Installation for Direct Insert Models

These instructions are for the installation of flow sensors into piping systems that are 

not

 under pressure at the time of 

installation . If the line must be tapped under pressure, a hot tap style sensor must be used . See the following section for hot 

tap installation instructions . 

Mounting

Adaptor

Stem

Stem Collar

Hex Cap

Cover

Pipe Saddle

(ref.)

Gasket

(ref)

O-Ring

O-Ring

Groove

O-Ring

Expanded View

Figure 4:  Installation for direct insert model

The insertion depth and alignment of the sensor are critical to the accuracy of the flow measurement . The impeller must be at 

the same location in the pipe as it was during calibration . Badger

 

Meter provides sensors with different stem lengths . Longer 

stems are intended for use in larger diameter pipes and shorter stems for use in smaller pipelines . However, stem length has 

no affect on the operation of the sensor provided that the impeller is positioned correctly in the pipe .
Direct insert models are available in stem lengths designated D1 and D2 . The D1 is intended for nominal pipe diameters from 

1-1/2…10 in . (38…254 mm), and the D2 for pipe diameters from 12…36 in . (30…91 cm) . However, pipe with extra thick walls, 

existing linings, or unusual tapping hardware may require longer length sensors . For these pipes, consult the factory . For 

larger pipe sizes, hot tap style sensors equipped with an isolation valves are recommended .
The preferred method of installation is by means of a saddle with 1 in . NPT outlet . On steel pipelines a weld-on type fitting 

may be substituted .
1 .  Attach the saddle to a section of pipe that has at least 10 diameters of straight pipe ahead and five diameters of straight 

pipe behind the saddle . Drill a minimum 1-1/8 in . (29 mm) diameter hole in the pipe .

2 .  Remove the sensor assembly from the mounting hardware by loosening the hex cap over the stem collar and the cover to 

the mounting adapter and detaching the assembly . Set aside taking care not to damage impeller/shaft assembly .

3 .  Attach the pipe thread end of the mounting adapter to the saddle or weld-o-let using a pipe joint compound and tighten 

the joint . Do not apply sealing compound to the top thread of the mounting adapter, it is sealed with an O-ring .

Mechanical Installation

Page 8 

May 2017

SEN-UM-00217-EN-10

Содержание SDI Series

Страница 1: ...Flow Sensors Insert Style Flow Sensors SDI Series Battery Powered SEN UM 00217 EN 10 May 2017 User Manual...

Страница 2: ...Flow Sensors Insert Style Flow Sensors SDI Series Battery Powered Page ii May 2017 SEN UM 00217 EN 10...

Страница 3: ...d Ordering Matrix 6 Display Options 6 Mechanical Installation 7 Installation for Direct Insert Models 8 Installation for Hot Tap models 10 Programming 15 Customer Reference Number Tables 17 K Offset T...

Страница 4: ...Flow Sensors Insert Style Flow Sensors SDI Series Battery Powered Page iv May 2017 SEN UM 00217 EN 10...

Страница 5: ...rue hot tap installation the sensor is mounted in the pipe under pressure by attaching a service saddle or weld on fitting to the pipe and mounting the isolating valve and nipple to the threaded conne...

Страница 6: ...R Stainless Steel 0 BEARING Torlon 0 Figure 1 Battery operated ordering matrix Pipe size for reference only Depending on pipe size tapping saddle or existing hardware longer sensor length may be requi...

Страница 7: ...ebris will interfere then the sensor should be located around the pipe from the top preferably not more than 45 degrees from top dead center The sensor should never be located at the bottom of the pip...

Страница 8: ...1 is intended for nominal pipe diameters from 1 1 2 10 in 38 254 mm and the D2 for pipe diameters from 12 36 in 30 91 cm However pipe with extra thick walls existing linings or unusual tapping hardwar...

Страница 9: ...r along the shaft until its bottom surface is at the mark on the stem Tighten the cap screw on the collar When the sensor is reassembled this will set the insertion depth of the sensor 5 Attach the se...

Страница 10: ...ipe diameters from 12 36 in 30 91 cm and stem length H3 is for nominal pipe diameters from 36 in and up However pipe with extra thick walls existing linings or unusual tapping hardware may require lon...

Страница 11: ...ded for drilling through a 1 in ball valve cannot be used 6 Attach the tapping machine to the tapping adapter Ensure that all connections and seals are tight 7 Slowly open the valve by rotating the ha...

Страница 12: ...e pipe by pushing against the top of the electronics housing with a slight twisting motion until the stem collar meets the cover The force required to push the sensor into the pipeline is approximatel...

Страница 13: ...ensor accessible by removing the side cover battery holder The battery is held in a spring clip attached to the cover The required battery is a 3V lithium C size that can be purchased through Badger M...

Страница 14: ...is an open collector transistor closure with a maximum sinking current of 100 mA The cable that plugs into the existing pigtail from the PC board is PN 807021 Power Connector Attach DI 3V Lithium only...

Страница 15: ...ect the PC to the SDI with the ASDIB 20 SDI programming kit Plug in the RJ11 plug from the ASDIB 20 kit to the RJ11 socket on Battery Powered SDI Connect the DB9 connector of the ASDIB 20 kit to the P...

Страница 16: ...progress It may take up to 1 1 2 minutes to program the Battery Powered SDI When the status bar says updated the Battery Powered SDI is programmed NOTE 2 N After you press Exit it takes about 10 seco...

Страница 17: ...1 73 3 1 32 0 316 1 83 3 1 32 8 in 8 625 Wall Insertion Depth Customer Ref 0 148 2 50 3 17 32 0 148 2 50 3 17 32 0 322 2 39 3 19 32 0 322 2 39 3 19 32 0 500 2 29 3 21 32 0 410 2 40 3 11 16 10 in 10 7...

Страница 18: ...8 1 7 16 0 060 0 49 1 7 16 0 049 0 50 1 7 16 0 042 0 51 1 7 16 2 in 2 125 Wall Insertion Depth Customer Ref 0 083 0 72 1 11 16 0 070 0 73 1 11 16 0 058 0 74 1 11 16 0 042 0 76 1 11 16 2 1 2 in 2 625 W...

Страница 19: ...6 8 in 9 050 Wall Insertion Depth Customer Ref 0 362 2 50 3 23 32 10 in 11 100 Wall Insertion Depth Customer Ref 0 444 3 06 4 3 8 12 in 13 200 Wall Insertion Depth Customer Ref 0 528 3 64 5 1 16 For o...

Страница 20: ...2 681251 15 359217 2 681251 14 116608 2 693176 14 116608 2 693176 12 779132 2 904373 12 779132 2 904373 12 in 12 750 K Offset 22 687525 5 074024 22 687525 5 074024 22 492687 4 969576 22 492687 4 96957...

Страница 21: ...fset Ductile Iron Because of the variety of iron pipe classes sizes and wall thicknesses consult the factory for customer reference number Pipe O D Schedule or pipe O D I D or Pipe O D and wall thickn...

Страница 22: ...38 mm diameter and up Accuracy Standard to 1 of rate over optimum flow range Straight Pipe Requirement Install sensor in straight pipe section with a minimum distance of 10 diameters upstream and 5 d...

Страница 23: ...a Short Circuit Current 50 mA typical n a 100 mA For direction 100 mA 100 mA 100 mA Output Frequency 800 Hz max n a Scaled by customer n a Scaled by customer Scaled by customer Output Pulse Width 5 m...

Страница 24: ...Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur w Poland 48 32 236...

Отзывы: