200 Series Metal Tee Sensors Matrix (½" to 2½")

Example:

2

x

x

x

x

x

-

x

x

x

x

STYLE

Tee Mounted Insert Sensor ( 2" and 2.5" only)

28

Cast Bronze Tee (1/2" to 1.5"only)

50

M ATERIAL

Brass/Bronze

BR

Stainless Steel ( 2" and 2.5" only)

SS

Tee - Carbon Steel Sensor Brass

CB

Tee - Carbon Steel Sensor Stainless Steel

CS

Size

0.5"

05

0.75"

07

1"

10

1.25"

12

1.5"

15

2"

20

2.5"

25

Electronics Housing

PPS

0

ELECTRONICS

Magnetic

2

FM/CSA Approved

4

Standard

5

 

IR-Irrigation

6

High Temperature

8

O-RING

Viton

0

EPDM

1

Buna N

8

SHAFT

Zirconia Ceramic

0

Hastalloy C

1

Tungsten Carbide

2

Titanium

3

Monel

5

316 Stainless Steel

6

Tantalum

7

IM PELLER

Nylon

1

Tefzel

2

BEARING

Pennlon

1

Tefzel

2

Teflon

3

Mechanical Installation

General

The accuracy of flow measurement for all flow measuring 
devices is highly dependent on proper location of the 
sensor in the piping system.  Irregular flow velocity 
profiles caused by valves, fittings, pipe bends, etc. can 
lead to inaccurate overall flow rate indications even 
though local flow velocity measurement may be accurate.  
A sensor located in the pipe where it can be affected by 
air bubbles, floating debris, or sediment may not achieve 
full accuracy and could be damaged.  Badger Meter flow 
sensors are designed to operate reliably under adverse 
conditions, but the following recommendations should be 
followed to ensure maximum system accuracy:

1)  Choose a location along the pipe where 10 pipe diam-

eters upstream and 5 pipe diameters downstream of 
the sensor provide no flow disturbance. Pipe bends, 
valves, other fittings, pipe enlargements and reduc-
tions should not be present in this length of pipe.

2) The preferred location for the sensor around the 

circumference of a horizontal pipe is on top.  If trapped 
air or debris will interfere, then the sensor should be 
located further around the pipe from the top but not 
more than 45 degrees from top dead center.  The 
sensor should never be located at the bottom of the 

pipe, as sediment may collect there.  Locations 
off top dead center cause the impeller friction to 
increase, which may affect performance at low 
flow rates.  Any circumferential location is correct 
for installation in vertical pipes. Rising flow 
preferred to reduce effects of any trapped air.

Mechanical Installation for 228BR, 228CB, 

228CS, and 228SS

                     

These tee-type sensors have a factory set inser-
tion depth and alignment.

Warning: do not disturb the position of 

thread hex adapter or the lower two nuts on 

the threaded rods  

 

 of the hex 

adapter. This could lead to inaccurate calibra-

tion and faulty reading of the ἀow rate.  

Remove sleeve assembly by removing the top 
7/16" nuts only. Pull the sleeve assembly straight 
out of the mounting adaptor.

To install the sensor tee

1) 

There must be free, unrestricted pipe for 

at least 10 diameters upstream and 5 diameters 
downstream of the tee.  

note: If soldering of 

threaded adapters is to be done near the as-

sembly, remove the sensor sleeve to prevent 

heat damage to O-rings and plastic parts.

2) 

Apply pipe compound over the first 3 or 4 

threads of the mating pipe.
3)   

Thread the pipe into the sensor tee until 

hand tight.
4) 

Tighten the pipe, using a wrench, an ad-

ditional 1 1/2 turns.

To install sensor in tee

1)   Apply a small amount of silicone grease to O-rings on 

sensor sleeve assembly and chamfer on inside lip of 
tee.  Clean off any grease which could be deposited 
on the impeller.

2)   Align flow arrow on sensor with direction of flow.
3)   Carefully press sleeve straight into hex mounting 

adaptor.

4)   Install 7/16 lock nuts on threaded rod, tighten, do not 

move bottom nuts as they set sensor depth.

5)   Before pressurizing pipe, verify that:

• All threaded connections are tight.

• The flow direction arrow on sensor is aligned with flow 

direction.

• The 7/16 nuts are re-installed on the threaded rods 

above the metal collar.

Mechanical Installation for 250BR

Install with flow label pointing in the direction of flow 
(downstream).

Содержание 228 Series

Страница 1: ...Installation Operation Manual BadgerMeter Inc Badger Series 250 228 Flow Sensors Metal Tee Type Impeller Flow Sensors 872021 Rev 6 4 09...

Страница 2: ...ssembly shaft and O rings are replaceable in the field Badger Meter flow sensors feature a closed six bladed impeller design using a proprietary non magnetic sensing technology The forward swept impel...

Страница 3: ...degrees from top dead center The sensor should never be located at the bottom of the pipe as sediment may collect there Locations off top dead center cause the impeller friction to increase which may...

Страница 4: ...r com 1 DO NOT remove the plastic caps from the sensor leads until ready to splice 2 Use a twisted pair cable suitable for direct burial to connect the sensor to the transmitter monitor or con troller...

Страница 5: ...rdous area The referenced installation drawing shows such apparatus located in a non hazardous location Proper interfacing between the hazardous and non hazardous areas must be pro vided It is of abso...

Страница 6: ...6...

Страница 7: ...S20xx xxxx 1 99 2 747 0 10 100 250BR05xx xxxx sch40 PVC none 0 337379 0 097041 0 8 8 sch80 PVC none 0 338073 0 134854 0 8 8 sch40 steel none 0 356212 0 075729 0 8 8 Type L none 0 350899 0 321666 0 8 8...

Страница 8: ...haft Replacement 10 Install the sensor into the 2 NPT adapter or tee so that alignment hole is facing upstream and flow ar rows point in the direction of the actual flow Since the positioning collar w...