This will open the MS/TP Check screen as shown below .
Press the Retrieve Parameters button which should display 340MB
transmitter object data as shown below .
The LED located next to the 340MB network port, labeled “Comm
LED”, will flash once to visually confirm communication between
the 340MB transmitter and Modbus master controller .
Use the scroll bar to view all object data .
If the 340MB transmitter fails to communicate with the Modbus
master controller, check that the correct polling address was
entered in step 12 found on page 8, the integrity of the network
port connection and, if necessary, settings in the Modbus master
controller .
Press the Close button to return to the Main Screen .
NETWOrK SET-uP
The following Register Map is provided to assist in the program-
ming of the Modbus network .
MOdEL 340MB rEGISTEr MAP
Register Name
Address
Data Type
R/W
Inlet Temperature
0
IEEE754 Float
Read Only
Outlet Temperature
2
IEEE754 Float
Read Only
Input Frequency
4
IEEE754 Float
Read Only
Total Volume
6
IEEE754 Float
R/W
Total Energy
8
IEEE754 Float
R/W
Flow Rate
10
IEEE754 Float
Read Only
Energy Rate
12
IEEE754 Float
Read Only
K Factor
14
IEEE754 Float
R/W
Offset
16
IEEE754 Float
R/W
Temperature Calculation Mode
18
IEEE754 Float
R/W
Flow Filter Coefficient
20
IEEE754 Float
R/W
Temperature Filter Coefficient
22
IEEE754 Float
R/W
Specific Heat Capacity
24
IEEE754 Float
R/W
Fluid Density
26
IEEE754 Float
R/W
Temp In A Coefficient
28
IEEE754 Float
R/W
Temp In B Coefficient
30
IEEE754 Float
R/W
Temp In C Coefficient
32
IEEE754 Float
R/W
Temp In Offset
34
IEEE754 Float
R/W
Temp Out A Coefficient
36
IEEE754 Float
R/W
Temp Out B Coefficient
38
IEEE754 Float
R/W
Temp Out C Coefficient
40
IEEE754 Float
R/W
Temp Out Offset
42
IEEE754 Float
R/W
All variables above take two Modbus register locations.
(4 bytes). Note some registers are read only.
MOdEL 340MB FACTOrY dEFAuLT SETTINGS
The table below is a list of factory default setting for all 340MB
variables . These settings can be changed by accessing the pa-
rameters sensor (page 7) or Configure MS/TP screen (page 8)
to best fit your application . As new valves are assigned, they can
be written in the blank provided next to each variable for future
reference .
Description
Default Value
Customer Value
Flow Sensor Type
Pulse
1
e
u
l
a
V
"
K
"
"Offset" Value
0
m
p
g
e
t
a
R
w
o
l
F
Flow Total
gallons
Temperature
°F
Energy Calculation
absolute
Temperature Sensor Type
thermistor
Energy Rate
kBTU/hr
Energy Total
BTU
Flow Filter Coefficient
5
Energy Filter Coefficient
1
Factory Default Settings - Model 340MB
PRELIMINARY