background image

PROGRAMMING

MPORTANT

I

You must connect terminals 1 and 5 together to enable the programming mode. After all programming is complete, remove the 

connection between terminals 1 and 5 to prevent the unit from being reprogrammed by mistake.

To access the programming screens, press and hold the 

 key while repeatedly pressing the 

 key until the 

Program 

Mode

 (1 through 6) you want displays on the screen .

1 01.000

Mode 1: Totalizer Scaler lets you enter the count scale factor . The far right digit will be flashing . 
1 .  Press 

 to select a digit value or press and hold 

 to scroll through the numbers . 

2 .  Press 

 to move the flashing digit one place to the left . 

3 .  Press 

 to change the value of the digit . 

4 .  Repeat this process until all digits are set correctly . 

NOTE:

N

You can program the ER-10 for a scaled pulse input that applies fixed zeros so one pulse 

can represent 1, 10 or 100 units .

Mode 1: 

Set to 01 .0000 to show reading in 1s; ER-10 has 

no

 fixed zeros; One pulse = 1 (ex . 12345678) 

Set to 10 .0000 to show reading in 10s; ER-10 has 

one

 fixed zero; One pulse = 10 (ex . 12345670

Set to 00 .0000 to show reading in 100s; ER-10 has 

two

 fixed zeros; One pulse = 100 (ex . 12345600

2 000000

Mode 2: Totalizer Decimal Point lets you enter the decimal point display on the totalizer screen . 
1 .  Press and hold 

 and then press 

 to move from screen one to screen two . 

2 .  Press 

 to move the decimal point to the new position .  

3   0000

Mode 3: Rate Scale Factor display shows the lowercase letter d on the right when it is time to 

enter the decimal point position for the rate scaler . 

OTE:

N

This decimal point is used for the rate scaler only and will not appear on the ratemeter 

screen . 

1 .  Press 

 to change the first digit to a new value . 

2 .  Press 

 to select the next digit to be changed . 

3 .  Repeat this process until all the digits are correct . 
4 .  When the d displays, press 

 to move the decimal point to another position .  

4   0000

Mode 4: Rate Scale Factor Decimal Point lets you enter the decimal point position for the 

ratemeter run-mode display . The display shows the 

Program Mode

 number (4) and four zeros . 

Press 

 to move the decimal point to another position . 

 

5   1

Mode 5: Rate ×1/×10 selects the 

Rate Display Multiplier

 of one or ten . Selecting rate ×10 adds a 

zero to the far right of the display . This zero will not change value and does not affect the decimal 

point . The display shows the 

Program Mode

 number (5) at the left and a 1 at the right . 

Press 

 to select 1 or 10 . 

6    r

Mode 6: Reset Key Enable/Disable determines if the front panel 

Reset

 key will function . The 

display shows the 

Program Mode

 number 6 on the left and the lowercase letter r on the right . 

1 .  Press 

 to select an option (R=Reset, NoR=Non-Reset) .

OTE:

N

The Reset (RST) terminal on the rear panel is still active when the front panel 

Reset

 

function is disabled . 

2 .  To exit the programming mode, remove the connection between terminals 1 and 5 .

Programming

Page 9 

September 2017

REG-UM-00471-EN-07

Содержание ER-10

Страница 1: ...Resettable Totalizer and Rate of Flow Indicator REG UM 00471 EN 07 September 2017 User Manual This product contains Lithium batteries Read this manual before attempting any installation wiring or ope...

Страница 2: ...Industrial Registers Models ER 10 ER 10 R ER 10H Digital Resettable Totalizer and Rate of Flow Indicator Page ii September 2017 REG UM 00471 EN 07...

Страница 3: ...rminals 7 Transmitter Connections 7 Operation 8 Display Types 8 Control Keys 8 Programming 9 Programming Calculations 10 Totalizer Programming 10 Rate of Flow Programming 10 Pulse Output Programming 1...

Страница 4: ...Industrial Registers Models ER 10 ER 10 R ER 10H Digital Resettable Totalizer and Rate of Flow Indicator Page iv September 2017 REG UM 00471 EN 07...

Страница 5: ...mer Service 1 800 876 3837 PRODUCT DESCRIPTION The ER 10 ER 10 R and ER 10H are external or battery powered electronic registers that display rate of flow and total flow They have independent programm...

Страница 6: ...o meet NEMA 4X Mode select programming button Gasket installed Install mounting clip Figure 1 Panel installation Battery Installation Replacement The ER 10 ER 10 R ER 10H are powered by one 3V Lithium...

Страница 7: ...bers in parenthesis refer to the terminal numbers on the ER 10 Connect the wire coming from the transmitter to the corresponding terminal number for the ER Series Remote models Connecting to a generic...

Страница 8: ...Total Rate key during normal operation the ER 10 toggles the display between the Flow Total and the Flow Rate The letter R on the left of the screen indicates that the Flow Rate is being displayed Pro...

Страница 9: ...ecimal point to the new position 3 0000 Mode 3 Rate Scale Factor display shows the lowercase letter d on the right when it is time to enter the decimal point position for the rate scaler NOTE N This d...

Страница 10: ...ls hour Rate scale factor To determine the Rate Scale Factor Program Mode 4 use the following formula Rate Scale Factor Seconds Transmitter Pulses per Unit Decimal Factor where Seconds is the number o...

Страница 11: ...0 52 396 1484 689 3 4 35 RCDL 126 671 33 463 947 566 1 40 RCDL 89 781 23 717 671 610 1 55 RCDL 58 064 15 339 434 351 1 70 RCDL 46 752 12 350 349 726 1 1 2 120 RCDL 23 867 6 305 178 539 2 170 RCDL 14 5...

Страница 12: ...3 Transmitter defective 1 Check programming 2 Check connections 3 Repair or replace transmitter Cannot program Program enable jumper is not installed or is installed improperly Install jumper from Te...

Страница 13: ...tank or into a calibrated vessel 5 Determine the number of pulses per gallon by dividing the indicator reading by the number of gallons of fluid in the vessel Use this value for your calculations Exam...

Страница 14: ...the balance of the above steps to re assemble the unit Disc meter 1 Remove the front cover on the ER 10 unit and disconnect the sensor wiring 2 Loosen the side seal screw on the assembly adapter twist...

Страница 15: ...rogrammable Rate Indicator Digits 4 5 4 calculated 5 displayed with fixed zero in LSD Scaler range 0 001 9999 Decimal point 5 positions programmable Accuracy 0 2 Update time 0 7 seconds Zero time 10 s...

Страница 16: ...alupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur w Poland 48...

Отзывы: