Differential Filtration Controller

Setting the Interval Time between backwash cycles

This parameter is the maximal time between two consecutive backwash cycles if no backwash cycle is triggered by the 

differential pressure switch (DIF). 
The programable range is up to 23 hours and 59 minutes, identified by “

A

”. if “

A

” is selected, the Interval Time parameter 

is ignored.
The factory-set parameters cannot be changed by the user and they include the following:

1.  Long press the 

MODE

 button followed by a short press on the 

MODE

 button: the following screen appears:

 

 

G75-DFC 

22/04/21 

                    Page 13 of 15 

 

 

 

 

 

 

Setting the Interval Time between backwash cycles: 

This parameter is the maximal time between two consecutive backwash cycles if no backwash cycle is triggered by the 
differential pressure switch (DIF).  

The  programable range is up to 23  hours  and  59  minutes, identified by “

A”

.  if  “

A”

  is selected,  the  Interval  Time 

parameter is ignored. 

1.

 

Long press the 

MODE

 button followed by a short press on the 

MODE

 button: the following screen appears: 

 

 

 

 

 

 

 

2.

 

Using the        and the        keys, adjust the minutes. If 

“A”

 is selected, press SET to complete the setting. 

3.

 

Press 

SET

 to continue. 

4.

 

Using the        and the        keys, adjust the hours.    

5.

 

Press 

SET

 to complete the setting. 

Setting the number of filters: 

The parameter designates the operating filters in the system (up to three filters); the default value is #1. 

Note:

 if needed (for technical reasons) the user may set the designated number not in a consecutive order. 

1.

 

Long press the 

MODE

  button  followed by two  short presses  on the 

MODE

  button:  the following screen 

appears: 

 

 

 

 

 

2.

 

 Using the      key to select valve #1, valve #1 remans ON and valve #2 starts blinking. Use the       key to 
deselect a valve. 

3.

 

Repeat the above process for filters number 2 and 3. 

2.  Using the   and the   keys, adjust the minutes. If “A” is selected, press SET to complete the setting.
3.  Press 

SET

 to continue.

4.  Using the   and the   keys, adjust the hours.   
5.  Press 

SET

 to complete the setting.

Setting the number of filters:

The parameter designates the operating filters in the system (up to three filters); the default value is #1.

Note: 

if needed (for technical reasons) the user may set the designated number not in a consecutive order.

1.  Long press the 

MODE

 button followed by two short presses on the 

MODE

 button: the following screen appears:

 

 

G75-DFC 

22/04/21 

                    Page 13 of 15 

 

 

 

 

 

 

Setting the Interval Time between backwash cycles: 

This parameter is the maximal time between two consecutive backwash cycles if no backwash cycle is triggered by the 
differential pressure switch (DIF).  

The  programable range is up to 23  hours  and  59  minutes, identified by “

A”

.  if  “

A”

  is selected,  the  Interval  Time 

parameter is ignored. 

1.

 

Long press the 

MODE

 button followed by a short press on the 

MODE

 button: the following screen appears: 

 

 

 

 

 

 

 

2.

 

Using the        and the        keys, adjust the minutes. If 

“A”

 is selected, press SET to complete the setting. 

3.

 

Press 

SET

 to continue. 

4.

 

Using the        and the        keys, adjust the hours.    

5.

 

Press 

SET

 to complete the setting. 

Setting the number of filters: 

The parameter designates the operating filters in the system (up to three filters); the default value is #1. 

Note:

 if needed (for technical reasons) the user may set the designated number not in a consecutive order. 

1.

 

Long press the 

MODE

  button  followed by two  short presses  on the 

MODE

  button:  the following screen 

appears: 

 

 

 

 

 

2.

 

 Using the      key to select valve #1, valve #1 remans ON and valve #2 starts blinking. Use the       key to 
deselect a valve. 

3.

 

Repeat the above process for filters number 2 and 3. 

2.  Using the   key to select valve #1, valve #1 remans ON and valve #2 starts blinking. Use the   key to deselect a 

valve.

3.  Repeat the above process for filters number 2 and 3.

Содержание G75-DFC

Страница 1: ...G75 DFC A U T O M A T I O N C O N T R O L Tackling climate change together Differential Filtration Controller Installation Operation Maintenance IOM...

Страница 2: ...part any part of this document or its content The confidential nature of and or privilege in the file enclosed is not waived or lost as a result of a mistake or error in this file If you received this...

Страница 3: ...Waterproof Small Wire Connector LV9000 8 DryConn 22 to 12 AWG Wire Connectors 8 Provided by DryConn 8 BATTERY INSTALLATION 9 Before installing the battery 9 Replacing the battery 9 The User Interface...

Страница 4: ...replacing a Low Battery icon appears on screen Technical Data Controller Set Supplied with DFC controller suitable for DC only and one analog sensor Mechanical Operating temperature 10 C to 60 C Outdo...

Страница 5: ...vant standards and regulations Electrical wiring should be performed by an authorized electrician only using standardized and approved components and tools Locate the G75 DFC Filtration Controller whe...

Страница 6: ...ontroller The G 75 DFC Main Components Electric cable Pipe fitting Mounting screws x 2 Pipe fitting Controller D Upper digits UD Lower digits LD DP Pipe fitting Mounting screws x 2 Controller DFC disp...

Страница 7: ...e Connects to the black wire of solenoid number 3 filter valve 3 Black wire of the Differential Pressure switch DP Switch Installation Connect the controller s molded cable with the 3 wire connector t...

Страница 8: ...ed connection Do not reuse DryConn 22 to 12 AWG Wire Connectors Provide by DryConn 1 Strip 22 18 wires 1 2 12 7mm And 16 12 wires 3 8 9 5mm 2 Align any frayed strands or conductors 3 Pre twisting unne...

Страница 9: ...k the cover and secure the four screws The LCD display shows The actual differential pressure DIF The pressure set point SET The flushing cycles counter FC While in flushing a Faucet icon appeases on...

Страница 10: ...the controller is paused such as off season or when controlling the filters is not required In the OFF mode the lower line of the controller LD displays OFF In this mode the controller stops reading t...

Страница 11: ...samples shortens The maximal interval time between readings is 60 seconds while the minimal interval time between readings is 5 seconds The delay between filters during flushing Off time between valve...

Страница 12: ...the above process for filters number 2 and 3 2 Using the and the keys adjust the minutes If A is selected press SET to complete the setting 3 Press SET to continue 4 Using the and the keys adjust the...

Страница 13: ...y 1 Incorrect DP settings Low 1 Check if the DP is set too low 1 Set the DP to 0 5 bar 2 Sensor not zeroed 2 Disconnect the upstream and downstream tubes and check that the pressure indicated in the o...

Страница 14: ...yer shall deliver the product to one of Baccara s facilities and collect it from the same facility once repair is completed G75 DFC 22 04 21 Page 15 of 15 Warranty Baccara Geva ACS Ltd Baccara product...

Страница 15: ...15 G75 DFC Differential Filtration Controller IOM IOM...

Страница 16: ...3 9553 4963 F 61 0 3 9553 4965 Cheltenham Victoria 3192 Australia australia baccara geva com www baccarageva com au Store www baccarastore com au BACCARA Espa a C Marqu s de Monteagudo N 24 Madrid T 3...

Отзывы: