In the terminal box of the controller, you can find a black knob. Pressing this knob or button results in activating a
menu, a selected line or confirming your choise. Rotating the button allow to change values (dial) or navigate
through the menu. The active line has a ">" mark in front of it.
Press the black button to continue. Following screen appears:
For standard TSU-M models the range setting is 117m. For TSU-ML models (low height) the standard setting is
92mm. Dial the correct setting for the model at hand (check the unit name plate) by rotating the black knob.
Confirm your selection by pressing the black know. The next screen appears:
Rotate the black button to dial 7 and press to confirm. The display indicates 'Range successfully changed'. In
case the button is pressed without dialing 7 you return to the previous menu and values are not stored.
After the range is entered, the following screen appears for a few seconds, followed by the next screen:
Now follow the procedure to set the zero level. When pressing the black button you enter the screen below. Rotate
the black button to select 'Set Zero Level' and press to activate. Make sure you only do this when no ice is present
in the ice tank and when the water level is at the zero level of the sight glass. (For concrete tank applications make
sure the water level is just above the coil header.)