- Field Mount type Pressure Indicating Controllers
27
Repeat actions in steps (4) and (5) until both rising points conforms with the set
point.
(6) Set the differential gap dial to the 100% position on the right or left side.
Adjust the feedback link adjusting pin so that the output rises at the setting point.
(to lower the output for once, slightly open the flapper with the tip of a screw
driver.)
(7) Repeat steps (4), (5) and (6) so that the output rising points falls within the gap of
set point (SP) + 1.5% F.S. at entire range of the differential gap dial.