AB-6584
9
Parts Identification
Figure 5. Parts identification
Table 2. Indication and operation of operating status LED
LED indication
LED operation
Data transmitting
Repetition of 1-second ON and I-second OFF
LC-bus error
Repetition of 0.25-second ON and 0.25-second OFF
Major alarm / initializing
ON
Minor alarm
Repetition of 1-second ON, 0.25-second OFF, 0.25-second ON, and 0.25-second OFF.
Engineering mode
Repetition of 0.25-second ON, 0.25-second OFF, 0.25-second ON, and 1.25-second OFF.
Power OFF
OFF
Connection of Data Setter for LonTalk Protocol
Connect the CompactFlash
®
memory type Data Setter (Model QY5111B) for LonTalk protocol to LC-bus port of Infilex AC with
the Data Setter adaptor (Part No. DY5301S0000) or to CONF. port of Infilex AC with the conversion cable Part No.
83166788-001 (1 cable) / 83166788-010 (10 cables) and Data Setter adaptor Part No. DY5301S0000.
For details of Data Setter adaptor Part No. DY5301S0000, refer to its Specifications manual.
∗
see Note.
Figure 6. Connection example of Data Setter with Data setter adaptor to LC-bus port/CONF. port of Infilex AC
LED for
operating status
S1 switch*
∗
Do not press S1 switch.
Battery holder
Indication tag
DIN rail
mounting
hook
Infilex
™
AC
Model WY5317
Infilex
™
GC
Model WY5311
Infilex
™
GD
Model WY5310
Data Setter
adaptor
Model DY5301S
Infilex
™
ZM
Model WY5322
IAC
Model WY7307
Infilex
™
FC
Model WY5305
Infilex
™
VC
Model WY5306
Data Setter
Model QY5111B
(For setting Infilex AC and other remote units connected on both LC-bus
and LS-bus: Connect Data Setter with Data Setter adaptor to LC-bus port
or CONF. port of Infilex AC.)
Note:
To connect the Data Setter with Data Setter adaptor to the CONF. port of Infilex AC, be
sure to provide the conversion cable between the Data Setter adaptor and Infilex AC.
(Conversion cable: Part No. 83166788-001 / 83166788-010)
LC-bus
(LonTalk
protocol)
LS-bus (LonTalk protocol)