Item 

Function 

Description 

Remark 

Control (2/2) 

Optimum 
temperature control 
of supply air*

1

 

Controls the supply air temperature of the air 
conditioning unit at the optimum level to provide 
comfort and to save energy. 

- One Infilex ZM controls up to 4 groups. 
-

 

AHU controller and Infilex ZM must be 
connected to the same NC-bus line.

 

Mixing loss control*

1

  Sets the difference between the set temperature of 

the perimeter air conditioning unit and the interior air 
conditioning unit that are interlocked.  This prevents 
the mixing loss. 

- One (group of) Infilex VC interlocks 

with another (group of) Infilex VC 
and/or Infilex FC. 

- Slave Infilex VC and/or Infilex FC can 

not interlock with a different Infilex VC 
and/or Infilex FC. 

- Do not operate the slave Infilex VC 

and/or Infilex FC with the user terminal. 

Parallel operation of 
multiple VAV*

1

 

Concurrently turns on/off the multiple VAV units or 
changes fan speed of the multiple VAV units (supply 
air VAV unit and return air VAV unit). 

- One-to-one Infilex VC or one-to- 

multiple Infilex VC are interlocked. 

- For the parallel operation, Infilex VC 

must be connected to the same 
SC-bus line. 

Fan powered control  Turns on/off the fan of the VAV unit with fan to 

maintain enough airflow.  

Fan output corresponds with heating/ 
cooling conditions and each fan type. 
  -  Series fan:  

Fan is ON when VAV unit is ON. 

  -  Parallel fan (for temperature):  

Fan is ON when VAV unit is ON in 
heating mode. 

  -  Parallel fan (for air volume):  

Fan is ON when VAV unit is ON in 
heating mode with low airflow. 

Reheat control*

1

 

Enables the heating mode by electric heater or hot 
water valve. 

- Electric heater and ON/OFF valve 

allow up to two-position control. 
Floating valve allows single-position 
control. 

- Reheat control is forcibly performed by 

operating the BMS client PC (manual 
override function).   

Monitoring (with the 
BMS client PC) 

Individual 
monitoring*

1

 

Monitors and controls the point data (measuring, 
setting, operation, and control data) of Infilex VC 
from the BMS client PC.   
The following are examples of the point data for 
individual monitoring: 
VAV ON/OFF, VAV failure, room temperature, cool 
setting/main setting, heat setting, heat high limit/set 
high limit, cool low limit/set low limit, setback, 
reheater output, fan output, measured air volume, 
max. air volume, damper position 
(Not all of the items above are required to monitor or 
control with the client PC.) 

 

Group monitoring*

1

  Forms a group of multiple Infilex VC, monitors and 

controls the following point data of the grouped 
Infilex VC through the BMS client PC: 
VAV ON/OFF, VAV failure, room temperature*

3

, cool 

setting/main setting, heat setting, heat high limit/set 
high limit, cool low limit/set low limit, setback 
(Not all of the items above are required to monitor or 
control with the client PC.) 

- All of Infilex VC connected from a 

single Infilex ZM are divided into up to 
25 groups.  (Various grouping is 
available.) 

- The point data for the group monitoring 

can not be individually monitored. 

- Both of the group monitoring and the 

individual monitoring can be applied to 
the grouped Infilex VC. (e.g., VAV 
ON/OFF for group monitoring and 
room temperature for individual 
monitoring) 

Batch operation*

1

 

Forcibly sets the airflow of all the VAV units (that are 
included in each air conditioning unit group) at the 
maximum or minimum volume by operating the BMS 
client PC. 

- One Infilex ZM controls up to four 

groups. 

- Batch operation is enabled with Infilex 

ZM as well as with the BMS client PC. 

BMS: Building management system 
VAV: Variable air volume 

 

Notes: 
*1  These functions are enabled by Infilex VC being combined with Infilex ZM and integrated in our BMS. 
*3  Room temperature for the group monitoring calculates either the average value in a group or the representative value of a group

.

 

Содержание Infilex VC

Страница 1: ...C Heating ventilation and air conditioning VAV Variable air volume Features Economical efficiency Temperature and air volume are controlled by a single controller VAV controller that resides on an act...

Страница 2: ...e of danger For example the sign on the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates...

Страница 3: ...erheating Be sure to provide a circuit breaker for the power to the product as the product does not have a power switch Do not test the withstand voltage of the product Doing so might cause accident o...

Страница 4: ...opanel and a temperature sensor can be connected to the same Infilex VC 6 Network variable enables Infilex VC to directly connect to other controllers via LC bus without Infilex ZM Figure 1 System con...

Страница 5: ...ls Item Part number Universal bracket 12595 00001 Modular branch unit DY7203A0000 Modular relay units 5 pieces set DY7202A0000 Adapters for connecting to a Pt100 temperature sensor 10 pieces set DY720...

Страница 6: ...r longer 40 mm or longer Operating environmental conditions Temperature 0 C to 50 C Humidity 10 RH to 90 RH Non condensing Vibration Max 3 2 m s 10 Hz to 150 Hz Transport storage conditions Temperatur...

Страница 7: ...er e g TYGON Model R 3603 Heater and fan Dry contact 30 V AC 0 8 A or 30 V DC 0 5 A Terminal connection Push in terminal block 2 5 mm 2 or smaller Max 5 m Temperature sensor Pt100 input Pt100 temperat...

Страница 8: ...AB 6655 8 Dimensions 5 N m torque type Figure 2 Dimensions 5 N m torque type mm 198 22 176 66 67 17 35 99 29 11 5 6 20 85 25 5 2...

Страница 9: ...nsions 10 N m torque type mm Universal bracket requiring separate order Figure 4 Dimensions Universal bracket mm 7 5 179 18 23 35 47 58 25 71 83 89 5 5 R2 2 R2 2 4 4 R2 2 4 4 12 2 2 10 206 80 66 25 18...

Страница 10: ...tor modular jack Wire connection indication printed on the body See Fig 6 Terminal block 11 pin Nonuse connector for setting High pressure port for differential pressure pickup Mounting slit Damper sh...

Страница 11: ...AB 6655 11 Wire Connection Indication Figure 6 Wire connection indication printed on Model VY5306C5X30...

Страница 12: ...e When an electric heater is connected additionally provide a circuit to prevent temperature rise Figure 7 Connection example for two step electric heater fan output control Model WY5306C5X30 To tempe...

Страница 13: ...urate control of Infilex VC installed in a 24 hour system floating valves are automatically closed when they are kept unclosed for 48 hours Power supply via safety isolating transformer To temperature...

Страница 14: ...ables to be connected x 4 for the bend radius e g Dimension L for 6 mm modular cable is larger than 24 mm for bend radius Figure 10 Maintenance clearance mm Installation procedure 1 Fully close the VA...

Страница 15: ...versal bracket protruding part into the slit of this product and fix the bracket with the two M4 tapping screws Note The universal bracket required for the installation of this product is commercially...

Страница 16: ...lly closed position This will allow the actuator to shut off the damper Using a wrench tighten the fastening nuts of the shaft clamp to completely fix this product See the following table for the nut...

Страница 17: ...icated with of Infilex VC Required specification of the air flow sensor tube Type Length Inner diameter Outer diameter Material Flexible tube Max 1 m 5 mm to 6 mm Max 10 mm PVC silicon rubber Inflexib...

Страница 18: ...arrower than the shaft may not be acceptable Appropriate screwdriver an example Model 9900 3 mm wide 100 mm long or Model 910 3 mm wide 75 mm long manufactured by Vessel Co Inc Since the terminal bloc...

Страница 19: ...d on the LAN cable by the cable stopper of the modular plug Check the contacts and the cable stopper when crimping the modular plug 5 Follow 1 to 4 for the other end of the LAN cable 6 Check continuit...

Страница 20: ...ure 21 Terminator connection example for bus topology Wiring length 250 900 m Wiring length Max 250 m Connection for free topology Total wiring length Max 450 m longest wiring length between one end t...

Страница 21: ...point is set by the BMS client PC Dual setting is available 2 VAV interlocking with air conditioning unit 1 Interlocks the ON OFF operations of the VAV units with those of the air conditioning units O...

Страница 22: ...BMS client PC manual override function Monitoring with the BMS client PC Individual monitoring 1 Monitors and controls the point data measuring setting operation and control data of Infilex VC from th...

Страница 23: ...s communication with LonTalk protocol Minor error Error 2 Figure 24 Descriptions of orange LED indications status IMPORTANT Do not press the LED button Operation of Infilex VC will be stopped and the...

Страница 24: ...opanel with address 1 connected to the Infilex VC will not work For two Neopanel connection provide Model QY7205CXXX1 for the address 1 and Model QY7205CXXX2 for the address 2 Address number is indica...

Страница 25: ...pull out the cables to make sure they are completely connected Optional Tools Figure 30 Modular crimper Part No DY7205A0002 Figure 31 Modular cable tester Part No DY7206A0000 Modular crimper See Fig...

Страница 26: ...it Messages VAV Object Device Documentation Node Object Configuration Properties CP Data File Transfer Configuration Properties Configuration Properties nc25 nciNetConfig SCPT_nwrk_cnfg nc165 nciDevMa...

Страница 27: ...temp_p nv16 nvoFlowControlPt SNVT_flow nv17 nvoSpaceTemp SNVT_temp_p nv3 nvoUnitSatus SNVT_hvac_status nv4 nvoBoxFlow SNVT_flow nv18 Configuration Properties nc49 nciSndHrtBt Mandatory nc60 nciSetPnts...

Страница 28: ..._obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default value...

Страница 29: ...SNVT name Valid range Default value Description SB RB MT nvoSpaceTemp SNVT_temp_p 10 00 to 50 00 C 327 67 Space temperature output inside differential pressure sensor nvoUnitStatus SNVT_hvac_status Un...

Страница 30: ...v_percent 0 000 to 100 000 0 000 Damper position output nvoFanSpeed SNVT_switch Fan output nvoReheater SNVT_lev_percentq 0 000 to 100 000 0 000 Reheater output nvoSpaceTemp2 SNVT_temp_p 10 00 to 50 00...

Страница 31: ...ration control parameter nciParaVav02 UCPTvavTempCtrl3 Temperature control parameter nciParaVav03 UCPTvavDischargeAirTempCtrl2 Duct inlet temperature optimization parameter nciParaVav04 UCPTvavFlowCtr...

Страница 32: ...Engineers ASHRAE TYGON is a trademark of Saint Gobain Performance Plastics Corporation Specifications are subject to change without notice Building Systems Company http www azbil com Rev 8 0 Mar 2018...

Отзывы: