background image

HR-LCD Pulse

HR-LCD PULSE

The HR-LCD pulse is a permanently sealed, electronic LCD register that produces a scaled output .

 

The HR-LCD scaled pulse 

register is available with a single output wire connection . Refer to 

Figure 3

 .

Wire Connections

Scaled output cable

 (Flying lead for field splice connection)

◊  For power, connect the 

red

 wire (positive) and the 

black

 wire (negative) .

◊  For signal, connect the 

green

 wire (positive) and the 

black

 wire (negative) .

Power/Scaled Cable

GREEN - Scaled Pulse

BLACK - Ground for Signal and Power

RED - 9-50V DC External Power + 

Figure 3:  HR-LCD pulse wiring

Measurement Resolution

Recordall 

 Disc Series

Size (in.)

Scaled  

(pulse/unit)

gal

ft

3

m

3

LP

5/8

1

10

100

M25

5/8

1

10

100

M35

3/4

1

10

100

M40

1

1

10

100

M55

1

1

10

100

M70

1

1

10

100

M120

1-1/2

0 .10

1

10

M170

2

0 .10

1

10

Recordall  

Turbo Series

Size (in.)

Scaled  

(pulse/unit)

gal

ft

3

m

3

T160

1-1/2

0 .10

1

10

T200

2

0 .10

1

10

T450

0 .10

1

10

T1000

4

0 .10

1

10

T2000

6

0 .01

0 .10

1

T3500

8

0 .01

0 .10

1

T5500

10

0 .01

0 .10

1

T6200

12

0 .001

0 .01

0 .10

T6600

16

0 .001

0 .01

0 .10

T1000

20

0 .001

0 .01

0 .10

Recordall 

Compound Series

Size (in.)

Scaled (pulse/unit)

gal

ft

3

m

3

High Side T200

2

0 .10

1

10

Low Side M25

2

1

10

100

High Side T450

3

0 .10

1

10

Low Side M25

3

1

10

100

High Side T1000

4

0 .10

1

10

Low side M35

4

1

10

100

High Side T2000

6

0 .01

0 .10

1

Low Side M35

6

1

10

100

High Side T3500

8

0 .01

0 .10

1

Low side M120

8

0 .10

1

10

Page 10 

April 2020

REG-UM-02466-EN-02

Содержание HR-LCD 4-20

Страница 1: ...High Resolution LCD Registers HR LCD 4 20 scaled unscaled HR LCD Pulse REG UM 02466 EN 02 April 2020 User Manual...

Страница 2: ...High Resolution LCD Registers HR LCD 4 20 scaled unscaled HR LCD Pulse Page ii April 2020 REG UM 02466 EN 02...

Страница 3: ...re 6 9 Digit Totalization 6 Rate of Flow 7 Meter Model Information 7 Installing the Register 7 Bayonet Mount 7 HR LCD 4 20 scaled unscaled 8 Wire Connections 8 Measurement Resolution 8 Specifications...

Страница 4: ...High Resolution LCD Registers HR LCD 4 20 scaled unscaled HR LCD Pulse Page iv April 2020 REG UM 02466 EN 02...

Страница 5: ...ity to operate the equipment DESCRIPTION High resolution registers are fully electronic solid state devices with no moving parts The devices come standard as factory programmed with the option for pro...

Страница 6: ...oot or cubic meter Example 123456 displayed value x 10 multiplier value 1234560 Extended Visual Reading Resolution Typical Billing Segments Status Indicators IR Programming Port 00 00 4 Digit Date Cod...

Страница 7: ...appears and Compound meters are indicated by a C See examples below Model 25 Disc Series Meter Calibrated in Gallons Model 450 Turbo Series Meter Calibrated in Gallons 2 in Low Side Compound Series M...

Страница 8: ...38 279 55 M70 1 1 10 100 46 773 349 884 12355 278 70 M120 1 1 2 0 10 1 10 23 866 178 533 6304 435 120 M170 2 0 10 1 10 14 565 108 950 3847 303 170 Recordall Turbo Series Size in Scaled pulse unit Unsc...

Страница 9: ...black wire negative Scaled digital output from the register has a default resolution of 1 10th of the register test circle resolution may vary in some cases The movement of the meter magnet is conver...

Страница 10: ...ies Size in Scaled pulse unit gal ft3 m3 LP 5 8 1 10 100 M25 5 8 1 10 100 M35 3 4 1 10 100 M40 1 1 10 100 M55 1 1 10 100 M70 1 1 10 100 M120 1 1 2 0 10 1 10 M170 2 0 10 1 10 Recordall Turbo Series Siz...

Страница 11: ...nt 100 mA Pulse Width 50 ms programmable 30 100 ms Power Input Voltage Range 9 50V DC supply Max Load Resistance Ohms 50 Ohms 50 Ohms supply voltage 9V Battery Lithium thionyl chloride AA cell fully e...

Страница 12: ...alarm remains active for 35 days The alarm automatically clears after 35 days if reverse flow condition has not recurred Suspected leak Register detects 24 hours without one 15 minute interval of no...

Отзывы: