Badger Meter Impeller Data Industrial 3100 Series Скачать руководство пользователя страница 9

Analog Input

As an alternative to the pulse inputs the Badger Meter Series 3100 can accept up to two analog inputs . The input is  

non-isolated, but can accept 0…1V DC; 0…5V DC; 0…10V DC; 0…20 mA; and 4…20 mA with both factory defined, and 

custom units of measure . Low impedance 100 ohm input for current inputs optimizes performance and flexibility for loop 

power supplies . Both the low and high end scaling are independent and field configured by the installer . 

Figure 7:  Current and voltage sourcing inputs

Output Wiring

The Series 3100 has four mechanical form “C” relays, one solid state, normally open (N .O .) switch closure, two analog outputs, 

RS-485 for Modbus and BACnet communications and a USB connector for configuration and other purposes .
See 

"Specifications" on page 27

 for maximum voltage and current ratings for each type output .

Mechanical Form “C” Relay (COM, N.O. and N.C.)

The four form “C” mechanical relays are labeled “NO” (normally open), “NC” (normally closed) and COM (common) .
When a relay is de-energized, the corresponding LED is unlit, and continuity exists between N .C . and COM; and, N .O . to COM 

is open .
When a relay is energized the corresponding LED lights yellow and there is continuity between N .O . and COM and N .C . to 

COM is open .

Installation 

Page 9 

August 2014

CTL-UM-001026-EN-04

Содержание Impeller Data Industrial 3100 Series

Страница 1: ...User Manual Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter CTL UM 01026 EN 04 August 2014...

Страница 2: ...Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page ii August 2014...

Страница 3: ...rm C Relay COM N O and N C 9 Normally Open Solid Switch 11 Analog Outputs 11 RS 485 Communication Wiring 12 USB Communications Port 12 Programming 13 Programming Flow Charts Relays 13 Key Pad Display...

Страница 4: ...Troubleshooting 26 Trouble Codes 26 Specifications 27 Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page iv August 2014...

Страница 5: ...AC DC to the optional 120 240V AC Nonvolatile memory no battery backup is required Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes f...

Страница 6: ...el Mount is designed for through panel mounting which allows access to the back of the unit The 3100 is secured to the panel by two draw brackets shown in Figure 2 below Wall Mount Badger Meter does n...

Страница 7: ...he power supply to the Series 3100 terminal marked LV AC DC and connect the negative end of the power supply to the Series 3100 terminal marked LV AC DC Earth ground can be connected to the terminal m...

Страница 8: ...ar panel terminals are used all parameters are set with the LCD keypad interface No internal or external jumpers switches or potentiometers require movement or adjustment Pulse Inputs Solid State Swit...

Страница 9: ...our mechanical form C relays one solid state normally open N O switch closure two analog outputs RS 485 for Modbus and BACnet communications and a USB connector for configuration and other purposes Se...

Страница 10: ...Figure 8 High flow shut down and normally open master valve Figure 9 High flow shut down with irrigation clock and normally closed master valve Installation Page 10 August 2014 CTL UM 001026 EN 04...

Страница 11: ...o analog outputs Each is isolated and independent and can be configured for 0 20 mA or 4 20 mA This unique design permits external conversion to externally to 0 5V DC or 1 5V DC with a 250 ohm resisto...

Страница 12: ...e 12 RS 485 communication wiring Modbus BACnet USB Communications Port Using the USB Port requires Windows HyperTerminal or other similar communications software Figure 13 USB port Installation Page 1...

Страница 13: ...rogramming Flow Charts Relays The following block diagrams explain various programming areas and are organized as follows Figure 14 Model 3100 programming chart Programming Page 13 August 2014 CTL UM...

Страница 14: ...Figure 15 Flow inputs Programming Page 14 August 2014 CTL UM 001026 EN 04...

Страница 15: ...Figure 16 Relays pulse outputs Programming Page 15 August 2014 CTL UM 001026 EN 04...

Страница 16: ...Figure 17 Analog inputs Programming Page 16 August 2014 CTL UM 001026 EN 04...

Страница 17: ...Figure 18 RS 485 communication port Programming Page 17 August 2014 CTL UM 001026 EN 04...

Страница 18: ...the MENU Button One each screen there are three Choices In this case RESET SETUP and DIAG selects RESET selects SETUP and selects DIAG RESET SETUP DIAG Main Set up screen accessed by press MENU One ea...

Страница 19: ...u Enter Set point 1 00000000 Menu Enter Figure 19 Selection screen Option List Screens Units of measure is an example of an options list Press to scroll up the list and to scroll down through the list...

Страница 20: ...her set point crossing before restarting the count from zero LATCH Locks relay in energized state If Latch is chosen once energized by the set point time delay the relay will remain energized until re...

Страница 21: ...006 30007 4 Flow 2 Total Input Register 30008 30009 BACnet The Model 3100 can be configured to communicate on a BACnet RS 485 MSTP Master Slave Token Passing system Configuration is via the front pane...

Страница 22: ...ata bits 1 stop bit no parity and no flow contr 6 When connected a symbol will appear in the upper left corner of the main HyperTerminal display screen 7 Press the Enter Key Both the Rx and Tx LED s o...

Страница 23: ...ore amenable to scripting it still accepts the same commands Any command entered without an sign and variable will display the current setting Example Typing display line 1 returns 0 which is the vari...

Страница 24: ...low rate min current flow 1 2 sensor avg 0 100 averaging time constant in seconds flow 1 2 rate units 0 19 flow channel rate units to display 0 GPM 1 gal s 2 gal hr 3 Mgal day 4 L s 5 LPM 6 L hr 7 ft3...

Страница 25: ...1 5 rate x totalizer rate relay 1 5 ctime 0 10000 pulse width in milliseconds relay 1 4 latch on off turn on off relay latching relay 1 4 setpoint x relay 1 4 setpoint x relay 1 4 relpoint x relay 1...

Страница 26: ...reading from analog input AD converter channel 1 32 Error reading from analog input AD converter channel 2 36 Error writing to analog input AD converter channel 1 37 Error writing to analog input AD...

Страница 27: ...r sourcing Sinking 30V DS 0 mA max 3 V 20 mA min Sourcing 600 max load USB Communication Provides complete access to all programming and operation features Requirements USB 2 0 A to Mini B five pin ca...

Страница 28: ...ico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa G...

Отзывы: