Nexus

®

 Modular Hybrid Cooler iPilot

®

 Control System Quick Start Guide 

 Instructions 

 

 

Page | 6 

 

 

iPilot® Control System Quick Start with Recommended Settings 
 

1.

 

Verify that the supply power is connected to the iPilot® control system. 

2.

 

Turn on all circuit breakers inside the iPilot® control system. 

3.

 

Close the iPilot

®

 control system panel and ensure that all the locks have been fully engaged and secured by rotating them 90° with a 

flathead screwdriver or coin. 

4.

 

Turn on the main power supply to the unit and ensure that main disconnect switch on the iPilot® control system is turned ON. 

5.

 

On the iPilot

®

 control system

 

keypad press 

Prg

. Press enter (

) 4 times to enter the default user password 

of “0000”.

 

 

 

6.

 

From the Main Menu scroll up (

) or down 

(

and highlight 

D. Clock Menu

, then press enter (

). While in the Clock Menu, press 

enter (

) to begin making changes. Use the up (

)/down 

(

)

 

arrows to set the date, time, and time zone, then press enter (

) to 

accept changes.

 

 

 

 

                    

 

 

 
 
 
 
 
 

Содержание Nexus

Страница 1: ...Nexus Modular Hybrid Cooler iPilot Control System Quick Start Guide...

Страница 2: ...ed additional information about this unit contact your local BAC Representative whose name and telephone number are on a label adhered to the control panel door The model number and serial number of t...

Страница 3: ...service maintenance or inspection on or near the fan s motor s or inside the unit without first ensuring that the fans and pump motors are disconnected from the power source locked out and tagged out...

Страница 4: ...tart Guide Instructions Page 4 2 Verify the equipment voltage noted on the equipment nameplate is equivalent to the site voltage The equipment nameplate can be found on the front control panel door an...

Страница 5: ...system interface or remotely with a signal by others b Analog Control Signal Terminals V 10V mA It is recommended to have the iPilot control system automatically modulate the fan speed for optimal en...

Страница 6: ...been fully engaged and secured by rotating them 90 with a flathead screwdriver or coin 4 Turn on the main power supply to the unit and ensure that main disconnect switch on the iPilot control system...

Страница 7: ...ons E02 Press enter to begin making changes Use the up down arrows to set the following values then press enter to accept changes Set Operating Mode to Nexus o If customer analog control signal will b...

Страница 8: ...e to go to BMS Communication E05 Press enter to begin making changes Use the up down arrows to set the following values then press enter to accept changes Choose Comm Type None BACnet IP BACnet MSTP M...

Страница 9: ...gin making changes Use the up down arrows to set the following values then press enter to accept changes Set Cond Bleed Enbl to ON Set Wtr Cond StPt to 3300 microohms cm Set WtrCondPtDiff to 600 0 mic...

Страница 10: ...Nexus Modular Hybrid Cooler iPilot Control System Quick Start Guide baltimoreaircoil com 2022 Baltimore Aircoil Company 7600 Dorsey Run Road Jessup MD 20794 410 799 6200 RGOMNXF 03_R1 0...