Badger Meter SDI Series Скачать руководство пользователя страница 9

Pipe Saddle

(ref.)

Mounting

Adapter

Gasket

(ref)

4 .  Locate the sensor rotor assembly a fixed distance from the center of the 

pipe . To position the impeller at this depth, a reference measurement for 

the pipe size and schedule is used .
a .  Look up the pipe size and schedule number in the 

“Customer Reference 

Number Tables” on page 17 

and note the Customer Reference 

Number (Customer Ref #) . 

NOTE:

N

The Customer Reference Number is calculated using the following 

formula:  

Ref # = Insertion Depth + Wall Thi Cover Thickness (0 .875 in . 

(22 mm))

b .  Next, measure from the outside wall of the pipe to the top of the 

installed mounting adapter . This is dimension “B” in 

Figure 5

 .

c .  Add this number to the reference measurement . The resulting number 

is dimension “C” in 

Figure 5

 .

  

Dimension “C” = Customer Ref # + Dimension “B”

d .  Dimension “C” is the distance from the recess of the sensor tip to the 

bottom of the stem collar . Insert the metal tab of a tape measure into 

the recess of the flow sensor tip . Extend the tape up the stem and mark 

the shaft with a pencil . 

e .  Slide the collar along the shaft until its bottom surface is at the mark 

on the stem . Tighten the cap screw on the collar . When the sensor is 

reassembled, this will set the insertion depth of the sensor .

5 .  Attach the sensor to the mounting adapter by gently pushing the flow 

sensor into the mounting adapter until the cover touches the mounting 

adapter . Tighten the cover against the O-ring seal . This will seal the 

sensor assembly .

6 .  Continue to insert the flow sensor stem until the stem collar meets the 

cover . Thread the hex cap onto the mounting adapter but do not tighten . 

7 .  Align the flow sensor with the pipe by using the flat cover on the 

electronics housing as a guide . Place a straightedge along the cover and 

rotate the sensor until the straightedge is parallel with the pipe as shown 

in 

Figure 6

 . 

8 .  Tighten the hex cap over the collar approximately 10 ft-lb . The hex cap 

holds the sensor alignment but performs no sealing functions .  

DO NOT OVER TIGHTEN 

9 .  Pressurize the pipeline and check for leaks

.

Pipe Saddle

(ref.)

Mounting

Adapter

Gasket

(ref)

Stem

Stem Collar

Hex Cap

Cover

Figure 5:  Dimensions "B" and "C"

Straight Edge Parallel to Pipe

Pipe

Pipe

SDI

Flow Sensor

Figure 6:  Level the sensor

Mechanical Installation 

Page 9 

May 2017

SEN-UM-00217-EN-10

Содержание SDI Series

Страница 1: ...Flow Sensors Insert Style Flow Sensors SDI Series Battery Powered SEN UM 00217 EN 10 May 2017 User Manual...

Страница 2: ...Flow Sensors Insert Style Flow Sensors SDI Series Battery Powered Page ii May 2017 SEN UM 00217 EN 10...

Страница 3: ...d Ordering Matrix 6 Display Options 6 Mechanical Installation 7 Installation for Direct Insert Models 8 Installation for Hot Tap models 10 Programming 15 Customer Reference Number Tables 17 K Offset T...

Страница 4: ...Flow Sensors Insert Style Flow Sensors SDI Series Battery Powered Page iv May 2017 SEN UM 00217 EN 10...

Страница 5: ...rue hot tap installation the sensor is mounted in the pipe under pressure by attaching a service saddle or weld on fitting to the pipe and mounting the isolating valve and nipple to the threaded conne...

Страница 6: ...R Stainless Steel 0 BEARING Torlon 0 Figure 1 Battery operated ordering matrix Pipe size for reference only Depending on pipe size tapping saddle or existing hardware longer sensor length may be requi...

Страница 7: ...ebris will interfere then the sensor should be located around the pipe from the top preferably not more than 45 degrees from top dead center The sensor should never be located at the bottom of the pip...

