve closed DIP 5 Current position of the actuator is saved as additional switching position 2EZ 1 See wiring diagram page 21 from 0 to 1 save 2EZ 1 2 DIP 6 Current position of the a...

Страница 23: ...run whether or not the unit was already initialized before starting the current initialization run The direction of operation must not be confused with heating cooling Heating in standard mode is carr...

Страница 24: ...t to 1 errors and alarms occurring during normal positioner operation will not be shown This enables errors occurring during initialization to be distinguished from errors during normal positioner ope...

Страница 25: ...zed and values for valve travel time and switching hysteresis are determined Switch DIP switch 12 from 0 to 1 to start an initialization run The red LED is lit during initialization When initializatio...

Страница 26: ...un Initialization still possible If the red LED is flickering the position of the potentiometer is at the edge of the optimal range and therefore OK 5 green and red flashing Error during initializatio...

Страница 27: ...ormal positioner operation Setting DIP switch 12 from 1 back to 0 permits the red LED to show any normal operational errors instead of initialization errors which may have occured Error code Error Cor...

Страница 28: ...allocated The error codes 7 to 10 are not allocated and are reserved for additional alarms Error code Error Corrective action 1 Sensor malfunction at analogue input AI1 No signal from potentiometer C...

Страница 29: ...tact load 10 V 100 mA 2 output signals Output 1 0 2 10 V min ohmic resistance 5k Output 2 0 4 20 mA max ohmic resistance 300 Factory setting 0 10 V and 0 20 mA Input signal 0 2 10V Re 63k 0 4 20mA Re...

Страница 30: ...cap nut from the actuator cover 3 Pull and gently turn cover to remove Screw the temperature sensor firmly into the hole by the load dependent limit switches Fix the heating element in its place on th...

Страница 31: ...positioner 7020A 42 Extension 50 Crank handle complete 60 Flange complete with connecting rod 70 Potentiometer assembly including 2 limit switches complete F1653882 and above new version 71 Potentiome...

Страница 32: ...orrectly installed 2 Check the actuator settings and the specifications on the nameplate 3 Correct the problems as specified in the checklist page 33 4 If the problem cannot be corrected contact the B...

Страница 33: ...ns dismantle linear actuator and return for repair Voltage drop due to connecting cables being too long and or having insufficient cross section Measure current data with linear actuator recalculate c...

Страница 34: ...6 Heilbronn Germany www baelz de Seite Page Motorized Linear Actuator baelz 373 E45 13 DIMENSIONAL DRAWINGS Fig 12 Dimensional drawing baelz E45 with S21 yoke and spindle 10 mm Fig 13 Dimensional draw...

Страница 35: ...H Co Koepffstrasse 5 74076 Heilbronn Germany www baelz de Seite Page Motorized Linear Actuator baelz 373 E45 Fig 14 Dimensional drawing baelz E45 with S41 yoke and spindle 16 mm Fig 15 Dimensional dra...

Страница 36: ......

Отзывы: