PD4-M-HCL 93006/93007
50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818
Page 8 / 10
Groups 1-4
Show / Check groupings
In the group assignment process: Saves
selected group of flashing DALI ECG
•
Group 1 for light zone A
dark areas (wall side)
•
Group 2 for light zone A
neutral regions
•
Group 3 for light zone A
light areas (window)
•
Group 4 for light zone B
Blackboard lighting
6.3. Device
Reset / Factory settings
In closed state: The device switches off the
connected load and restarts without self
test cycle.
In opened state: The device is reset to
factory settings when the potentiometers
are set to TEST and SUN, otherwise to
potentiometer settings. The settings made
during self test cycle remain valid.
Test mode
The test mode is for determining the
detection area. Upon each detected
movement the light is switched on
HCL test mode
The test mode is used to check the colour
temperature. The luminaires change from
warm to cold white in quick succession.
Light ON/OFF
Switches zone A ON/OFF
Brighter
Closed: Fast dimming up to MAX
Open: Slow dimming up to MAX
Darker
Closed: Fast dimming down to MIN
Open: Slow dimming down to MIN
Save Brightness
Closed: Closed dimming
Open: Saves the current light level
7. Addressing and formation of groups
Before groups are formed, it is recommended that you draw up
a plan showing the grouping of all DALI electronic ballasts in the
room.
7.1. Step 1: Broadcast Reset
To ensure that all connected DALI electronic ballasts with
identical basic settings are used, we recommend that you first
perform a broadcast reset.