Страница 8: ...1 is intended for nominal pipe diameters from 1 1 2 10 in 38 254 mm and the D2 for pipe diameters from 12 36 in 30 91 cm However pipe with extra thick walls existing linings or unusual tapping hardwar...

Страница 9: ...r along the shaft until its bottom surface is at the mark on the stem Tighten the cap screw on the collar When the sensor is reassembled this will set the insertion depth of the sensor 5 Attach the se...

Страница 10: ...ipe diameters from 12 36 in 30 91 cm and stem length H3 is for nominal pipe diameters from 36 in and up However pipe with extra thick walls existing linings or unusual tapping hardware may require lon...

Страница 11: ...ded for drilling through a 1 in ball valve cannot be used 6 Attach the tapping machine to the tapping adapter Ensure that all connections and seals are tight 7 Slowly open the valve by rotating the ha...

Страница 12: ...e pipe by pushing against the top of the electronics housing with a slight twisting motion until the stem collar meets the cover The force required to push the sensor into the pipeline is approximatel...

Страница 13: ...ensor accessible by removing the side cover battery holder The battery is held in a spring clip attached to the cover The required battery is a 3V lithium C size that can be purchased through Badger M...

Страница 14: ...is an open collector transistor closure with a maximum sinking current of 100 mA The cable that plugs into the existing pigtail from the PC board is PN 807021 Power Connector Attach DI 3V Lithium only...

Страница 15: ...ect the PC to the SDI with the ASDIB 20 SDI programming kit Plug in the RJ11 plug from the ASDIB 20 kit to the RJ11 socket on Battery Powered SDI Connect the DB9 connector of the ASDIB 20 kit to the P...

Страница 16: ...progress It may take up to 1 1 2 minutes to program the Battery Powered SDI When the status bar says updated the Battery Powered SDI is programmed NOTE 2 N After you press Exit it takes about 10 seco...

Страница 17: ...1 73 3 1 32 0 316 1 83 3 1 32 8 in 8 625 Wall Insertion Depth Customer Ref 0 148 2 50 3 17 32 0 148 2 50 3 17 32 0 322 2 39 3 19 32 0 322 2 39 3 19 32 0 500 2 29 3 21 32 0 410 2 40 3 11 16 10 in 10 7...

Страница 18: ...8 1 7 16 0 060 0 49 1 7 16 0 049 0 50 1 7 16 0 042 0 51 1 7 16 2 in 2 125 Wall Insertion Depth Customer Ref 0 083 0 72 1 11 16 0 070 0 73 1 11 16 0 058 0 74 1 11 16 0 042 0 76 1 11 16 2 1 2 in 2 625 W...

Страница 19: ...6 8 in 9 050 Wall Insertion Depth Customer Ref 0 362 2 50 3 23 32 10 in 11 100 Wall Insertion Depth Customer Ref 0 444 3 06 4 3 8 12 in 13 200 Wall Insertion Depth Customer Ref 0 528 3 64 5 1 16 For o...

Страница 20: ...2 681251 15 359217 2 681251 14 116608 2 693176 14 116608 2 693176 12 779132 2 904373 12 779132 2 904373 12 in 12 750 K Offset 22 687525 5 074024 22 687525 5 074024 22 492687 4 969576 22 492687 4 96957...

Страница 21: ...fset Ductile Iron Because of the variety of iron pipe classes sizes and wall thicknesses consult the factory for customer reference number Pipe O D Schedule or pipe O D I D or Pipe O D and wall thickn...

Страница 22: ...38 mm diameter and up Accuracy Standard to 1 of rate over optimum flow range Straight Pipe Requirement Install sensor in straight pipe section with a minimum distance of 10 diameters upstream and 5 d...

Страница 23: ...a Short Circuit Current 50 mA typical n a 100 mA For direction 100 mA 100 mA 100 mA Output Frequency 800 Hz max n a Scaled by customer n a Scaled by customer Scaled by customer Output Pulse Width 5 m...

Страница 24: ...Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur w Poland 48 32 236...

Отзывы: