max

50

Lux

1500

Lux

ON

OFF

Sensor and power supply in one case

Power supply:

 230 V~ 

±

10%

Detection area:

 

 360°

Range max. [m]:

 

   Ø 

radius

Seated:

  

  2.50   1.25

Walking across:

 

10.00   5.00

Walking towards:

 

  6.00   3.00

Mounting height:

  

2 - 3 m 

Power consumption:

 

< 1W

Channel 1 (Control the lighting)

Switching power:

 

2300 W, cos

ϕ

= 1;

 

1150 W, cos

ϕ

= 0.5

Time settings:

 

impulse or 15 sec. - 30 min.;

Light sensor:

 

10 - 2000 Lux

Protection:

  

IP20 / Class II / 

Dimensions:

 

L 91.5 x W 60 x H 73 mm

  

Housing:

 

 UV-   and  shock-resistant 

Polycarbonate

Ambient temperature:

 

-25°C to +50°C

Technical data PD5-Slave-Clip

Electrical data same as above, but just one channel for 

signaling motion detection

 

Declaration of Conformity: 

The product complies with 

the low voltage recommendation 2006/95/EC and the EMV 

recommendation 2004/108/EC

13. Technical data

11. Wiring diagrams

Typ

Part nr.

PD5-M-1C-Clip (Master)

92315

PD5-S-Clip (Slave)

92316

LUXOMAT

®

 Remote control:

IR-PD (incl. wall bracket) 

92160

IR-PD-Mini 92159

Accessory:

Wall bracket for remote control as replacement 92100

14. Article / Part nr. / Accessory

M

A

N – 6

70

– 13

06

13

-2

9. Range of Coverage

7.  Switching between fully automatic and 

semi automatic mode when open

(for IR-PD functions see page 1)

Fully automatic operation

In this operating mode, the lighting switches automatically on 

and off for increased comfort, depending on presence and 

brightness (red LED lights up for 1.5 sec.).

Semiautomatic operation

(Semiautomatic can only be activated via the remote control!)

In this operating condition, in order to gain increased 

savings, the lighting is energized only after being manually 

switched on. Switch-off takes place automatically (red LED 

fl ashes quickly for 3 sec.).

The semiautomatic mode basically behaves like the fully 

automatic one. However, the difference is that switching-on 

must always be carried out manually!

As many (closer-contact) buttons as desired can be wired in 

parallel on the “S” button input.

12. LED-functional indicators, fault-finding

The functional indicators in the case of the

LUXOMAT

®

 PD5-M-1C-Clip (red and green LED‘s)

Red LED indicating self-checking mode (over a period of 60 

seconds following mains‘-supply lock-on)

Flashing at intervals of 1 second

 

EEPROM/memory empty

Flashing rapidly

EEPROM/memory contains information

Red LED as an indicator of status

Flashing irregularly

Movements are detected within the area of coverage

Flashing regularly

 Detector identifies bright, light off 

(dependent upon operating mode)

Not illuminated

 Detector identifies dark, light on (after switch-on delay) 

(dependent upon operating mode)

Flashing extremely rapidly

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for 

commands from the remote control

Illuminated for 2 seconds and switching the relay

Signal validly received

10. Colour-coding of pre-wired for PD5-Clip-M

Colour coding for pre-wired cable for

PD5-S-Clip

Cable

8.  Manual switching when closed

You can switch the lighting on and off manually by pressing 

the pushbutton for a short time. It will stay on or off as long 

as people are detected plus the confi gured follow up time.

BROWN  = L’ (connected phase)

BLACK 

= L (permanent phase)

BLUE 

= N (neutral wire)

WHITE 

= not used

GREY 

= R  (remote for Slave 

and push button)

GREY  = L  (permanent phase)
WHITE  = N  (neutral wire)
GREEN  = R‘  (remote for Slave)

Illuminated for 0.5 seconds

 Not-accepted command, detector blocked

Green LED as an acknowledgement of receipt for 

commands from the remote control

Lights up for 3 seconds

Semi automatic or user signal correctly received

Green LED as an indicator of status for status “Permanent 

protection against sabotage”

Flashing irregularly

 Movement are detected within the area of coverage

Flashing regularly

 Detector identifies bright, light off 

(dependent upon operating mode)

Not illuminated

 Detector identifies dark, light on 

(dependent upon operating mode)

lluminated for 2 seconds

Signal validly received 

(only supported for “Light on/Light off” function)

1

2

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Walking across
Walking towards
Seated

10 m

6 m

2.50 m

10 m

360°

2.50 m

1

2

max

50

Lux

1500

Lux

ON

OFF

Presence and brightness-dependent light control with optional 

presence-dependent HVAC control

MASTER

Terminal connection for standard operation

MASTER

Standard operation with external push button

MASTER

SLAVE

MASTER

Terminal connection for Master-/Slave-operation

Terminal connection for parallel operation

The parallel operation is not allowed for Master units!

Master-/Slave-operation with one Master and several Slaves.

 

The Master is the only unit to read in the lux levels and to 

switch the connected loads. The Slave units will react on 

motion only, independently of the lux levels, by sending an 

impulse via the dry contact, to the Master. No further loads 

can be connected at this contact.

A separate remote input

 

(R) can be used to manually switch 

the light on and off as required.