Sensor and power supply in one case for onwall-, ceiling- 

and flushmounting

Power supply:

 230 V~ +6 %/-10 %

Power consumption:

 < 1W

Ambient temperature:

 -25°C to +50°C

Degree of protection /class:

 SM IP54, FC and FM IP20, FC 

with accessory IP23 / II 

Settings:  

manually and by remote control

Light values:

 20 - 1000 Lux (Remote control)

Extension of the detection area:

 with Slaves

Area of coverage:

 square 4 x 90°

Range of coverage Ø H 2,50 m / T = 18°C:

 

 

seated 4.20 m / tangential 7.50 m / radial 4.50 m

Recommended height for mounting:

 2 - 3 m

Light measurement:

 mixed light, da artificial light

Lux values:

 10 - 2000 Lux (Potentiometer)

• Relay/Channel 1 for light-connection

Type of contact:

 dry contact type NO

Contact load:

 2300 W cos (

ϕ)

=1 / 1150 VA cos (

ϕ)

= 0.5

Time-settings:

 15 sec. - 16 min. (30 min. with remote

control) / Test

• Relay/Channel 2 for HVAC

Contact load:

 230 V~, 3 A cos (

ϕ)

=1 

Time-settings:

 5 min. - 120 min. with time delay of 5 min. 

for follow-up time > 15 min.

Dimensions H x Ø [mm]

 

SM 

FC 

FM

PD1-M-2C 

80 x 98 

84 x 98  65 x 98

Visible portion when built into ceiling:

 30 x 98 mm

Technical data PD1-Slave

Electrical data same as above, but just one channel for 

signaling motion detection

 

Declaration of Conformity: 

The product complies with 

the low voltage recommendation 2006/95/EC and the 

EMV recommendation 2004/108/EC

11. Technical data PD1-Master-2C

10. PD1-M-2C - Connections

Type

SM

FC

FM

PD1-M-2C (Master)

92177

92174

92170

PD1-S (Slave)

92178

92175

92172

LUXOMAT

®

 Remote control:

IR-PD (incl. wall bracket) 

92160

IR-PD-Mini 

 

92159

Accessory:

BSK Ball basket guard   

92199

Wall bracket for remote control as replacement  92100

Blinds 

 

92260 

Occupancy detectors - Covering IP23 

92206

SM-Socket for PD1-FM   

92171

8. Article / Part nr. / Accessory

M

A

N 6

31

–  2

11

20

9–

1

7. Range of Coverage

5.  Fully / Semi automatic mode 

(for IR-PD functions see page 1)

 

Fully automatic operation

In this operating mode, the lighting switches automati-

cally on and off for increased comfort, depending on 

presence and brightness.

Semiautomatic operation

(Semiautomatic can only be activated via the remote 

control!)

In this operating condition, in order to gain increased 

savings, the lighting is energized only after being manu-

ally switched on. Switch-off takes place automatically.

The semiautomatic mode basically behaves like the fully 

automatic one. However, the difference is that switching-

on must always be carried out manually!

As many (closer-contact) buttons as desired can be wired 

in parallel on the “R” button input (ON/OFF).

6. Manual Switching 

 

You can switch the lighting on and off manually by 

pressing the pushbutton for a short time. It will stay on or 

off as long as people are detected plus the configured 

follow up time.

12. LED-functional indicators, fault-finding

The functional indicators in the case of the 

LUXOMAT

®

 

PD1-M-2C (red and green LED‘s) 

Red LED indicating self-checking mode (over a period 

of 60 seconds following mains‘-supply lock-on)

Flashing at intervals of 1 second

 

EEPROM/memory empty

Flashing rapidly

EEPROM/memory contains information

Red LED as an indicator of status

Flashing irregularly

Movements are detected within the area of coverage

Flashing regularly

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 Detector identifies dark, light on  

(dependent upon operating mode)

Flashing extremely rapidly

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for  

commands from the remote control 

Illuminated for 2 seconds

Signal validly received

Illuminated for 0.5 seconds

 Not-accepted command, detector blocked

Flashing extremely rapidly

 

 Not-accepted command, occurs, for example, when 

an attempt is made to input twilight-value are too 

bright or too dark

Lights up for 3 seconds

Fully automatic mode

Flashing for 3 seconds

Semi automatic mode

Green LED as an indicator of status (only for status 

“Permanent protection against sabotage”

)

Flashing irregularly

 Movement are detected within the area of coverage

Flashing regularly

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 Detector identifies dark, light on  

(dependent upon operating mode)

lluminated for 2 seconds 

Signal validly received  

(dependent upon operating mode)

7.5

0 m

4.20 m

7.50 m

4 x 90°

2.50 m

1

2

1

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Walking across
Walking towards
Seated

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

Connection PD1-M-2C

NO

NO

N

R

L L

SLAVE

L'

3A

2

9. Wiring diagrams

Standard operation, 

manual switching possible 

(NO-contact to be pressed for approx. 1sec.). The 

potentiometers not to be set on “Test“ or “Sun“ 

otherwise the preadjusted values will get lost during 

this manual operation.

Master-/Slave-operation, i.e. Masters opera-

te as Slaves but with additional push button 

function 

to switch the light manually. The preset 

values will not get lost. The Master is the only unit to 

read in the levels and to switch the connected loads. 

The Slave units will react on motion only, independ-

ently of the Lux levels, by sending an impulse via the 

dry contact, to the Master.

Terminal connection for Master-/Slave-operation

R 2

MASTER

MASTER/SLAVE 

modus

Master-/Slave-operation with one Master 

and several Slaves. 

The Master is the only unit 

to read in the Lux levels and to switch the connected 

loads. The Slave units will react on motion only, in-

dependently of the Lux levels, by sending an impulse 

via the dry contact, to the Master.

Terminal connection for standard operation

HVAC

MASTER

HVAC

SLAVE

MASTER

Terminal connection for Master-/Slave-operation

Standard operation with external push button

HVAC

MASTER

Standard operation

3

3

Отзывы: