![Badger Meter 340 MB Btu Series Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/badger-meter/340-mb-btu-series/340-mb-btu-series_installation-and-operation-manual_3403591010.webp)
10
Communication Port
RS-485 with termination, pull up and
pull down jumpers
Operating Temperature
0° C to +70° C
32° F to +158° F
Storage Temperature
-40° C to +85° C
-40° F to +185° F
Weight
4 .8 oz . with connector headers
installed
SENSOr CALIBrATION
Badger Meter
Use K and Offset provided in sensor
owner’s manual
Other Sensors
Check with factory
uNITS OF MEASurE
Flow measurement
Rate:
gpm, gph, l/sec, l/min, l/hr, ft3/sec,
ft3/min, ft3/hr, m3/sec, m3/min, m3/hr
Total:
gallons, liters, cubic feet, cubic
meters
Energy measurement
Rate
kBtu/min, kBtu/hr, kW, MW, hp, tons
Total
Btu, kBtu, MBtu, kWh, MWh, kJ, MJ
Temperature units
Fahrenheit, Centigrade
PrOGrAMMING
Requires PC or laptop running
Windows
®
2000, XP
Badger Meter Model 340BN
programming kit containing software
and Model A-301 programming cable is
required for programming and setup
SPECIFICATIONS
Power
Power supply options:
12-24 VAC rms Tolerance
12-24 VDC Tolerance
Current draw:
< 70mA @ 12 VDC
Flow Sensor Input
Pulse type sensors:
Signal amplitude:
2 .5 VDC threshold
Signal limits:
Vin < 35V (DC or AC peak)
Frequency:
0-10kHz
Pull-up:
15 VDC @ 2 k
Ω
Source Impedance
Sine wave sensors:
Signal amplitude:
30 mV p-p threshold
Signal limits:
Vin < 35V (DC or AC peak)
Frequency:
0-10kHz
Power out terminal
Excitation voltage 3 wire sensors:
15 VDC @ 500
Ω
Source Impedance
Temperature Sensor Input
2 required:
10 k
Ω
thermistor, 2 wire, type II,
10 k
Ω
@ 25°C
100
Ω
platinum RTD, DIN
calibration curve, conforms to
IEC-751 Standard
1000
Ω
platinum RTD, DIN
calibration curve, conforms to
IEC-751 Standard
calibration range 0-150°C
Metal Enclosure dimensions
Plastic Enclosure dimensions
PRELIMINARY