Badger Meter Impeller Data Industrial 3100 Series Скачать руководство пользователя страница 20

Solid State Switch and Form “C” Outputs

The four form C mechanical relays, and one N .O . solid state switch pulse output are completely independent, electrically 

isolated and can be programmed as either pulse or set-point outputs .

Totalizer – Pulse Output

When the function “Totalizer” is selected the unit of measure and resolution are independent from the displayed units, and 

can be programmed where 1 pulse occurs once every 0000000 .1 to 999999999 of units selected, with any pulse width from 

0001 to 9999 mS .

Set Points

The Set Point programming is extremely powerful and flexible, with unit of measure and resolution independent from the 

displayed units . Since the Set Point, Release Point and their associated time delays are fully independent, the alarm can be 

either a high rate or low rate, depending on whether the Set Point is selected greater than the release point, or the release 

point is greater than the Set Point . For applications where the relay must remained energized, once set, a latching feature is 

provided . When latched, the relay remains energized until reset from the front panel . While design planning, note that both 

the relays and the pulse outputs can be programmed as alarm points and only the relays provide both normally open and 

normally closed contacts . The switch is a simple N .O . contact .

Terminology

Display

Definition

Function

SETPT

Set point

If the set point value is a greater than the release point value, when 

the displayed flow rate exceed the set point, the Set Point Delay 

Timer is started . If the set point is less than the release point when the 

flow drops below the set point, the timer is started

SDLY

Set point time delay

If the set point remains crossed for a continuous period of time 

exceeding the set point delay setting, the relay will energize . If the 

flow rate briefly re-crosses the set point before the timer reaches 

its setting, the timer will reset and await another set point crossing 

before restarting the count from zero .

LATCH

Locks relay in energized state

If 

Latch

 is chosen, once energized by the set-point time delay, 

the relay will remain energized until reset from the front panel . 

Otherwise, the relay will de-energize when the Release Point Delay 

Timer times out .

RELP

Release point

If the relay is already energized, not latched and the flow input 

crosses the release point, the Release Point Delay timer is started .

RDLY

Release point time delay

If the release point remains crossed for a continuous period of 

time and exceeds the release point delay setting, the relay will de-

energize . If the flow rate briefly re-crosses the release point before 

the timer reaches its setting, the timer will reset and await another 

release point, crossing before restarting the count from zero .

High Flow Set Point

The 

SETPT

 must be a value greater than the 

RELP

 . The relay output will have continuity between its 

N.C.

 terminal and 

COM

 

until the flow has exceeded the 

SETPT

 for a continuous period of time exceeding the 

SDLY

 . At this time, the N .C . connection 

will open and the N .O . contact will have continuity to the 

COM

 terminal . When the flow has dropped below the 

RELP

 for a 

continuous period of time exceeding the 

RDLY

, the relay states will return to their original states . If the latch has been set to 

ON

 once the set point and set delay have been satisfied, the relay will not release until manually reset .

Low Flow Set Point

The 

SETPT

 must be a value less than the 

RELP

 . The relay output will have continuity between its 

N.C.

 terminal and 

COM

 until 

the flow drops below the 

SETPT

 for a continuous period of time exceeding the 

SDLY

 . At this time, the N .C . connection will open 

and the N .O . contact will have continuity to the 

COM

 terminal . When the flow has again risen above the 

RELP

 for a continuous 

period of time, exceeding the 

RDLY

, the relay states will return to their original states . If the latch has been set to 

ON

 when the 

set point and set delay have been satisfied, the relay will not release until manually reset .

Programming

Page 20 

August 2014

CTL-UM-001026-EN-04

Содержание Impeller Data Industrial 3100 Series

Страница 1: ...User Manual Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter CTL UM 01026 EN 04 August 2014...

Страница 2: ...Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page ii August 2014...

Страница 3: ...rm C Relay COM N O and N C 9 Normally Open Solid Switch 11 Analog Outputs 11 RS 485 Communication Wiring 12 USB Communications Port 12 Programming 13 Programming Flow Charts Relays 13 Key Pad Display...

Страница 4: ...Troubleshooting 26 Trouble Codes 26 Specifications 27 Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page iv August 2014...

Страница 5: ...AC DC to the optional 120 240V AC Nonvolatile memory no battery backup is required Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes f...

Страница 6: ...el Mount is designed for through panel mounting which allows access to the back of the unit The 3100 is secured to the panel by two draw brackets shown in Figure 2 below Wall Mount Badger Meter does n...

Страница 7: ...he power supply to the Series 3100 terminal marked LV AC DC and connect the negative end of the power supply to the Series 3100 terminal marked LV AC DC Earth ground can be connected to the terminal m...

Страница 8: ...ar panel terminals are used all parameters are set with the LCD keypad interface No internal or external jumpers switches or potentiometers require movement or adjustment Pulse Inputs Solid State Swit...

Страница 9: ...our mechanical form C relays one solid state normally open N O switch closure two analog outputs RS 485 for Modbus and BACnet communications and a USB connector for configuration and other purposes Se...

Страница 10: ...Figure 8 High flow shut down and normally open master valve Figure 9 High flow shut down with irrigation clock and normally closed master valve Installation Page 10 August 2014 CTL UM 001026 EN 04...

Страница 11: ...o analog outputs Each is isolated and independent and can be configured for 0 20 mA or 4 20 mA This unique design permits external conversion to externally to 0 5V DC or 1 5V DC with a 250 ohm resisto...

Страница 12: ...e 12 RS 485 communication wiring Modbus BACnet USB Communications Port Using the USB Port requires Windows HyperTerminal or other similar communications software Figure 13 USB port Installation Page 1...

Страница 13: ...rogramming Flow Charts Relays The following block diagrams explain various programming areas and are organized as follows Figure 14 Model 3100 programming chart Programming Page 13 August 2014 CTL UM...

Страница 14: ...Figure 15 Flow inputs Programming Page 14 August 2014 CTL UM 001026 EN 04...

Страница 15: ...Figure 16 Relays pulse outputs Programming Page 15 August 2014 CTL UM 001026 EN 04...

Страница 16: ...Figure 17 Analog inputs Programming Page 16 August 2014 CTL UM 001026 EN 04...

Страница 17: ...Figure 18 RS 485 communication port Programming Page 17 August 2014 CTL UM 001026 EN 04...

Страница 18: ...the MENU Button One each screen there are three Choices In this case RESET SETUP and DIAG selects RESET selects SETUP and selects DIAG RESET SETUP DIAG Main Set up screen accessed by press MENU One ea...

Страница 19: ...u Enter Set point 1 00000000 Menu Enter Figure 19 Selection screen Option List Screens Units of measure is an example of an options list Press to scroll up the list and to scroll down through the list...

Страница 20: ...her set point crossing before restarting the count from zero LATCH Locks relay in energized state If Latch is chosen once energized by the set point time delay the relay will remain energized until re...

Страница 21: ...006 30007 4 Flow 2 Total Input Register 30008 30009 BACnet The Model 3100 can be configured to communicate on a BACnet RS 485 MSTP Master Slave Token Passing system Configuration is via the front pane...

Страница 22: ...ata bits 1 stop bit no parity and no flow contr 6 When connected a symbol will appear in the upper left corner of the main HyperTerminal display screen 7 Press the Enter Key Both the Rx and Tx LED s o...

Страница 23: ...ore amenable to scripting it still accepts the same commands Any command entered without an sign and variable will display the current setting Example Typing display line 1 returns 0 which is the vari...

Страница 24: ...low rate min current flow 1 2 sensor avg 0 100 averaging time constant in seconds flow 1 2 rate units 0 19 flow channel rate units to display 0 GPM 1 gal s 2 gal hr 3 Mgal day 4 L s 5 LPM 6 L hr 7 ft3...

Страница 25: ...1 5 rate x totalizer rate relay 1 5 ctime 0 10000 pulse width in milliseconds relay 1 4 latch on off turn on off relay latching relay 1 4 setpoint x relay 1 4 setpoint x relay 1 4 relpoint x relay 1...

Страница 26: ...reading from analog input AD converter channel 1 32 Error reading from analog input AD converter channel 2 36 Error writing to analog input AD converter channel 1 37 Error writing to analog input AD...

Страница 27: ...r sourcing Sinking 30V DS 0 mA max 3 V 20 mA min Sourcing 600 max load USB Communication Provides complete access to all programming and operation features Requirements USB 2 0 A to Mini B five pin ca...

Страница 28: ...ico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa G...

Отзывы: