BA SYSTEMS BAS 918S - качественный и надежный прибор для вашего бизнеса. На нашем сайте вы можете скачать бесплатное руководство по эксплуатации для этого устройства. Узнайте все особенности и возможности продукта, скачав его с manualshive.com.
BA Systems—Petershvilevej 1—DK-3200 Helsinge—http://www.basystems.dk
BAS 918S/929S
Manual
BAS 91
8S/929S
Страница 1: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk BAS 918S 929S Manual Manual BAS 918S 929S...
Страница 2: ...nfiguration 17 Scheme list 18 Scheme introduction 19 Scheme 1 Central heating 20 Scheme 2 Central heating and Hot water tank 26 Scheme 3 Central heating with Heat Exchanger 35 Scheme 4 Central heating...
Страница 3: ...ace Technical data Power supply 24VAC DC or 240VAC Power 6W Digital outputs Solid state relay BAS918S 6 channals BAS929S 11 channels Max 1A ved 240VAC DC must be protected against inductive loads Ther...
Страница 4: ...basystems dk 4 BAS 918S 929S Manual Materials included 1 Produkt socket 2 Produkt front 3 4 pcs of 3 9mm x 32 mm screws for wall mount 4 Cable relief bracket for cable retention at socket 5 2 pcs of 3...
Страница 5: ...connector end of the front See illustration below Cut out area when cables inserted from behind Cut out area when cables inserted from this end Use a sharp knife to cut the plastic along or within th...
Страница 6: ...9S Manual Installation Generic socket connections are defined in placement and function in the following draw ings and descriptions This indicates the maximum I O configuration for the BAS9XXS control...
Страница 7: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 7 BAS 918S 929S Manual Controller profile...
Страница 8: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 8 BAS 918S 929S Manual Controller front Dimensions for wall mount are indicated from above drawing...
Страница 9: ...Up to 24V drive 24VAC DC power supply for extend ed drive capability Max 20W pr channal STPA Secondary Stepper motor connection As above 2 terminals combined with AO cur rent output capability Not co...
Страница 10: ...ordered The intension with this is to assemble Nul and Phase connections internally distributing connections from here Only one supply line into the controller is then required Alternative use will al...
Страница 11: ...nt configuration capabilities for each individual channel More information is seen on page 9 All channels are galvanic interconnected as well as connected to the internal controlling circuit An advant...
Страница 12: ...1000 2 x 0 4mA 20mA 2 x 0 2V 10V minimum 12 wires will be required If one cable is used for analog signals mixed with supply wires for pumps valves or motors it may be necessary to use twisted pair ca...
Страница 13: ...AO X _I See page 15 The signal reference for 3 and 4 for voltage as well as current loop terminals are located on AO3 and AO4 For inspiration see the following example Example Motor Valve connection S...
Страница 14: ...below Only authorized personel may do module mounting So when requesting this option the controller must be ordered with this included from the supplier Connection For cabled bus interfaces below mod...
Страница 15: ...ach controlling scheme The controller is always using BACnet port BAC0 47808 and is given the name BAS9XXS Device The controller ID can be configured by the menu system operated through the scroll but...
Страница 16: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 16 BAS 918S 929S Manual BAS 918S configuration...
Страница 17: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 17 BAS 918S 929S Manual BAS 929S configuration...
Страница 18: ...sections will define a process diagram cabling according to this and a description of Modbus parameters availa ble The list below defines available schemes 1 Central heating 2 Central heating and Hot...
Страница 19: ...ed Only one outdoor sensor is required for an installation Scaling For metering applications a conversion factor must be defined This is called scaling So when a controlling scheme is selected a scali...
Страница 20: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 20 BAS 918S 929S Manual Scheme 1 process diagram Central heating CH BAS918S or BAS929S AI3 AI1 AI2 DI1 DO1 AO1...
Страница 21: ...he components Circulation pump and Motor valve is to be supplied by 240VAC 240VAC installation DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A D...
Страница 22: ...sumes that Circulation pump and Motor valve is selected to support the same supply as the controller 24VAC or 24VDC installation DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 24...
Страница 23: ...perature also called climate compensation defined as follows Outdoor temperature Forward temperature Values in C At daytime the circulation pump is stopped when the temperature exceeds 20 C The pump i...
Страница 24: ...rward temp at 0 C outdoor temp 9 x Forward temp at 5 C outdoor temp 10 x Forward temp at 10 C outdoor temp 11 x Forward temp at 15 C outdoor temp 12 x Forward temp at 20 C outdoor temp 13 x Night comp...
Страница 25: ...p CV1_Tp10 Forward temp at 15 C outdoor temp CV1_Tp15 Forward temp at 20 C outdoor temp CV1_Tp20 Night compensation CV1_NATSNK Night compensation until this temperature CV1_NAT_MAX No night compensati...
Страница 26: ...Helsinge http www basystems dk 26 BAS 918S 929S Manual Scheme 2 process diagram BAS918S or BAS929S Centralvarme blandesl jfe med varmtvandsbeholder AI1 AI2 AI3 AI5 AI7 AI6 DI1 DO2 DO1 AO2 AO1 Central...
