7.3.2 Determining input and output signals
The actuator is either preset to 0...10 V, 0...20 mA or to 2...10 V, 4...20 mA . Depending on the configuration, the
lines for the input and output signals are connected to terminal X4.
7.4 Commissioning and settings
Figure 17: Positioning electronics
Potentiometers
P1
Lower limit adjustment
Turn clockwise to lower the limit
P2
Upper limit adjustment
Turn clockwise to lower the limit
P4
Span adjustment
Turn counter-clockwise to spread
the potentiometer signal