1100-2294 Rev 1 

39 

2.  Tap 

UniApps

 from the pop-up menu that appears.   

3.  Select the 

System

 tab, and then 

Time & Date

. Choose the date from the calendar tool on 

the left side of the screen and the time from the right side of the screen.  

4.  To return to the home page, press and hold the upper right corner again for 3 seconds.  

From the dropdown menu, choose UserApp.  

 

 

Figure 40 - Tap UniApps 

Figure 41 - Choosing the time and date 

Содержание MVR-SC

Страница 1: ...1100 2294 Rev 1 1 ...

Страница 2: ...y registration SERVICE POLICY Bacharach Inc maintains a service facility at the factory Some Bacharach distributors agents may also have repair facilities however Bacharach assumes no liability for service performed by anyone other than Bacharach personnel Repairs are warranted for 90 days after date of shipment sensors pumps filters and batteries have individual warranties Should your analyzer re...

Страница 3: ...s 10 2 2 System Components 11 2 2 1 MVR SC Refrigerant Leak Monitor 11 2 2 2 MVR 300 VRF Refrigerant Leak Detector 11 2 2 3 Ethernet Network Switch 11 2 2 4 Gateway 11 2 2 5 Modbus EZ Wire Kit 11 2 3 Hardware Overview 12 3 Installation 13 3 1 Network Overview 13 3 2 Floorplan Spreadsheet CSV 15 3 3 Gateway IP Address 17 3 4 Hardware Installation 20 3 5 Connecting Relays Alarm Fault 21 3 6 Connecti...

Страница 4: ... Modbus ID Manually 33 5 Operation 35 5 1 Overview of Normal Operation 35 5 2 Alarm Detection 35 5 3 Fault Detection 36 5 4 Communication Comm Error 37 5 5 Event History 38 5 6 Service Mode Screen 40 6 Additional Information 41 6 1 Disposing of the Instrument 41 6 2 Service Center Locations 41 ...

Страница 5: ...ger An imminently hazardous situation which if not avoided will result in death or serious injury Warning A potentially hazardous situation which if not avoided could result in death or serious injury Warning Potential electrical shock hazard which if not avoided could result in death or serious injury Caution A potentially hazardous situation which if not avoided could result in physical injury o...

Страница 6: ...nce de energize the power supply and contact a qualified repair technician or the nearest Bacharach Service Center IMPORTANT Before using this product carefully read and strictly follow the instructions in the manual Ensure that all product documentation is retained and available to anyone operating the instrument IMPORTANT The MVR SC must be installed by a suitably qualified technician who will i...

Страница 7: ...gerant leak detectors for the following High or low PPM alarm events Hardware faults Network connectivity The MVR SC controller will respond to these events as follows Alarm activates the alarm relay flashes the screen to RED activates the audible buzzer Fault activates the fault relay flashes the screen to AMBER activates the audible buzzer Communication Error flashes the screen to BLUE indicates...

Страница 8: ...st screens have the following menu icons 2 1 3 Status Icons Each floor and room will use the following status icons Icon Icon Name Home Alarm list Fault list Comm Error Floor list Icon Icon Name Alarm Fault Comm Error Normal Not yet commissioned ...

Страница 9: ...ach floor will designate the highest severity status from all devices on that floor 2 1 5 Room Device list each floor Detailed view for each MVR 300 room in the system grouped on a given floor Figure 2 Floor List Figure 3 Room Device List ...

Страница 10: ...ng screen tap the gear icon This screen is passcode protected to avoid unintentional changes The Passcode screen appears Enter the passcode for the MVR SC controller to unlock and allow changes The default system passcode for the MVR SC is 6388 Figure 4 System Settings Figure 5 Passcode ...

Страница 11: ...rigerant leak detection for occupied rooms in VRF applications 2 2 3 Ethernet Network Switch An Ethernet network switch is used to provide connectivity between the MVR SC Controller and the individual Modbus Gateways up to 8 ports 2 2 4 Gateway A gateway is used to create small networks of MVR 300 Refrigerant Detectors up to 15 per gateway to ease installation and troubleshooting 2 2 5 Modbus EZ W...

Страница 12: ...gerant Leak Monitor The MVR SC provides centralized alarming and monitoring for all connected MVR 300 Gas Detectors Figure 6 MVR SC Overview Component Description 1 PLC Touch Screen 2 Fault Relay 3 Alarm Relay 4 Modbus 5 Power 24V DC IN 6 Cable Entries 4 ...

Страница 13: ...etwork through an Ethernet switch to the MVR SC Up to seven gateways can be used in a fully populated network The MVR SC provides centralized monitoring of all devices in the network with a 15 second scan rate When creating the floorplan follow these conditions Keep daisy chain segments of MVR 300 devices as near as possible to the gateway to which they connect We recommend keeping this distance u...

Страница 14: ...o eight digits of letters and or numbers It is possible to hardwire up to 15 devices to the controller s Modbus RTU port To indicate these in the floorplan fill in the cells at the bottom of the spreadsheet rows with IP marked Direct Each Gateway s IP Address must be unique If only one gateway is used its IP address should be 192 168 0 1 The IP address for subsequent gateways would be 192 168 0 2 ...

Страница 15: ...rk but only those with floor and room cells populated will be active and displayed Insert the USB stick into a computer that has Excel software installed 1 Open the flash drive and click the example CSV file titled data csv In this file there are columns labeled Index Floor Room Gateway Modbus ID and IPAddress Of those six columns ONLY the middle three Floor Room and Gateway can be edited Figure 1...

Страница 16: ...Error Reference source not found Error Reference source not found Special Notes There can be multiple gateways on a given floor and is not limited to one gateway per floor To have floors in numeric order have them listed as such in the data csv file The data csv file does not do any interior or alphabetical sorting Every assigned room in the data csv file must have a Modbus number assigned The col...

Страница 17: ...es 1 Connect the first Gateway to be changed to a PC using either Ethernet port Power the gateway with 24VDC 2 Download MGate Manager for windows from a https moxa com en products industrial edge connectivity protocol gateways modbus tcp gateways mgate mb3170 mb3270 series resources b Direct Zip download link 3 Open the MGate Manager Application Press the Search Button to start looking for devices...

Страница 18: ... press Configuration a Note if this step requires a password it is moxa 6 Navigate to the Network tab the second tab Figure 15 Network tab 7 In the Network tab you will be able to set the IP Change the IP from 192 168 0 1 to the IP that corresponds with your Gateway index 1 7 from the chart above Figure 13 Broadcast Search Figure 14 Gateway Configuration ...

Страница 19: ...change the last digit to match 192 168 0 2 etc 9 Repeat this process for the remaining gateways in the system The gateways contain powerful built in troubleshooting features If system troubleshooting is required please reach out to Bacharach Product Support for relevant documentation and support Figure 16 Network Setting OK screen ...

Страница 20: ...VR SC s touch screen is readily accessible for viewing alerts and responding to alarm conditions 1 Connect the controller to a 24V DC rated power supply Near to the 24V DC is a terminal block for direct Modbus RTU connections This is to be used for troubleshooting or very small direct connected networks less than 15 units A typical large floorplan should be divided into segments connecting via Gat...

Страница 21: ...ormally closed 3 6 Connecting Ethernet Gateways Connect the Ethernet output from the controller to the gateway s Note If multiple gateways are in use their Ethernet ports may be daisy chained or an optional Ethernet switch can be used to connect all gateways and the controller onto the same local subnetwork Connect the Modbus cable to the gateway output as depicted below Figure 18 Wiring Relays Fi...

Страница 22: ...ugh 16 and the unique IP address of the Gateway to which they are connected Additional resources for the MVR 300 VRF Refrigerant Leak Detector are available online To download these resources visit http bit ly 2wr9eMn Special Notes The gateway provides the link between the MVR SC and up to 15 MVR 300 devices Cable recommended Belden 3106 1 5 twisted pair shielded or similar Daisy chain only minimi...

Страница 23: ...n editable fields for Modbus ID and Gateway IP address The floor and room fields are to be completed prior to installation in order to ensure correct wiring and function Up to 100 MVR 300 devices can be connected to the MVR SC These are to be grouped as Modbus RTU daisy chain segments of up to 15 devices terminating at a Gateway Up to seven gateways can be used in a fully populated network Gateway...

Страница 24: ...same floor those devices must have the same floor name capitalization matters The MVR SC will display a new floor tile for each unique name appearing in the floorplan spreadsheet up to 16 district values The floor and room cells can be named with any combination of up to eight digits of letters and or numbers It is possible to hardwire up to 15 devices to the controller s Modbus RTU port To indica...

Страница 25: ... spreadsheet as a csv format and upload it onto the USB stick at the device root folder The filename must be named as data csv or the MVR SC will not be able to find the file when importing 7 Upload the spreadsheet into the controller from the USB stick using the steps outlined in Section Error Reference source not found Error Reference source not found Special Notes There can be multiple gateways...

Страница 26: ...e MGate Manager Application Press the Search Button to start looking for devices 11 Choose Broadcast Search to search on the entire connected 12 When discovered the Gateway should show up in the table Select its row and press Configuration a Note if this step requires a password it is moxa 13 Navigate to the Network tab the second tab Figure 15 Network tab 14 In the Network tab you will be able to...

Страница 27: ...process for the remaining gateways in the system The gateways contain powerful built in troubleshooting features If system troubleshooting is required please reach out to Bacharach Product Support for relevant documentation and support ...

Страница 28: ...00 to its install location 2 Set Modbus ID Manually Use the RS485 port on the controller to manually set the Modbus IDs and then install according to the floorplan while keeping track of assigned Modbus IDs 4 5 Method 1 Modbus ID Auto assign 1 MVR 300 devices can be auto assigned their Modbus ID using 2 person verification technique This process gives that added advantage of physically verifying t...

Страница 29: ...0 2294 Rev 1 29 3 On the MVR SC touch screen tap the pin icon in the bottom right of the screen to advance to the Floors screen and then tap the floor that is to be commissioned Figure 23 Floor List screen ...

Страница 30: ...en have a co worker tap the top single dot with the magnetic wand on the MVR 300 for less than a second Device should make an audible sound signaling that it is in Commissioning Mode Optionally the MVR 300 may be taken out of this mode by briefly tapping Magnetic Switch B Figure 24 Tap the tile of room to commission Figure 25 The MVR 300 ...

Страница 31: ... has successfully commissioned a Success message should appear If the commission was unsuccessful an Unable to Contact Device message should appear 6 Once the commission is successful tap the Back button to go back to the devices screen Figure 26 Device Modbus Pairing Figure 27 Once commission is successful tap Back ...

Страница 32: ...that the commission was successful 7 Repeat these steps for each room on a floor and each floor in the building until all MVR 300 devices have been commissioned When all devices have been commissioned the green System Normal splash will display on the Home Screen Figure 28 Green checkmark appears Figure 29 System Normal screen ...

Страница 33: ...ller for ease 1 From Settings open the Set Modbus ID screen to select and apply a specific Modbus ID 2 Tap Search to connect to the device If the unit does not have factory Modbus ID 1 this can be restored by doing a factory reset In case the MVR 300 has had its Modbus ID changed by the user to some ID other than the default address 1 do the following to reset to factory settings a Power OFF the M...

Страница 34: ...move the magnet wand and cycle power The MVR 300 will have reverted to default settings and Modbus ID 1 e Specify a unique ID for the MVR 300 which can be numbers 2 through16 f Tap Set Unit ID to apply this ID g Repeat the above steps for each device Keep track of the assigned IDs and install according to the floorplan spreadsheet Figure 31 Set Unit ID ...

Страница 35: ...arm condition To respond to an alarm event 1 Tap Mute to silence the alarm This will mute the buzzer at the controller for 30 minutes 2 Tap Details to open the Devices in Alarm screen to view the device s impacted The Devices in Alarm screen will list the Floor Room location designate the highest severity status from all devices on that floor and network details for each affected MVR 300 Refer to ...

Страница 36: ...spond to a Fault event 1 Tap Mute to silence the alert This will mute the buzzer at the controller for 30 minutes 2 Tap Details to open the Devices in Fault screen to view the device s impacted The Devices in Fault screen will list the Floor Room location status and network details for each affected MVR 300 Figure 34 Fault Detected screen Figure 35 Devices in Fault screen ...

Страница 37: ...will be indicated with an alert To respond to a Comm Error event 1 Tap Details to open the Comm Error screen to view the device s impacted The Comm Error screen will list the Floor Room location status and network details for each affected MVR 300 Figure 36 System Status screen Figure 37 Comm Error screen ...

Страница 38: ...ed as neither alarm nor fault are created when a device status clears to normal Note The Fault Code is stored as a decimal value and should be converted back to a hex or binary value for easier interpretation of the specific fault codes The Time and Date can be set using the UniApps utility 1 Press and hold the B icon in the upper right corner for 3 seconds Figure 38 Event History screen Figure 39...

Страница 39: ... Date Choose the date from the calendar tool on the left side of the screen and the time from the right side of the screen 4 To return to the home page press and hold the upper right corner again for 3 seconds From the dropdown menu choose UserApp Figure 40 Tap UniApps Figure 41 Choosing the time and date ...

Страница 40: ...n order to facilitate maintenance on the network or MVR 300 devices To access the Service Mode Screen 1 Open the Settings screen gear icon in upper right and tap the Service Mode button 2 Tap Apply to begin a 30 minute countdown A timer appears once activated and tapping Apply again will restart the countdown Figure 42 Service Mode screen ...

Страница 41: ...s Prior to shipping equipment to Bacharach visit www mybacharach com for a Returned Merchandise Authorization Number RMA All returned goods must be accompanied by an RMA Pack the equipment securely in its original packing if possible as Bacharach cannot be held responsible for any damage incurred during shipping to our facility Location Contact Information Shipping Address United States Phone 1 72...

Отзывы: