21. 100 h function
(long press when closed)
T5 and T8 are recommended to burn-in for 100 h at maximum
brightness before dimming. This would prolong the life of the
lamp.
In the 100 h function mode, the detector only switches on and
off. A dimming to the set value will be suppressed. The lamp has
to burn for 100 h, until the set value gets regulated.
The 100 h function will be activated by pressing the button
longer (>3 sec.). An activated time can be stopped by a long
press of the button again. The red / green LED indicates if the
function is activated.
Before any dimming is possible, the dimming function is
suppressed for 100 h at T5 or 80 h at T8 fluorescent lamps .
They have to burn in at 100%.
Failure to comply to the 100 h burn-in would lead to reduc-
ing the life of the lamp. Unwanted random variations in light
intensity can be the result.
24. Reset the detector
The double lock being activated, the detector can be reset (deacti-
vation of the double lock) as follows:
•
Disconnect operating voltage
•
Connect operating voltage for 31 to 59 secs.
•
Disconnect operating voltage again
•
Connect operating voltage again and wait for the self
testing
•
Open detector
With this procedure, the remote control programmed values are
not deleted (before activation of the double lock).
Alternatively, the detector can be reset in this way:
•
Disconnect operating voltage
•
Set potentiometer B to "TEST" and potentiometer A to
"SUN"
•
Connect operating voltage
Except of the INI ON/OFF setting, the detector will be reset to
factory settings or the settings of the potentiometers.
Pushing the "RESET" button on the remote control in open state
will delete all of the values which were set by means of the remote
control (except of INI ON/OFF) and set the detector back to
factory settings.
17. Light regulation
The detector integrated two different light control algorithms. The
set value for the first algorithm is adjusted by potentiometer (LUX)
on the device. Very small light amounts, which shine directly to
the detector, have the result of a trigger under control of the set
value.
The second algorithm has an integrated daylight compensation.
Therefore, it is necessary that the detector analyses the switched
light quantity. This algorithm can only be used by remote control.
The programming of the set value and the measurement of the
light quantity is carried out in two steps:
In the open state
•
The set value will be adjusted without daylight (please
darken the room) by using the remote control.
•
Measuring the light quantity will be initiated by a long
press (> 3 sec) of the test button. The detector turns the
light on for 5 min. at 100%. Then the light will turn off
and on for a short time and stays on after that. This
measuring process is shown by a flashing green LED (10
sec off / 1 sec on). This measuring process is required for
every change of the set value.
If the measuring process is not performed, the detector performs it
automatically when the ambient light is less than 50 LUX for 1 h.
18. Fully automatic/ Semi-automatic mode
max
50
Lux
1500
Lux
ON
OFF
The mode is changed using the button "Light" in the open state.
Each time the button is pressed, the current operating mode is
indicated by the LEDs:
Red lights for 3 sec. = Fully automatic mode
Green lights for 3 sec. = Semi-automatic mode
Fully automatic mode
In this operating mode, the lighting switches on and off
automatically for increased comfort depending on presence and
brightness.
Semi-automatic mode
In this operating mode, the light turns on only after a manual
switching, for an increased savings success. Switching off is
automatically or manually.
The semi-automatic mode basically behaves like the fully
automatic mode. The only difference is that the switching on has
to be done by hand, always!
!
19. Settings during the Self-test cycle
In the first 60 seconds after connecting the AC voltage, the
following functions can be set:
!
INI-OFF/ON mode:
Turn off or turn on the detector during the self-test cycle of
60 sec. The final state is active. Factory setting is that the
light is on during initialization.
In the mode INI-OFF, the detector does not turn on
after connection to mains. Even movement switches the
detector on only after 60 sec.
Startup behavior:
The set value can be reached in two ways after
switching on. The detector switches the lights on at 10%
and then adjusts upwards (min button) or it switches the
light on at 100% and regulates down (max button). This
is confirmed by a short flashing of red and white LEDs
as well as the lighting. By factory default setting, the
detector switches the light on at 100%.
20. Self-test cycle/Reset
Test mode
“TEST” button for activating the test mode, “Reset” button
for deactivating it.
Resetting when closed
The lighting is switched off, and the follow-up times are
reset.
22. Manual Switching
(short press when closed)
max
50
Lux
1500
Lux
ON
OFF
You can switch the lighting on and off manually by pressing
the button for a short time. It will stay on or off as long as
people are detected plus the configured follow-up time.
23. Manual Dimming – Preset/User
Manually dimming with external pushbutton - You can dim
manually by pressing the push button for a long time (> 2sec.).
When the button is released, the current dimming value is
retained. Upon renewed dimming, the dimming direction is
reversed.
max
50
Lux
1500
Lux
ON
OFF
Two different operating modes can be selected
in the open state.
The button "Doublelock" is for toggling between the modes.
Each time the button is pressed, the current operating mode is
indicated:
Red lights for 3 sec. = Preset
Green lights for 3 sec. = User
PRESET –
the set value brightness is adjusted during start-up
operation by the installer and remains unchanged. The set value
brightness configured through manual dimming is only applied for
the time being.
The constant light regulation is now deactivated!
The current set artificial light level is maintained independent of
the ambient/daylight brightness! After switching off and then
on again, the originally adjusted set value brightness is reset =
constant light regulation is activated.
USER
The set value brightness is changed upon each manual dimming
and is re-adjusted by the user. The constant light regulation
remains activated!