9
HYDROCLIMA 2 - User Manual
Configuration
Technical data
* The battery life strongly depends on the working time window, set during the configuration process, and on the
environmental conditions. Estimation of the battery life is given by the configuration software.
Programming and configuration of the device is carried out by radio, using an RFM-RX2 and BMetering software.
To trigger the configuration procedure, the BMetering software must be properly configured:
→ For the factory state of the allocator, press the button for < 1s,
→ For the allocator already configured, press the button for > 5s, until the display shows the message “rF”.
The method of configuration has been described in the documentation concerning the B Metering software
user manual
Type
Hydroclima 2, electronic, two-sensor one
Available versions
Compact, with an external temperature probe
LCD
7 segment display with icons
Dimensions
102 mm x 40 mm x 27 mm (h x w x d)
Power supply
Lithium battery 3.6V
Maximum battery life
10 Years*
Application temperatures
From 35°C to 105°C
From 35°C to 130°C (version with a remote sensor, length of the sensor
3m)
Accuracy of the measurement
Temperature Sensors – thermistors 1%
Way of reading
Physical (display)
Radio (remote)
Communication with the device
Radio, two-ways directions
Configuration
Radio configuration, via Bmetering software and RFM-RX2
Power of the transmitter
10 dBm (10 Mw)
Frequency of the transmitter
868,950 Mhz
Frequency of the receiver
868,300 Mhz
Start accounting ( thermal energy consumption units)
Radiator’s temperature > 22.5°C
Δt ≥3k (difference between a temp. Of a radiator and the ambient
temp.)
Measurement method
Two-sensor or single sensor (depending of the conditions)