Motorized Linear Actuator
baelz 373-E45
4.4 Electrical connection
Risk of electric shock!
Danger
Use an appropriate power supply to ensure that no hazardous voltage can enter the
device during normal operation or in the event of a system failure or defective system
components.
Failure to heed this warning may result in death, serious injury or substantial material
damage.
For short-circuit protection and disconnection of the actuator from the power supply, fuses and
switch disconnectors must be provided on site. The current values for the rating depend on the
operating current of the motor (refer to the nameplate).
The electrical connection should only be carried out by trained, qualified personnel.
● Prior to connection, observe the instructions in this chapter.
● After connection, but before applying voltage, observe the instructions in the chapter
"Commissioning" (page 12).
● When making the electrical connection, be sure that the power supply is turned OFF!
Ensure protection against unintentional reconnection to the power supply!
● For wiring and connection, observe the regulations for the construction of electric power
installations and the regulations of the local energy supplier!
● Check compliance of the supply voltage and frequency with the specifications on the
nameplate of the actuator and on the nameplate of the actuator motor.
● Always select the cable cross section so as to match the actuator's power consumption
and the required cable length. Minimum cross section of the cable for this linear
actuator: 1 mm²
In case of malfunction
:
Dangerous voltage if protective earth conductor is NOT connected! Risk of electric shock!
→ Do not operate the device if the protective earth conductor is not connected!
Trapped wires can lead to short circuiting! Risk of electric shock and malfunction.
4.5 Carrying out the electrical connection
Risk of electric shock!
Danger
→ Disconnect the device from the power supply before removing cover.
Always use the wiring diagram on the inside of the cover or supplied with the actuator.
Replace the dummy plugs with cable glands.
1. Strip the cable as necessary.
2. Strip the ends of the individual wires.
3. For flexible wires: Use wire end ferrules as specified in DIN 46228.
4. Connect the wires as shown in the job-specific wiring diagram.
The IP-rating shown on the nameplate is only valid if suitable cable glands are used.