Nexus
®
Modular Hybrid Cooler iPilot
®
Control System Quick Start Guide
–
Instructions
Page | 7
7.
Press
Esc
to return to the Main Menu. From the Main Menu, scroll up (
↑
) or down
(
↓
)
and select
“
A. User Menu
”
, then press enter
(
←
). Press down (
↓
) to go to
“
Oper Conditions E02
”
. Press enter (
←
) to begin making changes. Use the up (
↑
)/down
(
↓
)
arrows to
set the following values, then press enter (
←
) to accept changes.
-
Set Operating Mode to Nexus
o
If customer analog control signal will be used, reference step 1.b of Optional Wiring Feature for Unit Communication
-
Set Run Authorization to ON
-
Set Leaving Process Fluid Setpoint at the value stated in the equipment Submittal
Set Water/Energy Saving between 1-7 (5 recommended)