Troubleshooting and Testing Procedures (cont.)

             

 

The 7 segment clock display is also used to aid with error codes that can occur. It will shut off after 

 

3 minutes of no button activity. To wake up the display, simply press any button.

5.  Displayed Error Codes are as Follows:

 

OVER LOAD:

 

Will be displayed by flashing “LoAd” on the clock display. If 

 

this condition occurs, the Power Pack will Auto reset 3 times 

 

and if Over Load condition still exists, it will shut off and 

 

continue flashing “LoAd”. To resolve this, try and find the 

 

defective light or remove some of the lights to lower the load. 

 

Shorted underground wiring, usually at a distance away, can 

 

also cause this, but it will generally trip the Over Load condition 

 

faster than too many lights on one circuit will.

 

SHORT CIRCUIT: 

 

Will shut down the Power Pack within a few seconds upon 

 

powering on and it will flash “Shrt” on the display. Check 

 

for faulty wiring, frayed wires near the +/- terminal block 

 

or defective LED bulb. Isolate short. Reset by unplugging 

 

the AC cord, wait 5 seconds and reconnect. Power on unit. 

 

If Short circuit does not exist, continue. If fault returns 

 

again, isolate the bad wiring or faulty LED bulb.

 

BAD POWER SUPPLY: 

 

Will be displayed by flashing “dbPS” on the clock display only 

 

upon power on and when 0 volts output detected. If this condition 

 

occurs, remove all landscape wiring from output terminal block, 

 

remove AC power cord, wait 5 seconds to reset and if message 

 

still exist then will require service.

 

FLASHING 12:00: 

 

Will be displayed when system has not been programed, or 

 

when battery level is too low. Press and hold the clock button 

    

While selecting up/dn arrow to adjust to local time setting. After 

 

1 hour plugged into AC power, the battery will be charged.

 

FAN MONITOR:

 

If fan is obstructed, there will be 3 attempts to unjam the fan 

 

from insects or possible plant growth entering the rear vents. 

 

The Power Pack will shut off and flash “FAn”. Unplug the AC 

 

cord and inspect rear vents. Plug in the AC power cord and try again.

6.  Electrical Specifications:

1-1:

 

USA Input voltage: /-10%   50-60Hz  

  Euro Input voltage: 220-/- 10%   50-60Hz.

1-2:

 

Output DC voltage: (MAX) 13.3VDC  +/- 5% variable dimer to 8.5VDC +/-2% (MIN)

1-3: 

   Maximum DC AMPS 12.5 continuous

1-4:

     Overload trip @ 17-19 amps from 3-15 minutes

Operating Instructions

150W Power Pack

 

Содержание 150W

Страница 1: ...a component of landscape lighting systems where the suitability of the combination shall be determined by CSA or local inspection authorities having jurisdiction Use Azek TimberTech wire only To order additional lengths of wire order AZTDLLEDWIRE for secondary runs only The secondary wiring is intended for shallow burial less than 6 inches 152mm Only use a proper three pronged GFCI outlet The powe...

Страница 2: ...Power and Lights ON Dimmer Control 3 8 Operating Instructions 150W Power Pack ...

Страница 3: ... desired TIME OFF 2 3 AUTO Uses the Photo Eye trigger control It turns off when there is light on the eye for over one minute and turns on when there is no light on the eye for over one minute 2 4 OFF Power Pack will not come on 2 5 ON Power Pack is always on Use this mode for other home automation systems 2 6 4 6 8 10 Uses the Photo Eye trigger control The Power Pack will come on at dusk and will...

Страница 4: ... Cooling Fan Monitor and Auto Reset Testing the Photo Eye Option 1 Use the internal built in Photo Eye Note Photo eye must be uncovered at all times except when using the external photo eye probe Option 2 Use the External Photo Eye This option is used when the Power Pack is mounted inside or when you are trying to block uncontrolled light from a nearby source You should make sure the internal Phot...

Страница 5: ... on unit If Short circuit does not exist continue If fault returns again isolate the bad wiring or faulty LED bulb BAD POWER SUPPLY Will be displayed by flashing dbPS on the clock display only upon power on and when 0 volts output detected If this condition occurs remove all landscape wiring from output terminal block remove AC power cord wait 5 seconds to reset and if message still exist then wil...

Отзывы: