3-11
Installation & Operation Manual
Modbus Register Map
MODEL 340BN/MB Register Map
Register Name
Address
Data Type
Read/Write
Temperature 1
40001 + 40002 IEEE 754 Float Read Only
Temperature 2
40003 + 40004 IEEE 754 Float Read Only
Flow Input (Hz)
40005 + 40006 IEEE 754 Float Read Only
Total Flow
40007 + 40008 IEEE 754 Float R/W
Total Energy
40009 + 40010 IEEE 754 Float R/W
Flow Rate
40011 + 40012 IEEE 754 Float Read Only
Energy Rate
40013 + 40014 IEEE 754 Float Read Only
K Factor
40015 + 40016 IEEE 754 Float R/W
Offset
40017 + 40018 IEEE 754 Float R/W
Temp. Calc. Mode 40019 + 40020 IEEE 754 Float R/W
Flow Filter Coef.
40021 + 40022 IEEE 754 Float R/W
Temp. Filter Coef. 40023 + 40024 IEEE 754 Float R/W
Specific Heat
40025 + 40026 IEEE 754 Float R/W
Fluid Density
40027 + 40028 IEEE 754 Float R/W
T1 A Coefficient
40029 + 40030 IEEE 754 Float R/W
T1 B Coefficient
40031 + 40032 IEEE 754 Float R/W
T1 C Coefficient
40033 + 40034 IEEE 754 Float R/W
Temp 1 Offset
40035 + 40036 IEEE 754 Float R/W
T1 A Coefficient
40037 + 40038 IEEE 754 Float R/W
T1 B Coefficient
40039+ 40040
IEEE 754 Float R/W
T1 C Coefficient
40041 + 40042 IEEE 754 Float R/W
Temp 1 Offset
40043 + 40044 IEEE 754 Float R/W
RS-485 Network Configuration – BACnet
Figure 29: BACnet Option
Select BACnet, to access the BACnet pull down menus.
Select the BAUD rate to match other devices on the network.
BACnet Device Name can be set to help identify this device and location.
BACnet Device ID ( Incidence #) is a unique number to identifies this device on the network.
Typically, the first part of the number is the same network #, and the last two characters are the same as the Address.
This is not a requirement, but can help in system planning.