21. 100 h function

(long press when closed) 

T5 and T8 are recommended to burn-in for 100 h at maximum 

brightness before dimming. This would prolong the life of the 

lamp.  
In the 100 h function mode, the detector only switches on and 

off. A dimming to the set value will be suppressed. The lamp has 

to burn for 100 h, until the set value gets regulated. 
The 100 h function will be activated by pressing the button 

longer (>3 sec.). An activated time can be stopped by a long 

press of the button again. The red / green LED indicates if the 

function is activated.

Before any dimming is possible, the dimming function is 

suppressed for 100 h at T5 or 80 h at T8 fluorescent lamps .

 

They have to burn in at 100%.

Failure to comply to the 100 h burn-in would lead to reduc-

ing the life of the lamp. Unwanted random variations in light 

intensity can be the result.

24. Reset the detector

The double lock being activated, the detector can be reset (deacti-

vation of the double lock) as follows:

• 

Disconnect operating voltage 

• 

Connect operating voltage for 31 to 59 secs.  

• 

Disconnect operating voltage again

• 

Connect operating voltage again and wait for the self 

testing

• 

Open detector

With this procedure, the remote control programmed values   are 

not deleted (before activation of the double lock).
Alternatively, the detector can be reset in this way:

• 

Disconnect operating voltage 

• 

Set potentiometer B to "TEST" and potentiometer A to 

"SUN"

• 

Connect operating voltage

Except of the INI ON/OFF setting, the detector will be reset to 

factory settings or the settings of the potentiometers.

Pushing the "RESET" button on the remote control in open state 

will delete all of the values which were set by means of the remote 

control (except of INI ON/OFF) and set the detector back to  

factory settings.

17. Light regulation

The detector integrated two different light control algorithms. The 

set value for the first algorithm is adjusted by potentiometer (LUX) 

on the device. Very small light amounts, which shine directly to 

the detector, have the result of a trigger under control of the set 

value.

The second algorithm has an integrated daylight compensation. 

Therefore, it is necessary that the detector analyses the switched 

light quantity. This algorithm can only be used by remote control. 

The programming of the set value and the measurement of the 

light quantity is carried out in two steps: 

In the open state

• 

The set value will be adjusted without daylight (please 

darken the room) by using the remote control.

• 

Measuring the light quantity will be initiated by a long 

press (> 3 sec) of the test button. The detector turns the 

light on for 5 min. at 100%. Then the light will turn off 

and on for a short time and stays on after that. This 

measuring process is shown by a flashing green LED (10 

sec off   / 1 sec on). This measuring process is required for 

every change of the set value.

If the measuring process is not performed, the detector performs it 

automatically when the ambient light is less than 50 LUX for 1 h.

18.  Fully automatic/ Semi-automatic mode   

max

50

Lux

1500

Lux

ON

OFF

 

The mode is changed using the button "Light" in the open state.

Each time the button is pressed, the current operating mode is 

indicated by the LEDs:

Red lights for 3 sec.  = Fully automatic mode 

Green lights for 3 sec.  = Semi-automatic mode 

Fully automatic mode

 

In this operating mode, the lighting switches on and off 

automatically for increased comfort depending on presence and 

brightness.

Semi-automatic mode 

In this operating mode, the light turns on only after a manual 

switching, for an increased savings success. Switching off is 

automatically or manually.
The semi-automatic mode basically behaves like the fully 

automatic mode. The only difference is that the switching on has 

to be done by hand, always!  

!

19. Settings during the Self-test cycle

In the first 60 seconds after connecting the AC voltage, the 

following functions can be set:

!

INI-OFF/ON mode:  

 

Turn off or turn on the detector during the self-test cycle of 

60 sec. The final state is active. Factory setting is that the 

light is on during initialization.
In the mode INI-OFF, the detector does not turn on 

after connection to mains. Even movement switches the 

detector on only after 60 sec.

Startup behavior:

The set value can be reached in two ways after 

switching on. The detector switches the lights on at 10% 

and then adjusts upwards (min button) or it switches the 

light on at 100% and regulates down (max button). This 

is confirmed by a short flashing of red and white LEDs 

as well as the lighting. By factory default setting, the 

detector switches the light on at 100%.

20. Self-test cycle/Reset

Test mode  

“TEST” button for activating the test mode, “Reset” button 

for deactivating it.

Resetting when closed 

The lighting is switched off, and the follow-up times are 

reset.

22. Manual Switching

(short press when closed) 

  

max

50

Lux

1500

Lux

ON

OFF

You can switch the lighting on and off manually by pressing 

the button for a short time. It will stay on or off as long as 

people are detected plus the configured follow-up time.

23.   Manual Dimming – Preset/User

 

 

Manually dimming with external pushbutton - You can dim 

manually by pressing the push button for a long time (> 2sec.). 

When the button is released, the current dimming value is 

retained. Upon renewed dimming, the dimming direction is 

reversed.

max

50

Lux

1500

Lux

ON

OFF

         Two different operating modes can be selected  

      in the open state.

The button "Doublelock" is for toggling between the modes. 

Each time the button is pressed, the current operating mode is 

indicated:
Red lights for 3 sec.  = Preset

Green lights for 3 sec.  = User

PRESET – 

the set value brightness is adjusted during start-up 

operation by the installer and remains unchanged. The set value 

brightness configured through manual dimming is only applied for 

the time being.  
The constant light regulation is now deactivated!  

The current set artificial light level is maintained independent of 

the ambient/daylight brightness! After switching off and then 

on again, the originally adjusted set value brightness is reset = 

constant light regulation is activated.

USER

The set value brightness is changed upon each manual dimming 

and is re-adjusted by the user. The constant light regulation 

remains activated!