Installation and Operating Instruction for
B.E.G.
- Occupancy detector PD4-M-2C-DUO-FC/FM
LUXOMAT
®
PD4-M-2C-DUO
1. Mounting preparation
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision of
qualified skilled electrical personnel
in accordance with electredechnical
regulations.
Disconnect supply before installing!
The device is not suited for safe dis-
connection of the mains supply.
When in Master/Slave mode of
operation, the Master-appliance must
always be installed at the location
where there is least daylight.
GB
3a. Hardware configuration SM
Position light sensor LED’s and potentiometers
LED 1 green
LED 2 white
LED 3 red
Light sensor channel 1
5. DIP switch functions
DIP-
switch
ON
OFF
1
Semi automatic mode
Fully automatic mode
2
daylight
mixedlight
3
LED OFF
LED ON
DIP
OFF
ON
1
2
3
The detector has
been designed
and developed
specifically for instal-
lation in suspended
ceilings.
A circular opening
of diameter 68 mm
must first of all be
produced in the
ceiling.
2b. Installation of the
LUXOMAT
®
PD4-M-2C-DUO-FC
The detector can be installed
in conventional inlet-sockets
mounted on the ceiling.
The assembly plate enclosed
must be stripped off prior
to installation and secured
to the ceiling using 2 or 4
screws and ensuring that it is
not laterally transposed.
( For connections please see
pt. 21!)
2c. Installation of the
LUXOMAT
®
PD4-M-2C-DUO-FM
B.I.T
.
Q.C
.
PAS
SED
1
LED 1 green
LED 2 white
LED 3 red
3b. Hardware configuration FM and FC
Position light sensor LED’s and potentiometers
Potentiometer 1 Lux channel 1
Potentiometer 2 Time channel 1 & 2
Potentiometer 3 Lux channel 2
DIP 1
FA/SA
DIP 2
MIX/DAY
DIP 3
LED ON/OFF
Default:
VA, MIX and LED ON
The DIP switch settings are overriden using the remote control.
4a. Position DIP-switches SM
DIP 1
FA/SA
DIP 2
MIX/DAY
DIP 3
LED ON/OFF
Default:
VA, MIX and LED ON
The DIP switch settings are overriden using the remote control.
4b. Position DIP-switches FM and FC
The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the
potentiometers
• Reset when open
Potentiometer3 Time channel 1&2
Potentiometer1 Lux channel 1
Potentiometer2 Lux channel 2
Option: 92092
Wall bracket for remote control
IR-PD-DUO
6. Putting into operation of the remote control
LUXOMAT
®
IR-PD-DUO
Check Battery:
Open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
Caution:
Settings with remote control super-
sede the settings by potentiometers.
Light sensor channel 2
Light sensor channel 2
Light sensor channel 1
IR-PD-DUO
R S1
L
–
L
Rel2
N
Rel1
230
VAC ±10%
50-60
Hz
S2
Slave/
Remote
ON
OFF
LED ON_OFF
MI
X_D
AY
VA_HA
ON
OFF
DIP
1
2
3
S
L
L
R
Rel2
N
Rel1
230
VAC ±10%
50-60
Hz
ON
OFF
DIP
1
2
3
1 2
1
2 3
3
40
15
30
1
2 5
10
16
TES
T
120
A
5
60
50
40
30
15
x
1 2 3
2a. Installation of the
LUXOMAT
®
PD4-M-2C-DUO-SM
The detector must be
installed on a solid
and level surface. The
circular cover ring must
be removed prior to as-
sembly. To do this, twist
the lens anticlockwise
through approximately 5°
and lift off.
Having connected up the
wires in accordance with
regulations, secure the
detector with 2 screws.
After installation replace
the lens and lock (turn
clockwise). Mains to be
connected.
Having connected up the cables in accordance
with regulations, the detector is inserted into
the opening as shown in the drawing opposite
and fixed into position with the assistance of the
spring clip.