4X”- 6” Deringer 20/30 Maintenance Instructions
BD-INST-4X2030 | Rev A | 09/06/2019 | Copyright 2011 Backflow Direct, LLC
Closing Shut-Off Valves Prior to Maintenance
1.
Slowly rotate Shut-Off Valve #2 Handle (B) clockwise
to the closed position. Flag perpendicular to flow (A).
2.
Slowly rotate Shut-Off Valve #1 Handle (C) clockwise
to the closed position. Flag perpendicular to flow (A).
Note:
When yellow/orange position indicator flags are
parallel with the flow of water the shut-off valves are in the
open position. Before doing any maintenance be sure the
yellow or orange flow indicators (flags) are perpendicular
to the flow of water and valve body indicating shut-off
valves are in the closed position (A).
FLOW
Page 3 of 20
FLOW
Note
B
C
A
A