PULSE INPUT (AR/t)

The AR/t transmitter sends pulse signals to the AR/e controller.
Each pulse represents a specific quantity of water for a
particular meter size.

Meter

Pulse Rate

RCDL Models 25, 35 and 40

1 pulse = 1 Gallon

RCDL Models 70, 120, 170 and
Industrial Turbo 2", 3" and 4"

1 pulse = 10 Gallons

Industrial Turbo 6"

1 pulse = 100 Gallons

Reed switch transmitters have two black leads. Connect these
leads to terminals 1 & 2 in any order.

Electronic transmitters have one black lead and one white
lead. Connect these leads as per the diagram at right.

In the Automatic mode, the relay will be energized at the end
of the batch for the amount of seconds programmed via the
SIGNAL DURATION procedure (see page 6). The relay con-
tacts can be wired to a timer or regeneration cycle controller.

REMOTE START & STOP (OPTIONAL)
Remote Start Input

When activated, it will abort a batch before its completion,
initiating tank regeneration at the same time.

In the 

Manual 

mode, the output relay will be energized

indefinitely and the display will be reset to zero until the STOP
command is received.

In the 

Automatic 

mode, the output relay will be energized for

the programmed duration (see operation section page 6) and
the display will be reset to the batch preset value and continue
to count down when pulses are received.

If a 

START 

command is received while the LOCKOUT is active,

the command will be stored in memory and acted upon as soon
as the LOCKOUT signal is terminated.

Remote Stop Input

Is used to terminate the output signal. This function is enabled
after a START command is received or after the output relay
is energized at the end of the batch.

In the 

Manual 

mode, it will terminate the output signal, reset

the counter to the batch preset value and enable the transmit-
ter pulse input.

PULSE INPUT (RTR)

The RTR transmitter/register sends pulse signals to the AR/e
controller. Each pulse represents a specific quantity of water
for a particular meter size.

Meter

Pulse Rate

RCDL Models 25, 35, 40, & 70

1 pulse = 1 Gallon

RCDL Models 120 and 170

1 pulse = 10 Gallons

RCDL Turbo Series 1 1/2" - 6"

1 pulse = 100 Gallons

These transmitters have one black lead and one red lead.
Connect these leads as per the diagram.

RELAY OUTPUT

The regeneration signal relay is energized at the end of the
batch or when a START command is initiated.

In the Manual mode, the relay will remain energized until the
SIGNAL STOP is initiated. The relay contacts can be used to
activate a warning device to indicate that manual regenera-
tion of the system is necessary.

In the 

Automatic 

mode, it will only terminate the output signal.

LOCKOUT INPUT (OPTIONAL)

To avoid simultaneous regeneration of multiple tanks, a lock-
out signal can prevent a controller from sending a regenera-
tion signal at the end of the batch.

Содержание AR/e

Страница 1: ...adgerMeter Inc Model AR e AR t RTR Service Information File manual for future reference and service Serial Number Date Installed Service Line Operator IMPORTANT Read this manual before attempting any...

Страница 2: ...accessories for any physical damage such as scratches loose or broken parts or any other sign of damage that may have occurred during shipment Note If damage is found request an inspection by the carr...

Страница 3: ...Note Terminalblockassemblyunplugsfromprintedcircuit board for ease in connecting field wiring Disconnect all power to the unit before connecting wires to any of the terminals Do not use machine power...

Страница 4: ...re received IfaSTARTcommandisreceivedwhiletheLOCKOUTisactive the command will be stored in memory and acted upon as soon as the LOCKOUT signal is terminated Remote Stop Input Isusedtoterminatetheoutpu...

Страница 5: ...0000 X100000 no label no label RCDL 70 AR t 120 170 and Ind Turbo 2 3 4 OPERATION The basic function of the AR e controller is to provide a signal to external equip ment once a predetermined amount of...

Страница 6: ...se non rechargeable battery If you find it necessary to send unit to factory contact your Badger representative or dealer for material return authori zation Packagetheunitproperly andincludeabriefdesc...

Страница 7: ...1 Defective relay 1 Replace relay See page 7 energized at end of batch or 2 Lockout is active 2 Check switch 2 position and wiring to when a START command is lockoutterminals received Signal indicator...

Страница 8: ...pt to the extent an outstanding bid obligation exists BadgerMeter Inc P O Box 245036 Milwaukee WI 53224 9536 Telephone 414 355 0400 877 243 1010 Fax 414 355 7499 866 613 9305 www badgermeter com Copyr...

Отзывы: