
IAM-100 and Controller Manual
8
6209-9000 Rev 2
1.3. Specifications
Specification
IAM-100
IAM Controller
Operating Power
Supply
120 VAC/60 Hz or
220 VAC/50 Hz; 11 W Max
120 VAC/60 Hz or
220 VAC/50 Hz; 11 W Max
Power Status
Green LED
Green LED
Alarm Status
Red LED
Red LED
Fault Status
Buzzer inactive, Green LED
off, and Red LED on
Horn inactive, Green LED
off, and Red LED on
Audible Alarms
Internal buzzer with mute
button
External horn with mute
button
Buzzer/Horn
Deactivate
By onboard jumper
By key switch
Alarm Relays
(Volt Free)
2 Relays: 3 A @ 24 VDC
3 A @ 120 VAC
2 Relays: 10 A @
230/120 VAC
Alarm Reset
Selectable manual or
automatic
Remote reset, downstream
resets any IAM-100 monitor
or controller connected to a
channel, after gas has
cleared
Selectable Alarm Delay
0, 5, 10 or 15 minutes
N/A
Warm-up Delay
5 minutes initially
N/A
Enclosure Rating
Standard: IP30
IP51
Dimensions & Weight
See housings table on
page 9
262 x 265 x 84 mm; 2.6 kg
[10.3 x 10.4 x 3.3 in; 5.7 lb]
Cable
Recommendations
IAM to IAM-C:
16-24 AWG, 2-conductor
(7/0.2 mm, 2 conductor)
984.25 ft (300 m) max
IAM-C to IAM-C:
7/0.2 mm, 2 conductor
[16-24 AWG, 2-conductor]
300 m [984 ft] max
Approvals
CE
UL/CSA 61010-1
CE
FCC Part 15, Subpart B
UL/CSA 61010-1
Содержание IAM-100
Страница 6: ...IAM 100 and Controller Manual 6 6209 9000 Rev 2 Figure 1 IAM 100 Figure 2 Optional IAM 100 Controller ...
Страница 7: ...IAM 100 and Controller Manual 6209 9000 Rev 2 7 Figure 3 Sample Architecture Diagram ...
Страница 13: ...IAM 100 and Controller Manual 6209 9000 Rev 2 13 Figure 5 Typical Dimensions of the IAM 100 Back ...
Страница 14: ...IAM 100 and Controller Manual 14 6209 9000 Rev 2 Figure 6 Controller Housing ...
Страница 34: ...IAM 100 and Controller Manual 34 6209 9000 Rev 2 ...
Страница 35: ...IAM 100 and Controller Manual 6209 9000 Rev 2 35 ...