CHAPTER 1:  INTRODUCTION 

1.1.  Overview 

Congratulations on your purchase of the Bacharach Model 3600 high performance oilless recovery 
system.  Bacharach has worked hard to make the Model 3600 the highest performing, most portable and 
easiest to use recovery system on the market.  We are committed to your complete satisfaction! 

 

Please note that Bacharach requires that a filter be used on the inlet hose coming from the system being 
serviced in order to protect the compressor from particulate.  
A standard filter or filter dryer is suggested.  The compressor warranty will be voided if it is determined that 
a filter was not used during the operation of this equipment. 
 

WARNING:  Before starting the 3600 recovery unit, you MUST OPEN the outlet port on the unit 

and open the port to the recovery tank.  Read the entire operating instruction 
manual before use.  Failure to open the outlet port will cause permanent damage to 
the unit and void the warranty. 

 
WARNING:  You must use a DOT recovery cylinder approved for use with R-410A refrigerant.   

This recovery system is equipped with a high-pressure shutoff switch set to turn the 
unit off at 550 psi.   Using any other cylinder may cause the pressure in the recovery 
cylinder to exceed the cylinder’s pressure rating. 

 
CAUTION:  These instructions are for personnel trained and experienced in the handling of 

refrigerants.  Unqualified individuals should not attempt to operate this equipment.  
Failure to follow proper operating procedures may cause personal injury. 

 

 
 

1.2.  Specifications 

Category 

Description 

Model 

Model 3600 

Description 

Portable Commercial Oilless Recovery System 

Refrigerants 

R12, R-22, R-134a, R-500, R-502, R-410AHP/MP Blends 

Power Source 

120V AC 60 Hz 

Wattage/Amperes 

800 W / 8.0 A max 

Compressor 

½ HP High Performance Oilless 

High Pressure Shutoff 

550 psi 

Dimensions (H x W x D) 

12.0" x 13" x 7.5" 

Weight 

35 Lbs. 

 

Содержание Refrigerant Recovery System 3600

Страница 1: ...ing Vapors reduce oxygen available for breathing and are heavier than air Decomposition products are hazardous Liquid contact may cause frostbite All refrigerant containers equipment and hoses are und...

Страница 2: ...OF UNIT FEATURES 7 3 2 LED DISPLAY 8 CHAPTER 4 RECOVERY 9 4 1 HELPFUL HINTS FOR RECOVERING R 410A 9 4 2 VAPOR LIQUID RECOVERY PROCEDURES 9 4 3 VAPOR RECOVERY HOSE CONNECTION 11 4 4 LIQUID PUSH PULL RE...

Страница 3: ...tire operating instruction manual before use Failure to open the outlet port will cause permanent damage to the unit and void the warranty WARNING You must use a DOT recovery cylinder approved for use...

Страница 4: ...ndensing ensures high recovery rates even on the hottest days Self purging valve completely purges the condenser and tubing eliminating cross contamination when switching between refrigerants Solid st...

Страница 5: ...t 18 inches above the floor This equipment should not be used in the vicinity of spilled or open containers of flammable materials 5 DISCONNECT UNIT BEFORE SERVICING Electrical shock hazard may be pre...

Страница 6: ...in enclosed and low lying areas Avoid contact of liquid with eyes and prolonged skin exposure Wear safety goggles and protective gloves Do not apply open flame or heat unit above 125 F Do not allow re...

Страница 7: ...port It points DOWN when it is open and to the left when CLOSED 6 Inlet Port Refrigerant hose connection for incoming refrigerant vapors 7 Outlet Port Refrigerant hose connection for outgoing refrige...

Страница 8: ...power switch is ON and the compressor is running Red High Pressure Condition Indicates that there is a high pressure condition that must be corrected The internal high pressure switch activates at 55...

Страница 9: ...ns Connect refrigerant hoses to recovery cylinder the unit and A C system as shown in Figure 1 NOTE You must use an external filter drier in the suction line in order to meet the conditions of the uni...

Страница 10: ...NOTE A small amount of inlet pressure may be needed to reset the vacuum switch this is normal Red a Indicates that there is a high pressure condition that must be corrected Check for restrictions or a...

Страница 11: ...very Hose Connections Use only approved DOT recovery cylinders Follow precautions and warnings listed on the cylinder If servicing a system with a compressor burn out use a high acid type filter drier...

Страница 12: ...ng non compressible fluids such as liquid refrigerant however the 3600 has been designed with a special head and valves that enable it to handle liquid directly This feature makes the 3600 easier to u...

Страница 13: ...m switch to the OFF position NOTE Liquid push pull operations do not pull a vacuum on a system You must perform a vapor recovery operation in order to pull the system down to the required vacuum level...

Страница 14: ...Connections Use only approved DOT recovery cylinders Follow precautions and warnings listed on the cylinder If servicing a system with a compressor burn out use a high acid type filter drier and do n...

Страница 15: ...mpressor properly equalizes 2 Turn the system switch to the ON position The LED status will be green NOTE If the compressor fails to start cycle the purge valve from the RECOVERY to PURGE position to...

Страница 16: ...RATE THE MODEL 3600 WITHOUT THE 80 SHUTOFF CORD ATTACHED TO THE RECOVERY CYLINDER Bacharach uses and recommends the Air Conditioning Refrigeration Institute s AHRI guideline K for the safe filling and...

Страница 17: ...20 volt power source Fan Will Not Start Green LED Defective fan Replace fan Obstruction in fan blades Remove obstruction NONE System switch is off Turn system and fan switch to on position Unit Starts...

Страница 18: ...Refrigerant Recovery System Model 3600 18 CHAPTER 6 ELECTRICAL SCHEMATIC...

Страница 19: ...00 2024 0050 VALVE CHECK 1 4 1 00 2024 0270 VALVE 3 WAY BALL 1 8 FEM NPTF DROP 2 00 2030 0031 CONDENSER ASSY MODEL 3600 1 00 2035 0380 SUCTION HOSE 1 4 FLR X 1 4 FLR BLUE 1 00 2035 0390 DISCHARGE HOSE...

Страница 20: ...del 3600 20 World Headquarters 621 Hunt Valley Circle New Kensington PA 15068 Ph 724 334 5000 Fax 724 334 5001 Toll Free 1 800 736 4666 Web site www MyBacharach com E mail help MyBacharach com PRINTED...

Отзывы: