In case of either 100 Vac or 200 Vac, the voltage which is applied 
to the load in the ON condition is VL = VS - (output voltage drop 
x number of units) (V).  Note that the load will not be activated 
unless VL is more than the minimum activating voltage of the 
load.
When more than 2 units are connected in series and are used in 
an AND switching circuit, the maximum number of units is 3. 
(Pay attention to the VS value shown in the figure below.)

In principle it is not possible to use more than 2 proximity 
switches in parallel as an OR switching circuit.  A parallel 
connection can be used only if A and B do not operate at the 
same time and if it is not necessary to hold the load.  However, 
consumption current (leakage current) will be multiplied by n (the 
number of proximity switches), and recovery failure will occur 
more easily.
If A and B operate at the same time and if it is necessary to 
retain the load, a parallel connection cannot be used.  Under 
these conditions, when A is turned ON, the voltage at both ends 
of A and B drops to approx. 10V, allowing load current to flow 
through A.  When a target object approaches B, the switching 
element of B cannot be activated because the voltage at both 
ends of B is too low.  When A is again turned OFF, the voltage 
at both ends of A and B increases to the power supply voltage, 
and at this point B can be turned ON for the first time. 
During this time, since there is a period (approx. 10 ms) when 
both A and B are OFF, the load is momentarily reset.  In order to 
retain the load, use a relay as shown below. 

When the proximity switch is connected to a load such as an 
electromagnetic switch, lamp or motor that causes inrush current, 
use the switch within the rated current, which includes the inrush 
current.

After the power is turned ON, it takes at most 80 ms until the 
proximity switch is ready for sensing. If the load and the proximity 
switch use different power supplies, be sure to turn the proximity 
switch ON before turning the load ON.

A minimal current flows as leakage current for operating the 
circuits even when the proximity switch is OFF.  Keep this in mind 
when turning off connected loads.

The minimum bend radius (R) of the cable is 3 times the cable 
diameter.  Take care not to bend the cable beyond this radius.  
Also, do not excessively bend the cable within 30 mm of the cable 
lead-in port.

Be sure to connect the proximity switch to the power supply via 
the load.  If the switch is connected directly to the power supply, 
the switch will be damaged. Also, output does not have polarity, 
so the load can be connected to either side of the power supply.  
However, we recommend connecting the load to the non-
grounded side to prevent short-circuiting of the power supply if a 
ground fault caused by damage to the proximity switch occurs.

Load

Load

Load

Load

Load

AC power 

supply voltage (Vs)

4.

Cautions for series or parallel connection

5.

Loads that cause inrush current

7.

Operation upon power ON

6.

Connection to power supply and load

8.

Influence of leakage current

9.

Minimum cable bend radius (R)

         Series connection (AND switching circuit)

         Parallel connection (OR switching circuit)

4.1

4.2

Before use, thoroughly read the “Precautions for use” and “Precautions for handling” in the Technical Guide 
on pages 

C-107 to C-113 as well as the instruction manual and product specification for this switch.

7

8

Содержание FL7M Series

Страница 1: ...n mode Setting indicator Catalog listing Exterior Sensing distance Operation mode Setting indicator Catalog listing Exterior Sensing distance Operation mode Setting indicator Catalog listing AC DC2 wi...

Страница 2: ...is used 25Hz When DC power supply is used 400Hz 10 max for the range of 25 to 70 C when 25 C is taken as standard temperature in sensing distance 10 to 60 C 4 000 Vac 50 60 Hz for 1minute Ni plated b...

Страница 3: ...24 Vdc Stainless steel SUS304 Brass Aluminum Copper Size d of one side of target object mm Voltage drop V Load current mA Leakage current mA Supply voltage v Size d of one side of target object mm Siz...

Страница 4: ...all length plus about 30 mm When using an angled connector dimension L2 is the overall length plus 20 mm Indicator lamp Indicator lamp Vinyl insulated cable PVC Vinyl insulated cable PVC 2000 min 2000...

Страница 5: ...connector type Toothed washer Hexagonal nut Indicator lamp Vinyl insulated cable PVC 300 min Toothed washer Hexagonal nut Indicator lamp Vinyl insulated cable PVC 300 min Toothed washer Hexagonal nut...

Страница 6: ...ed poorly the IP67 protection is lost or looseness occurs Fasten the connector securely by hand Gold plated brass Contact holder Glass lined polyester resin Housing Polyester elastomer Coupling Ni pla...

Страница 7: ...Leave space between the switch and surrounding metal as shown below Shaded areas indicate surrounding metal other than the target object When mounting proximity switches either parallel to or facing...

Страница 8: ...connected to a load such as an electromagnetic switch lamp or motor that causes inrush current use the switch within the rated current which includes the inrush current After the power is turned ON i...

Отзывы: