background image

Register output specifications & wiring 

Page 12/15 

 

 

AC_ILR_BA_02_1805 

 

5.2.  Dual pulse (model ILR 720)  

Register wiring 

External DC+: Yellow 

External ground: Brown 

Pulse output 1: White 

Pulse output 2: Green 

External reset: Grey 

DC input: 8 to 24 VDC; 20 to 40mA 

Outputs:  Dual-pulse  output  with  internal  pull-up  resistor;  optional  open  collector 

output with output jumper removed; dual pulse output forms a quadrature signal for 

direction of flow. 

Inputs: External reset pulled low to reset the batch totalizer. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 14: ILR 720 wiring 

 

 

 

ILR 720 

Yellow 

White 

Brown 

Ground 

Pulse 

output 

8-24V DC input 

Green 

Output 

jumper 

Grey 

External 

reset 

Output 

jumper 

+3.0V DC 

Содержание ILR710

Страница 1: ...Badger Meter Europa GmbH Registers type ILR7XX and ILR7XXT INSTALLATION AND OPERATION MANUAL May 2018 AC_ILR_BA_02_1805...

Страница 2: ...s with display 6 3 5 Changing the display mode for all ILR models with display 7 3 6 Exiting programming mode for all ILR models with display 7 4 Additional programming Industrial analog and industria...

Страница 3: ...ectric shock Failure to properly earth a unit may cause damage to that unit or data stored within it Protection class The device has protection class IP 65 and needs to be protected against dripping w...

Страница 4: ...mmendations Page 2 15 AC_ILR_BA_02_1805 RoHs Our products are RoHs compliant Battery disposal The batteries contained in our products need to be disposed of as per your local legislation acc to EU dir...

Страница 5: ...press either the TOTAL or RESET button once 2 2 Status The status indicators are RESET and TOTAL 2 3 Totalizers The top row of indicators is the batch totalizer This totalizer displays the cumulative...

Страница 6: ...are calculated in volume unit per minute 2 5 Battery The LBat indicator will indicate when the battery is approaching end of life When the indicator is illuminated the 2 3AA 3 0 VDC lithium battery i...

Страница 7: ...ale factor programming 3 2 Scale factor for all ILR models with display The register collects input pulses from the oval gear meter and then determines the appropriate display output using the scale f...

Страница 8: ...9999 99 on the top row integer values are displayed on the bottom row Example 10 45 would display 45 on the top row and 10 would be displayed on the bottom row 2 When finished adjusting the pulse rate...

Страница 9: ...le a letter is flashing on the display press the RESET button to select either totalizer or flow rate 2 Upon completion of this setting the programming of the industrial standard register and the indu...

Страница 10: ...s The Output Pulse Length should be set to less than the value of t Per the equation Maximum meter flow rate in GPM or l m t x 1000 60X output pulse rate where t the required pulse rate in millisecond...

Страница 11: ...o advance to the next screen To advance to the next programming screen hold the TOTAL button for one second 4 3 Analog maximum flow rate for models ILR750 and ILR750T Indicated by a H on the left hand...

Страница 12: ...he plus symbol will not be shown Once the adjustment of the linearisation is completed press and hold the TOTAL button for one second to advance to the next linearisation point Number 9 at the left ha...

Страница 13: ...Yellow External ground Brown Pulse output White DC Input 8 to 24 VDC 20 to 40mA Outputs Pulse output with internal pull up resistor optional open collector output with output jumper removal pulse out...

Страница 14: ...nput 8 to 24 VDC 20 to 40mA Outputs Dual pulse output with internal pull up resistor optional open collector output with output jumper removed dual pulse output forms a quadrature signal for direction...

Страница 15: ...ngs Max power 10W not to exceed max voltage 200 VDC peak AC max current 0 5A DC peak AC Outputs Raw reed switch output with no signal conditioning Pulse per unit of measure IOG series Note Actual puls...

Страница 16: ...DC 20 to 40mA Outputs Analog 4 to 20mA output in loop powered configuration external load of 50 ohms to 250 ohms flow rate is linear scaled between 4mA minimum and 20mA maximum set points flow rates b...

Страница 17: ...ir Harmlessness declaration Page 15 15 AC_ILR_BA_02_1805 6 Return of goods for repair Harmlessness declaration Please refer to our claims return form harmlessness declaration under www badgermeter de...

Страница 18: ...line Phone 49 7025 9208 0 or 46 Fax 49 7025 9208 15 Badger Meter Europa GmbH Subsidiary of Badger Meter Inc USA N rtinger Strasse 76 72639 Neuffen Germany E mail badger badgermeter de www badgermeter...

Отзывы: