background image

10

 

Instruction 3015-4149 

SECTION 5 

Multiple HGM’S 

 

MULTIPLE HGM300’S WITH RDM800 

NOTE 1:

  The last HGM300 or RDM800 on either end of the network must have its 

terminator in the “IN” position, and all other units must have their terminators in the 
“OUT” position.  

NOTE 2:

 The total length of the RS-485 cable cannot exceed 4500 feet. (Use 

instrument cable 20 gage multi-strand shielded and twisted pair – similar or equal to 
Belden cable #8762.) 

RS-485 CONNECTIONS BETWEEN HGM300’s  

NOTE:

 The terminators in the RDM800 and HGM300 Unit 4 must be in the “IN” 

position. The terminators in HGM300 Units 1, 2 & 3 must be in the “OUT” position.  

 
 
 
 
 
 
TERMINATOR   

  TERMINATOR  

 TERMINATOR 

  TERMINATOR 

     “OUT” 

 

        “OUT”  

 

 

      “OUT” 

 

 

        “IN” 

 
 
 
 
 

Connecting To A Building Management System 

The HGM300 may be connected to a Building Management System via the RS-485 connector. The node 
address switch on each HGM300 can be set from “1” to “15” in order to identify itself to the Building 
Management System. Note that Building Management Systems set to a “0” or “1” address both respond 
to messages from the RDM800 as address “1” therefore you should not have a unit set to “0” and another 
set to “1” on the same network.  

If the HGM300 network is connected directly to a Building Management System it 

may not

 be connected 

to the RDM800. However, the RDM800 has two communication ports, an “upstream” port (labeled TO 
HOST) and a “downstream port (labeled TO MONITORS). A BMS node may be connected to the up 
stream RDM800 port while the downstream RDM800 port talks to the HGM300’s. In this case, the BMS is 
talking “through” the RDM800 to the HGM300’s, but not physically on the HGM300/RDM800 network. 

NOTE:

  If the HGM300 is not at the end of the line in a series connection, then the terminator on the HGM 

must be set to “OUT.”  Also, each end of the series must have the terminator set to “IN”. 

 

 

 

 

 

   TERMINATOR 

 

 

 

 

 

          “OUT” 

       

 

         

 

 
 
 
 
 
       TERMINATOR 

          

TERMINATOR 

 TERMINATOR 

 TERMINATOR 

    

 “IN” 

 

    

  “OUT”  

 

      “OUT” 

 

         “IN” 

 
 

HGM300 
NODE 1 

HGM300 
NODE 2 

HGM300 
NODE 3 

HGM300 
NODE 4 

BMS 

TERMINATOR 

“IN” 

RMD800 

HGM300 
UNIT 2 
NODE 2 

HGM300 
UNIT 3 
NODE 3 

HGM300 
UNIT 4 
NODE 4 

HGM300 
UNIT 1 
NODE 1 

RS-485 

Содержание HGM300

Страница 1: ...c HGM300 RDM800 monitor system connections SECTION 5 Page 10 Multiple HGM connections SECTION 6 Page 12 Powering up the monitoring system SECTION 7 Page 13 Programming the HGM300 using the RDM800 SECT...

Страница 2: ...s that is number of zones AC input voltage and dual 4 20ma DC option if ordered RDM800 Remote Display Module if ordered Charcoal filter with T bolt bracket line end filter assembly Quantity dependant...

Страница 3: ...ne the best locations The smoke test would provide the pattern of air currents present in the mechanical room The RDM800 should be mounted outside of the mechanical room or at least just inside of a d...

Страница 4: ...tor Terminator Switch 4 20 mAdc Interface Board Optional Factory Default Switch Relay Connector Leak Spill Evac Fault Ground Stud AC IN Connector T1 Location of AC Input Line Filter 230 VAC Units Only...

Страница 5: ...Instruction 3015 4149 5 RDM800 Components Terminator Switches RS 485 to HGM300 Monitors RS 485 to Building Management System Relay Connector AC IN Connector T3...

Страница 6: ...Both loops must be wired if this option is installed If only one loop is used the unused loop must have a jumper wire installed Connect 120 230 VAC power to the RDM800 by removing the four screws hol...