Страница 27: ...plied by 240VAC DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B DO11A DI2 DI1 AI5 AI5 AI1 AI1 AI2...
Страница 28: ...cted to support the same supply as the controller DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B...
Страница 29: ...perature also called climate compensation defined as follows Outdoor temperature Forward temperature Values in C At daytime the circulation pump is stopped when the temperature exceeds 20 C The pump i...
Страница 30: ...om 0 100 Hot Water Tank temperature regulation values are given by a Day setpoint and as a Night setpoint Each controlled by a timer By default the day value is 55 C and night value 45 C Default timer...
Страница 31: ...d temp at 0 C outdoor temp 9 x Forward temp at 5 C outdoor temp 10 x Forward temp at 10 C outdoor temp 11 x Forward temp at 15 C outdoor temp 12 x Forward temp at 20 C outdoor temp 13 x Night compensa...
Страница 32: ...signed integer 16 bit signed integer Hot Water Tank control Daytime setpoint 21 x Nighttime setpoint 22 x Return limiter maximum temperature 23 x Legionalla process 0 Off 1 Sunday 2 Monday 7 Saturday...
Страница 33: ...V1_Tp10 Forward temp at 15 C outdoor temp CV1_Tp15 Forward temp at 20 C outdoor temp CV1_Tp20 Night compensation CV1_NATSNK Night compensation until this temperature CV1_NAT_MAX No night compensation...
Страница 34: ...Return limiter maximum temperature VB1_Retmax Legionalla process 0 Off 1 Sunday 2 Monday 7 Saturday 8 All days VB1_Legio Return limiter forced set point VB1_Set_beg Pump state 0 Off 1 On _VB1_CP401 S...
Страница 35: ...BA Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 35 BAS 918S 929S Manual Scheme 3 process diagram Central heating with Heat Exchanger BAS918S or BAS929S AI1 AI2 AI3 AI4 DI1 AO1 DO1...
Страница 36: ...components Circulation pump and Motor valve is to be supplied by 240VAC DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B D...
Страница 37: ...ng assumes that Circulation pump and Motor valve is selected to support the same supply as the controller DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N...
Страница 38: ...perature also called climate compensation defined as follows Outdoor temperature Forward temperature Values in C At daytime the circulation pump is stopped when the temperature exceeds 20 C The pump i...
Страница 39: ...orward temp at 0 C outdoor temp 9 x Forward temp at 5 C outdoor temp 10 x Forward temp at 10 C outdoor temp 11 x Forward temp at 15 C outdoor temp 12 x Forward temp at 20 C outdoor temp 13 x Night com...
Страница 40: ...1_Tp10 Forward temp at 15 C outdoor temp CV1_Tp15 Forward temp at 20 C outdoor temp CV1_Tp20 Night compensation CV1_NATSNK Night compensation until this temperature CV1_NAT_MAX No night compensation b...
Страница 41: ...levej 1 DK 3200 Helsinge http www basystems dk 41 BAS 918S 929S Manual Scheme 4 process diagram Central heating with heat exchanger and hot water supply BAS918S or BAS929S AI3 AI4 AI1 AI5 AI2 AI7 AI6...
Страница 42: ...DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B DO11A DI2 DI1 AI5 AI5 AI1 AI1 AI2 AI2 AI3 AI3 AI4 AI4 AI10...
Страница 43: ...supply as the controller DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B DO11A DI2 DI1 AI5 AI5 AI...
Страница 44: ...perature also called climate compensation defined as follows Outdoor temperature Forward temperature Values in C At daytime the circulation pump is stopped when the temperature exceeds 20 C The pump i...
Страница 45: ...om 0 100 Hot Water Tank temperature regulation values are given by a Day setpoint and as a Night setpoint Each controlled by a timer By default the day value is 55 C and night value 45 C Default timer...
Страница 46: ...rd temp at 0 C outdoor temp 9 x Forward temp at 5 C outdoor temp 10 x Forward temp at 10 C outdoor temp 11 x Forward temp at 15 C outdoor temp 12 x Forward temp at 20 C outdoor temp 13 x Night compens...
Страница 47: ...signed integer 16 bit signed integer Hot Water Tank control Daytime setpoint 21 x Nighttime setpoint 22 x Return limiter maximum temperature 23 x Legionalla process 0 Off 1 Sunday 2 Monday 7 Saturday...
Страница 48: ...V1_Tp10 Forward temp at 15 C outdoor temp CV1_Tp15 Forward temp at 20 C outdoor temp CV1_Tp20 Night compensation CV1_NATSNK Night compensation until this temperature CV1_NAT_MAX No night compensation...
Страница 49: ...Return limiter maximum temperature VB1_Retmax Legionalla process 0 Off 1 Sunday 2 Monday 7 Saturday 8 All days VB1_Legio Return limiter forced set point VB1_Set_beg Pump state 0 Off 1 On _VB1_CP401 S...
Страница 50: ...Systems Petershvilevej 1 DK 3200 Helsinge http www basystems dk 50 BAS 918S 929S Manual Scheme 5 process diagram Dual Central heating BAS918S or BAS929S CH1 CH2 AI1 AI2 AI3 AI6 AI5 DI1 DO1 DO2 AO1 AO...
Страница 51: ...ve is to be supplied by 240VAC DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B DO11A DI2 DI1 AI5 A...
Страница 52: ...r valve is selected to support the same supply as the controller DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO1...
Страница 53: ...perature also called climate compensation defined as follows Outdoor temperature Forward temperature Values in C At daytime the circulation pump is stopped when the temperature exceeds 20 C The pump i...
Страница 54: ...rd temp at 0 C outdoor temp 9 x Forward temp at 5 C outdoor temp 10 x Forward temp at 10 C outdoor temp 11 x Forward temp at 15 C outdoor temp 12 x Forward temp at 20 C outdoor temp 13 x Night compens...
Страница 55: ...orward temp at 0 C outdoor temp 29 x Forward temp at 5 C outdoor temp 30 x Forward temp at 10 C outdoor temp 31 x Forward temp at 15 C outdoor temp 32 x Forward temp at 20 C outdoor temp 33 x Night co...
Страница 56: ...V1_Tp10 Forward temp at 15 C outdoor temp CV1_Tp15 Forward temp at 20 C outdoor temp CV1_Tp20 Night compensation CV1_NATSNK Night compensation until this temperature CV1_NAT_MAX No night compensation...
Страница 57: ...emp CV2_Tp10 Forward temp at 15 C outdoor temp CV2_Tp15 Forward temp at 20 C outdoor temp CV2_Tp20 Night compensation CV2_NATSNK Night compensation until this temperature CV2_NAT_MAX No night compensa...
Страница 58: ...shvilevej 1 DK 3200 Helsinge http www basystems dk 58 BAS 918S 929S Manual Scheme 6 process diagram Dual Central heating with Heat Exchanger BAS918S or BAS929S CH1 CH2 AI2 AI4 AI3 AI1 AI5 AI7 AI6 DI1...
Страница 59: ...DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B DO11A DI2 DI1 AI5 AI5 AI1 AI1 AI2 AI2 AI3 AI3 AI4 AI4 AI10 AI10 AI6 A...
Страница 60: ...the controller DO8B DO8A DO4B DO4A DO5B DO5A DO6B DO6A DO7B DO7A DO3B DO3A 240VAC N 240VAC L 24VAC L 24VAC N DO1B DO1A DO2B DO2A DI4 DI3 DO9B DO9A DO10B DO10A DO11B DO11A DI2 DI1 AI5 AI5 AI1 AI1 AI2 A...
Страница 61: ...perature also called climate compensation defined as follows Outdoor temperature Forward temperature Values in C At daytime the circulation pump is stopped when the temperature exceeds 20 C The pump i...
Страница 62: ...rd temp at 0 C outdoor temp 9 x Forward temp at 5 C outdoor temp 10 x Forward temp at 10 C outdoor temp 11 x Forward temp at 15 C outdoor temp 12 x Forward temp at 20 C outdoor temp 13 x Night compens...
Страница 63: ...x Forward temp at 0 C outdoor temp 29 x Forward temp at 5 C outdoor temp 30 x Forward temp at 10 C outdoor temp 31 x Forward temp at 15 C outdoor temp 32 x Forward temp at 20 C outdoor temp 33 x Nigh...
Страница 64: ...V1_Tp10 Forward temp at 15 C outdoor temp CV1_Tp15 Forward temp at 20 C outdoor temp CV1_Tp20 Night compensation CV1_NATSNK Night compensation until this temperature CV1_NAT_MAX No night compensation...
Страница 65: ...emp CV2_Tp10 Forward temp at 15 C outdoor temp CV2_Tp15 Forward temp at 20 C outdoor temp CV2_Tp20 Night compensation CV2_NATSNK Night compensation until this temperature CV2_NAT_MAX No night compensa...
Страница 66: ...t push enters the editing mode Now a value may be changed using the scroll wheel Two short pushes terminates editing mode One long push cancels editing To access the Service Menu a PIN code must be in...
Страница 67: ...the options When the re quested controlling scheme is displayed push the button and the selection is made Please note that the schemes shown below are just for illustration They may not represent the...
Страница 68: ...follows Now scroll to the parameter to be changed position shown with reverse marking Push one time and the variable to the right may be changed by scrolling between options Enter one short push and...
Страница 69: ...y IP addresses and configuration options for this Configurations must be made to support the actual network segment This way the controller web page and data may be accessed from the network either fr...
Страница 70: ...ort push enters the menu a long push leaves the menu A long push will always exit the submenu and eventually re turn to the active scheme diagram Submenu Actual is shown below as an example Central he...
Страница 71: ...until all digits has been set Finally 2 short pushes will store the complete value and editing is done As shown below a key sign might be shown on a line In that case a password must be en tered in t...
Страница 72: ...ion used must open port 75 and port 80 from the internet using NAT so port data may be routed to the controller Watch screen This menu allow settings of current time GMT offset Daylight saving time on...
Страница 73: ...web browser and a dedicated application must be installed The following operating systems are supported Windows Linux MAC OS Android The Android application is downloaded from the BA Systems WEB page...