BAS 918S/929S
Manual
Scheme 5, BACnet parameter list continued:
Description
Analog Value
Analog Input
Data format
Central heating circuit 2/control
Summer daytime Setpoint
CV2_Summerday
Vinter daytime Setpoint
CV2_Vinterday
Summer nighttime Setpoint
CV2_Summernight
Vinter nighttime Setpoint
CV2_Vinternight
Forward temp at
-
20°C outdoor temp.
CV2_Tm20
Forward temp at
-
15°C outdoor temp.
CV2_Tm15
Forward temp at
-
10°C outdoor temp.
CV2_Tm10
Forward temp at
-
5°C outdoor temp.
CV2_Tm05
Forward temp at 0°C outdoor temp.
CV2_Tp00
Forward temp at 5°C outdoor temp.
CV2_Tp05
Forward temp at 10°C outdoor temp.
CV2_Tp10
Forward temp at 15°C outdoor temp.
CV2_Tp15
Forward temp at 20°C outdoor temp.
CV2_Tp20
Night compensation
CV2_NATSNK
Night compensation until this temperature
CV2_NAT_MAX
No night compensation below this temperature
CV2_NAT_DIS
Forced displacement
CV2_VAMEMES
Forced displacement reset time (seconds)
CV2_VM_SET_T
Return temperature maximum
CV2_Retmax
Set state (0:Auto, 1:Stop, 2:Start)
CV2_OMS
Return limiter forced set point
CV2_Set_beg
Pump state (0:Off,1:On)
CV2_CP301
Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop)
CV2_STATE
Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop,
4:Day/off, 5:Night/off)
CV2_SV_stat
Central Heating circuit 2/Values measured
Out door sensor temperature
_CV2_TC901
Forward temperature
_CV2_TC301
Return temperature
_CV2_TC401
Not used (returns 0)
_EMPTY_
Motor valve position i percent
_CV2_MV401
Pump Stop/Start
CV2_CP301