Страница 7: ...RELAYS 5 AMP 240 VDC B A GND RS 485 OPTIONAL DUAL LOOP 4 20 mADC COMMON COMMON LOOP 1 ZONE LOOP 2 PPM SPECIAL NOTE TO ESTABLISH THE RS 485 COMMUNICATION LINK WITH THE RDM800 OR WITH A BUILDING MANAGEM...

Страница 8: ...R DEFINABLE RS 485 TO HOST SPECIAL NOTE TO ESTABLISH THE RS 485 COMMUNICATION LINK WITH THE RDM800 OR WITH A BUILDING MANAGEMENT SYSTEM USE 18 GAGE AWG MULTI STRANDED SHIELDED AND TWISTED PAIR INSTRUM...

Страница 9: ...the Common on the relay block Connect one end of strobe or horn to the NO of whichever level of alarm is appropriate for application The other end of strobe or horn is connected to the Line of the au...

Страница 10: ...ement System Note that Building Management Systems set to a 0 or 1 address both respond to messages from the RDM800 as address 1 therefore you should not have a unit set to 0 and another set to 1 on t...

Страница 11: ...ted to a Building Management System Daisy Chain Fashion RS 485 TERMINATOR IN TERMINATOR TERMINATOR TERMINATOR TERMINATOR OUT OUT OUT IN HGM300 UNIT 1 NODE 1 HGM300 UNIT 2 NODE 2 HGM300 UNIT 3 NODE 3 H...

Страница 12: ...essed Contact the factory if they do not chirp DO NOT plug the gas sample inlets of any unused zones During start up the software will pull a vacuum test to verify the number of zones and a plugged zo...

Страница 13: ...sure STP which is 1 atmosphere and 25 degrees C This function is rarely if ever used The PPM readings displayed are inversely related i e as temperature goes up PPMs decrease to the temperature of the...

Страница 14: ...splayed for this zone This key is used to clear the peak PPM for this zone which is displayed at the top of this screen The peak PPM gives the PPM level time and date of the highest refrigerant readin...

Страница 15: ...rface cable to PC and RS 232 port on the HGM300 3 Insert software disk into PC 4 Open the HGM300 software using Windows Explorer 5 Upon start up the program will immediately attempt to download data f...

Страница 16: ...a Saved Program to an HGM300 Open the HGM300 PC software open the proper saved program connect the PC to the HGM300 go to HGM SEND SETUP and then press ENTER The saved program will be sent to the HGM...

Страница 17: ...m If there are more then eight alarms additional screens can be displayed by pressing the MORE button Each active alarm is indicated by a blinking box As an alarm is acknowledged the box stops blinkin...

Страница 18: ...ned to the Alarm Summary Screen and the box associated with that alarm will no longer be blinking indicating that the alarm has been acknowledged Repeat this procedure for each active alarm When all a...

Страница 19: ...utes the trend is recorded every time the zone is sampled From the top level Zone Screen press the button adjacent to the zone that you wish to work with to go to that zone s Zone Setup Screen 1 and t...

Страница 20: ...FAULT The detector voltage may be out of tolerance Check the Diagnostic Screen for the DET voltage AVE voltage and ZERO voltage Call the factory with this information for further instructions REZERO...

Страница 21: ...onnector Check for an illegal parameter If necessary reset to the factory default settings Viewing the Fault Log From the Fault Screen press the button under LOG This screen lists the last 20 fault co...

Страница 22: ...me range as line 1 LINE 4 Noise This is a 16 point running average of the noise portion of IR bench output This reading is valuable mainly when refrigerant is NOT present LINE 5 Average Absorbency Thi...

Страница 23: ...temperature along with the raw voltage from the temperature sensor and has the same range as line 9 LINE 11 Pressure This is the current absolute manifold pressure in PSIA along with the output voltag...

Страница 24: ...Hunt Valley Circle New Kensington PA 15068 WARRANTY HIGHLIGHTS PLEASE REVIEW COMPLETE WARRANTY CONDITIONS PARTS 2 YEARS AFTER SHIPMENT FROM FACTORY UNLESS OTHERWISE NEGOTIATED LABOR 90 DAYS AFTER SHI...

Отзывы: