5. USER INTERFACES
Continued from the previous page
Address
Access
Description
0xF001
-/W
Allowed alarms:
•
bit 0 – active level on BIN1 input
•
bit 1 – active level on BIN2 input
•
bit 2 – active level on BIN3 input
•
bit 3 – active level on BIN4 input
•
bit 4 – exceeded the lower limit of the AN1 analogue input
•
bit 5 – exceeded the upper limit of the AN1 analogue input
•
bit 6 – exceeded the lower limit of the AN2 analogue input
•
bit 7 – exceeded the upper limit of the AN2 analogue input
•
bit 8 – exceeded the limit frequency of CNT1
•
bit 9 – exceeded the limit frequency of CNT2
...
0xF100
-/W
Negative logic of binary inputs:
•
bit 0 – BIN1 input
•
bit 1 – BIN2 input
•
bit 2 – BIN3 input
•
bit 3 – BIN4 input
...
0xF200
-/W
Normal level of binary outputs:
•
bit 0 – OUT1 output
0xF201
-/W
Feeder – number of pulses at the BIN1/CNT1 input
0xF202
-/W
Feeder – pulse length at the OUT1 output [1/8 sec]
...
0xF300
-/W
AN1 – sampling period [sec]
0xF301
-/W
AN1 – multiplicative constant (with sign)
0xF302
-/W
AN1 – additive constant (with sign)
0xF303
-/W
AN1 – hysteresis value (with sign)
0xF304
-/W
AN1 – lower limit (with sign)
0xF305
-/W
AN1 – upper limit (with sign)
To be continued on the next page
33