Azbil Infilex VC Скачать руководство пользователя страница 1

AB-6655 

  Our controller Infilex series:  Infilex is named for “Infinity” and “Flexible”.

 

© 2006-2018 Azbil Corporation All Rights Reserved.

 

Specifications/Instructions 

 

Infilex

 VC 

Variable Air Volume Controller with Actuator 

for LonTalk® Communication 

 
General 

Infilex VC (Infilex: named for “Infinity” and “Flexible”) Model 
WY5306C  is  a  VAV  controller  with  an  actuator  that 
communicates  via  LonTalk®  protocol.    Infilex  VC  provides 
high-performance  DDC  of  VAV  unit  in  a  building 
air-conditioning  system.    Thus,  Infilex  VC,  networked  even 
within a complicated HVAC system, controls VAV unit.   
Besides, Infilex VC offers building owners and operators the 
flexible and enhanced controls of temperature and VAV for 
various VAV units. 
Infilex  VC  sends  unique  energy-saving  information  to  its 
networked zone controller, enhancing overall controllability of 
a building management system. 

DDC: Direct digital control 
HVAC: Heating, ventilation, and air conditioning 
VAV: Variable air volume 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

●  Economical efficiency: 
     - Temperature and air-volume are controlled by a  single 

controller. 

     - VAV  controller  that  resides  on  an  actuator  offers  great 

value. 

●  Wide range of application: 

Most  of  the  major  VAV  types  for  industry  are 
preconfigured in the controller. 

●  Unique energy conservation control: 
     - VAV  damper  opens  wide  to  minimize  the  fan  power 

consumed by static pressure. 

     - Network  with  a  zone  controller  allows  supply  air 

temperature to be  modified at an optimum level. 

 

●  Advanced building management integrated into BMS: 

Our  digital  user  terminal  Neopanel  enables  users  and 
operators to modify the preset setting of temperature and 
operating  schedule  (to  extend)  and  offers  flexibility  of 
temperature control and schedule control. 

●  L

ON

M

ARK

® certified product 

VAV system is configured with LonTalk® protocol.  Also, 
Infilex VC is L

ON

M

ARK

® (version 3.4) certified and thus 

interoperable integrated in the L

ON

W

ORKS

® system. 

●  CE Marking certified product: 

Infilex  VC  Model  WY5306C  conforms  to  all  the 
applicable standards of CE Marking. 

 

Содержание Infilex VC

Страница 1: ...C Heating ventilation and air conditioning VAV Variable air volume Features Economical efficiency Temperature and air volume are controlled by a single controller VAV controller that resides on an act...

Страница 2: ...e of danger For example the sign on the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates...

Страница 3: ...erheating Be sure to provide a circuit breaker for the power to the product as the product does not have a power switch Do not test the withstand voltage of the product Doing so might cause accident o...

Страница 4: ...opanel and a temperature sensor can be connected to the same Infilex VC 6 Network variable enables Infilex VC to directly connect to other controllers via LC bus without Infilex ZM Figure 1 System con...

Страница 5: ...ls Item Part number Universal bracket 12595 00001 Modular branch unit DY7203A0000 Modular relay units 5 pieces set DY7202A0000 Adapters for connecting to a Pt100 temperature sensor 10 pieces set DY720...

Страница 6: ...r longer 40 mm or longer Operating environmental conditions Temperature 0 C to 50 C Humidity 10 RH to 90 RH Non condensing Vibration Max 3 2 m s 10 Hz to 150 Hz Transport storage conditions Temperatur...

Страница 7: ...er e g TYGON Model R 3603 Heater and fan Dry contact 30 V AC 0 8 A or 30 V DC 0 5 A Terminal connection Push in terminal block 2 5 mm 2 or smaller Max 5 m Temperature sensor Pt100 input Pt100 temperat...

Страница 8: ...AB 6655 8 Dimensions 5 N m torque type Figure 2 Dimensions 5 N m torque type mm 198 22 176 66 67 17 35 99 29 11 5 6 20 85 25 5 2...

Страница 9: ...nsions 10 N m torque type mm Universal bracket requiring separate order Figure 4 Dimensions Universal bracket mm 7 5 179 18 23 35 47 58 25 71 83 89 5 5 R2 2 R2 2 4 4 R2 2 4 4 12 2 2 10 206 80 66 25 18...

Страница 10: ...tor modular jack Wire connection indication printed on the body See Fig 6 Terminal block 11 pin Nonuse connector for setting High pressure port for differential pressure pickup Mounting slit Damper sh...

Страница 11: ...AB 6655 11 Wire Connection Indication Figure 6 Wire connection indication printed on Model VY5306C5X30...

Страница 12: ...e When an electric heater is connected additionally provide a circuit to prevent temperature rise Figure 7 Connection example for two step electric heater fan output control Model WY5306C5X30 To tempe...

Страница 13: ...urate control of Infilex VC installed in a 24 hour system floating valves are automatically closed when they are kept unclosed for 48 hours Power supply via safety isolating transformer To temperature...

Страница 14: ...ables to be connected x 4 for the bend radius e g Dimension L for 6 mm modular cable is larger than 24 mm for bend radius Figure 10 Maintenance clearance mm Installation procedure 1 Fully close the VA...

Страница 15: ...versal bracket protruding part into the slit of this product and fix the bracket with the two M4 tapping screws Note The universal bracket required for the installation of this product is commercially...

Страница 16: ...lly closed position This will allow the actuator to shut off the damper Using a wrench tighten the fastening nuts of the shaft clamp to completely fix this product See the following table for the nut...

Страница 17: ...icated with of Infilex VC Required specification of the air flow sensor tube Type Length Inner diameter Outer diameter Material Flexible tube Max 1 m 5 mm to 6 mm Max 10 mm PVC silicon rubber Inflexib...

Страница 18: ...arrower than the shaft may not be acceptable Appropriate screwdriver an example Model 9900 3 mm wide 100 mm long or Model 910 3 mm wide 75 mm long manufactured by Vessel Co Inc Since the terminal bloc...

Страница 19: ...d on the LAN cable by the cable stopper of the modular plug Check the contacts and the cable stopper when crimping the modular plug 5 Follow 1 to 4 for the other end of the LAN cable 6 Check continuit...

Страница 20: ...ure 21 Terminator connection example for bus topology Wiring length 250 900 m Wiring length Max 250 m Connection for free topology Total wiring length Max 450 m longest wiring length between one end t...

Страница 21: ...point is set by the BMS client PC Dual setting is available 2 VAV interlocking with air conditioning unit 1 Interlocks the ON OFF operations of the VAV units with those of the air conditioning units O...

Страница 22: ...BMS client PC manual override function Monitoring with the BMS client PC Individual monitoring 1 Monitors and controls the point data measuring setting operation and control data of Infilex VC from th...

Страница 23: ...s communication with LonTalk protocol Minor error Error 2 Figure 24 Descriptions of orange LED indications status IMPORTANT Do not press the LED button Operation of Infilex VC will be stopped and the...

Страница 24: ...opanel with address 1 connected to the Infilex VC will not work For two Neopanel connection provide Model QY7205CXXX1 for the address 1 and Model QY7205CXXX2 for the address 2 Address number is indica...

Страница 25: ...pull out the cables to make sure they are completely connected Optional Tools Figure 30 Modular crimper Part No DY7205A0002 Figure 31 Modular cable tester Part No DY7206A0000 Modular crimper See Fig...

Страница 26: ...it Messages VAV Object Device Documentation Node Object Configuration Properties CP Data File Transfer Configuration Properties Configuration Properties nc25 nciNetConfig SCPT_nwrk_cnfg nc165 nciDevMa...

Страница 27: ...temp_p nv16 nvoFlowControlPt SNVT_flow nv17 nvoSpaceTemp SNVT_temp_p nv3 nvoUnitSatus SNVT_hvac_status nv4 nvoBoxFlow SNVT_flow nv18 Configuration Properties nc49 nciSndHrtBt Mandatory nc60 nciSetPnts...

Страница 28: ..._obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default value...

Страница 29: ...SNVT name Valid range Default value Description SB RB MT nvoSpaceTemp SNVT_temp_p 10 00 to 50 00 C 327 67 Space temperature output inside differential pressure sensor nvoUnitStatus SNVT_hvac_status Un...

Страница 30: ...v_percent 0 000 to 100 000 0 000 Damper position output nvoFanSpeed SNVT_switch Fan output nvoReheater SNVT_lev_percentq 0 000 to 100 000 0 000 Reheater output nvoSpaceTemp2 SNVT_temp_p 10 00 to 50 00...

Страница 31: ...ration control parameter nciParaVav02 UCPTvavTempCtrl3 Temperature control parameter nciParaVav03 UCPTvavDischargeAirTempCtrl2 Duct inlet temperature optimization parameter nciParaVav04 UCPTvavFlowCtr...

Страница 32: ...Engineers ASHRAE TYGON is a trademark of Saint Gobain Performance Plastics Corporation Specifications are subject to change without notice Building Systems Company http www azbil com Rev 8 0 Mar 2018...

Отзывы: