Impeller Assembly and Shaft Replacement

IMPELLER ASSEMBLY AND SHAFT REPLACEMENT

If you are replacing an existing Badger Meter sensor and have already calibrated your flow monitor/endpoint, no calibration 

changes are necessary . For installation of a new flow monitor or for relocation of a sensor in a new pipe size, refer to the 

calibration instructions in this manual . 

 

1 .  Depressurize and vent the pipe, and remove power to the installation from which the sensor is to be removed .
2 .  Remove the clevis pin .
3 .  Remove the sensor from the tee .

OTEE:

N

Note the impeller blade orientation relative to the flow arrows . To maintain proper calibration, the impeller must 

be reinstalled in the same manner with the impeller blades pointing toward the flow source as indicated by the 

flow arrows .

4 .  To remove the old impeller blade assembly, push the old shaft out of the sleeve with the new shaft (or small diameter rod) 

just far enough to grab the end with a pair of pliers, and pull the shaft completely out . The impeller assembly will now be free, 

and will drop out . 

5 .  Inspect the shaft and bearings for wear and replace as necessary .
6 .  See 

Figure 2

 below . To reinstall, position the impeller in the cavity, oriented so that the impeller blades point in the flow 

direction (as described in the 

NOTE

 above) . The flow direction arrow on the top of the sensor housing should point 

downstream with the impeller blades pointing upstream .

7 .  Carefully push the shaft through the housing and impeller, taking care not to damage the bearings . Make sure the shaft is 

inserted far enough so that it clears the housing on each side of the impeller housing . 

OTEE:

N

If the shaft is not carefully installed, the bearing can be deformed, preventing free rotation .

8 .  Inspect the O-rings for damage and replace as necessary . Clean the O-rings and the sleeve, and relubricate with silicone 

grease from the packet provided, or use another acceptable lubricant .

9 .  Install the sensor into the tee so the flow arrow points in the direction of the actual flow . 
10 . Install or replace the clevis pin .
This completes the replacement procedure . The system can now be repressurized and tested .

NOTE DIRECTION OF ARROW

USE PLIERS HERE

NOTE DIRECTION OF

IMPELLER

USE METAL PIN TO

REMOVE CERAMIC SHAFT

Figure 2:  Impeller Assembly and Shaft

Page 9 

February 2018

SEN-UM-01664-EN-10

Содержание Impeller Data Industrial 228PV Series

Страница 1: ...Flow Sensors Series 228PV PVC Tee Type Flow Sensors SEN UM 01664 EN 10 February 2018 User Manual...

Страница 2: ...Sensor 3 Model 228PV 3 Mechanical Installation 5 General Information 5 Mechanical Installation Procedure 5 Electrical Installation 6 Standard Sensors 6 IR Sensors 6 Intrinsically Safe Electrical Inst...

Страница 3: ...ides several basic sensor configurations using the same impeller element This allows for a wide range of applications and pipe sizes Sensors are normally supplied with 20 feet 6 meters of 2 conductor...

Страница 4: ...quipment may be impaired ATTENTION Le capteur de d bit de type turbine d crit dans le pr sent manuel n est pas destin tre utilis dans des applications de s curit critiques L utilisation du dispositif...

Страница 5: ...ductions should not be present in this length of pipe The preferred location for the sensor around the circumference of a horizontal pipe is at the 12 o clock position The sensor should never be locat...

Страница 6: ...ors The sensor leads are supplied with watertight caps over the ends NOTE N DO NOT remove the plastic caps from the sensor leads until ready to splice 1 Use a twisted pair cable suitable for direct bu...

Страница 7: ...ctors To make sure the installation is intrinsically safe the connection of the intrinsically safe sensor to instruments and or power supplies must take place using an approved intrinsically safe barr...

Страница 8: ...f each tee sensor Badger Meter sensors operate both above and below the indicated flow rates However good design practice dictates the use of this range for best performance Sensors should be sized fo...

Страница 9: ...t the shaft and bearings for wear and replace as necessary 6 See Figure 2 below To reinstall position the impeller in the cavity oriented so that the impeller blades point in the flow direction as des...

Страница 10: ...ecommended design flow range Transducer Excitation Supply voltage 8V DC min 35V DC max Quiescent current 600 A typical OFF State VHigh Supply voltage 600 A Supply impedance ON State VLow 1 2V DC 40 mA...

Страница 11: ...must be between 8 24V DC for the sensor to operate If the voltage is acceptable reconnect the flow sensor and re measure Depending on the age of the flow sensor the voltage should drop slightly Curren...

Страница 12: ...DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur w Poland 48 32 236 8787 Europe Middle...

Отзывы: